APC 412 kVA, SYBT3 installation manual Meaning Corrective Action

Page 59

 

 

 

 

CHAPTER 4: MESSAGES

 

 

 

 

 

 

 

PowerView Message

 

Meaning

 

Corrective Action

 

 

 

 

 

 

General

Redundancy Restored.

 

Power module redundancy loss occurred

 

No corrective action necessary.

Status

 

 

and was restored. Either additional

 

 

(continued)

 

 

modules have been installed or the load

 

 

 

 

 

has been reduced.

 

 

 

 

 

 

 

 

 

Load is No Longer above

 

The load exceeded the load alarm

 

 

 

Alarm Threshold.

 

threshold. The situation has been

 

 

 

 

 

corrected because either the load

 

 

 

 

 

decreased or the threshold was

 

 

 

 

 

increased.

 

 

 

 

 

 

 

 

 

Min Runtime restored.

 

The system runtime dropped below the

 

 

 

 

 

configured minimum runtime and was

 

 

 

 

 

restored.

 

 

 

 

 

Either additional battery modules were

 

 

 

 

 

installed, the existing battery modules

 

 

 

 

 

were recharged, the load was reduced,

 

 

 

 

 

or the threshold was raised.

 

 

 

 

 

 

 

 

Module

Bad Battery Module.

 

A battery module failed and requires

 

Refer to module replacement

Failure

 

 

replacement.

 

procedure SYMMETRA RM

 

 

 

 

 

INSTALLATION MANUAL.

 

Bad Power Module.

 

A power module failed and requires

 

 

 

 

 

 

 

 

replacement.

 

 

 

 

 

 

 

 

 

Intelligence Module is

 

The MIM failed and requires

 

 

 

installed and failed.

 

replacement.

 

 

 

 

 

 

 

 

 

Redundant Intelligence

 

The RIM failed and requires

 

 

 

Module is installed and

 

replacement.

 

 

 

failed.

 

 

 

 

 

 

 

 

 

 

Threshold

Load is above kVA alarm

 

The load has exceeded the user

 

Option 1: Reduce the load.

Alarm

threshold.

 

specified load alarm threshold.

 

 

 

 

 

 

 

Option 2: Use the PowerView

 

 

 

 

 

interface to raise the alarm

 

 

 

 

 

threshold.

 

 

 

 

 

 

 

Redundancy has been

 

The UPS no longer detects redundant

 

Option 1: If possible, install

 

lost.

 

power modules. Either power module(s)

 

additional power modules.

 

 

 

failed or the load increased.

 

 

 

 

 

 

 

Option 2: Decrease the load.

 

 

 

 

 

Option 3: Disable the

 

 

 

 

 

redundancy alarm by setting

 

 

 

 

 

redundancy to zero.

 

 

 

 

 

(Startup>Setup>Alarms>

 

 

 

 

 

Redundancy>Zero)

 

 

 

 

 

 

19

Image 59
Contents APC Symmetra RM KVA UPS Installation Manual Page Safety and General Information Installation Conventions Used in this Manual General Equipment SafetyHandling Safety Battery Safety Deenergizing SafetyElectrical Safety Japan and 200 V Countries North America and 208 V CountriesEurope and 230 V Countries Countries Regulatory Agency ApprovalsDeclaration of Conformity Europe and 230 V Countries APC Contact Numbers and Support Limited WarrantyLife Support Policy Copyright and Trademark InformationSafety and General Information Japan Replacement Modules Model Number DescriptionAbout Your UPS EuropeExtended Run PowerDistribution OptionsFront View Component Identification Product OverviewRear View Component Identification UPS- Rear View SYPD3 installedMIM RIM System Block DiagramBasics Electrical Preparation Reminder ChecklistPurchase of System Site PreparationLbs kg Short-Term Battery Module Storage RequirementsWeights Length Width Height Measurements Inches cm Shipping & ReceivingThermal Dissipation Installation RequirementsPhysical Requirements Environmental RequirementsElectrical Requirements Remote Emergency Power Off RepoUnpacking Installing the UPSContents Moving the UPS to the Installation SiteInstallation Installing in a Four Post Rack Installation Installation Japan 200 Wiring the UPSPower Cord Ratings Switch Setting North America Installation Installation Completing the Installation Installation Connecting Load Equipment to the UPS Final Installation Checklist Replacing Power Modules Post Installation ProceduresReplacing Battery Modules Replacing Intelligence Modules Technical Reference Operational SpecificationsInput Specifications Compliance Specifications Output SpecificationsPhysical Specifications APC Symmetra RM 4-12 kVA UPS Page Messages Table of Contents Menu Description PowerViewNavigation Navigation Name Sound Function Keys FunctionsTurning on the UPS Powering Up the Load Equipment Powering Down the Load Equipment Bypass Operation Shown connected to Symmetra RM 2-6 kVA Language SettingTypical Programming Cable Getting Started Getting Started Menu Item Function Command ReferenceAccessories Menu Control MenuDisplay Function Options Display MenuLogging Menu Diagnostics MenuHelp Menu Status Menu Menu Item Function Options Setup MenuUPS ID PowerView Message Meaning Corrective Action TroubleshootingMessages Meaning Corrective Action Messages PowerView Message Meaning Corrective Action Messages Service Maintenance

412 kVA, SYBT3 specifications

The APC SYBT3 412 kVA is a high-performance uninterruptible power supply (UPS) system designed to provide reliable power solutions for critical applications in various industries. Ideal for data centers, telecom infrastructures, and other mission-critical operations, the APC SYBT3 is engineered to deliver a robust power backup to prevent downtime.

One of the main features of the APC SYBT3 is its impressive capacity of 412 kVA. This high power output ensures that it can support large loads while maintaining stable operations even during power fluctuations. The system is designed to handle essential equipment, guaranteeing that your operations continue without interruption.

The APC SYBT3 utilizes advanced technologies to optimize performance and energy efficiency. This includes an intelligent battery management system that prolongs battery life while ensuring reliable energy delivery. The UPS is equipped with a modern inverter that efficiently converts DC battery power to AC power, enabling seamless transitions during power outages.

Another key characteristic of the APC SYBT3 is its modular design, which allows for easy integration into existing systems. This modularity supports scalability, enabling users to expand their power capacity as needed without significant infrastructure changes. This feature is particularly beneficial for organizations that anticipate growth or fluctuations in power requirements.

The APC SYBT3 also boasts superior communications features, including an advanced monitoring interface. This feature allows for real-time tracking of power parameters, battery health, and operational status, ensuring users can address potential issues before they escalate. Remote monitoring capabilities enable IT personnel to manage the UPS from anywhere, enhancing operational efficiency.

In addition to its robust power performance, the APC SYBT3 offers a compact footprint, making it suitable for environments where space is limited. This design consideration ensures that large power needs can be met without sacrificing valuable real estate.

Overall, the APC SYBT3 412 kVA UPS represents a blend of advanced engineering, efficient power management, and user-friendly features. Its ability to provide seamless power continuity makes it an indispensable asset for organizations seeking to safeguard their critical operations against power interruptions.