Friedrich CP08F10, CP06F10 manual Room AIR Conditioner Voltage Limits

Page 23

Troubleshooting Guide

ROOM AIR CONDITIONER VOLTAGE LIMITS

NAME PLATE RATING

MINIMUM

 

MAXIMUM

 

 

 

 

 

 

 

 

 

 

115V ± 10%

103.5V

 

 

126.5V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPLAINT

 

CAUSE

 

 

REMEDY

 

 

 

 

 

 

Fan motor will not run.

 

No power

 

Check voltage at outlet. Correct if none.

 

 

 

 

 

 

 

 

Wire disconnected or

 

Connect wire. Refer to wiring diagram for

 

 

connection loose

 

terminal identification. Repair or replace loose

 

 

 

 

 

terminal.

 

 

 

 

 

 

 

 

Capacitor (Discharge

 

Test capacitor.

 

 

capacitor before testing.)

 

Replace if not within ±10% of manufacturer's

 

 

 

 

 

rating. Replace if shorted, open, or damaged.

 

 

 

 

 

 

 

 

Will not rotate

 

Fan blade hitting shroud or blower wheel hitting

 

 

 

 

 

scroll. Re-align assembly.

 

 

 

 

 

Units using slinger ring condenser fans must

 

 

 

 

 

have 0.22~0.25 inch clearance to the base.

 

 

 

 

 

If necessary, shim up the bottom of the fan motor

 

 

 

 

 

with mounting screw(s).

 

 

 

 

 

Check fan motor bearings; if motor shaft will not

 

 

 

 

 

rotate, replace the motor.

 

 

 

 

 

 

Fan motor runs.

 

Revolves on overload

 

Check voltage. See limits on this page.

 

 

 

 

 

If not within limits, call an electrician.

 

 

 

 

 

Test capacitor.

 

 

 

 

 

Check bearings. Does the fan blade rotate

 

 

 

 

 

freely?

 

 

 

 

 

If not, replace fan motor.

 

 

 

 

 

Pay attention to any change from high speed to

 

 

 

 

 

low speed. If the speed does not change,

 

 

 

 

 

replace the motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23Room Air Conditioner

Image 23
Contents Room Air Conditioner Service and Parts Manual Table of Contents Be sure not to do Safety PrecautionsDo not modify power cord length Do not clean the air conditioner with water Outside Dimensions DimensionsSymbols Used in this Manual Operation Product SpecificationsRoom Air Conditioner Cabinet DisassemblyMechanical Parts Front GrilleAIR Guide and Blower Air Handling PartsCompressor Electrical PartsMotor Overload ProtectorCapacitor Power CordCapillary Tube EvaporatorPulling Vacuum Circuit Diagram Electronic Control Device Piping System Troubleshooting GuideUnit runs but poor cooling Troubleshooting GuideFails to Start Possible Trouble Electric Parts Troubleshooting GuideSet the Temp. setting to lower Temp Is the voltage No.16 CN-DISP1 on Main P.W.B Assy DC 5V? Room AIR Conditioner Voltage Limits Troubleshooting Guide Complaint Cause Remedy Exploded View Pwbpcb ASSEMBLY,DISPLAY Pwbpcb ASSEMBLY,DISPLA Use Factory Certified Parts