Certain air compressors can be converted from 120V to 240V operation. When converting an air compressor to 240V operation, the attached
Some models have a dual voltage motor, 120 and 240 volt. They are wired for 120 volt but can be converted to 240 volt operation. Instructions for connecting the motor for operation at 240 volt can be found printed on the label attached to the side of the motor.
Certain air compressor models can be operated on a 15 amp circuit if:
1.Voltage supply to circuit is normal.
2.Circuit is not used to supply any other electrical needs (lights, appliances, etc.)
3.Extension cords comply with specifications in this manual.
4.Circuit is equipped with a 15 amp circuit breaker or 15 amp time delay fuse.
Extension Cords
To avoid voltage drop and power loss to the motor, and to prevent overheating, use extra air hose instead of an extension cord.
If an extension cord must be used:
•use only a
•make sure the extension cord is in good condition.
•the extension cord should be no longer than 50 feet.
•the minimum wire size is 12 gauge (AWG). (Wire size increases as gauge number decreases. 10 AWG and 8 AWG may also be used. DO NOT USE 14 AWG or 16 AWG.)
Piping
Plastic or PVC pipe is not designed for use with compressed air. Regardless of its indicated pressure rating, plastic pipe can burst from air pressure. Use only metal pipe for air distribution lines.
If a pipe line is necessary, use pipe that is the same size as the air tank outlet. Piping that is too small will restrict the flow of air. If piping is over 100 feet long, use the next larger size. Bury underground lines below the frost line and avoid pockets where condensation
can gather and freeze. Apply pressure before under- ground lines are covered to make sure all pipe joints are free of leaks.
Connect the piping to the 3/8" NPT air outlet opening at the end of the air tank.
Additional Regulators and Controls
Since the air tank pressure is usually greater than that which is needed, a separate regulator is employed to control the air pressure ahead of any individual air driven device.
Separate air transformers which combine the function of air regulation, moisture and dirt removal should be used where applicable.
Break-in Procedure
Serious damage may result if the following
This procedure is required only once, before the air com- pressor is put into service.
1.Set the pressure switch "AUTO/O" lever in the "O" position for "Off".
2.Plug the power cord into the correct branch circuit receptacle.
3.Do not attach hose to outlet. Leave the outlet open to the atmosphere.
4.Turn the regulator clockwise, opening it fully, to prevent air pressure
5.Move the "AUTO/O" lever to "AUTO". The com- pressor will start.
6.RUN THE COMPRESSOR FOR 30 MINUTES. Make sure the regulator is open and there is no tank pressure
7.After 30 minutes, close the regulator by turning it counterclockwise. The air tank will fill to
D21245 | 10 — ENG |