CHAPTER 4: MESSAGES

 

PowerView Message

 

Meaning

 

Corrective Action

 

 

 

 

 

 

 

 

Threshold

Redundancy is below

 

Actual power module redundancy has

 

Option 1: If possible, install

 

Alarm

alarm threshold.

 

fallen below the user specified

 

additional power modules.

 

(continued)

 

 

redundancy alarm threshold. Either

 

 

 

 

 

 

power module(s) failed or the load has

 

Option 2: Decrease the load.

 

 

 

 

increased.

 

 

 

 

 

 

 

 

Option 3: Use the PowerView to

 

 

 

 

 

 

decrease the redundancy alarm

 

 

 

 

 

 

threshold.

 

 

 

 

 

 

(Startup>Setup>Alarms>

 

 

 

 

 

 

Redundancy)

 

 

 

 

 

 

 

 

 

Runtime is below alarm

 

The predicted runtime is lower than the

 

Option 1: Allow the battery

 

 

threshold.

 

user specified for the minimum runtime

 

modules to recharge.

 

 

 

 

alarm threshold. Either the battery

 

 

 

 

 

 

capacity has decreased or the load

 

Option 2: If possible, increase

 

 

 

 

increased.

 

the number of battery modules.

 

 

 

 

 

 

Option 3: Decrease the load.

 

 

 

 

 

 

Option 4: Use the PowerView to

 

 

 

 

 

 

decrease the minimum runtime

 

 

 

 

 

 

alarm threshold.

 

 

 

 

 

 

(Startup>Setup>Alarms>

 

 

 

 

 

 

Runtime)

 

 

 

 

 

 

 

 

Bypass

Bypass is not in range

 

The frequency and/or voltage are out of

 

Option 1: Decrease the

 

 

(either freq or voltage).

 

acceptable range for bypass. This

 

sensitivity to input frequency.

 

 

 

 

message occurs when the UPS is online

 

(Startup>Setup>OutputFreq)

 

 

 

 

and indicates that the bypass mode may

 

 

 

 

 

 

not be available if required. The system

 

Option 2: Correct input voltage

 

 

 

 

may start

 

to provide acceptable voltage

 

 

 

 

on-battery.

 

and/or frequency.

 

 

 

 

 

 

 

 

 

Bypass contactor stuck in

 

The UPS is positioned in the bypass

 

Call your contract service

 

 

bypass position.

 

position and cannot go on-line.

 

provider or APC Technical

 

 

 

 

 

 

Support.

 

 

Bypass contactor stuck in

 

The UPS is positioned in the on-line

 

 

 

 

 

 

 

 

on-line position.

 

position and cannot go to bypass.

 

 

 

 

 

 

 

 

 

 

 

UPS in bypass due to

 

The UPS has transferred to bypass

 

 

 

 

internal fault.

 

mode because a fault has occurred.

 

 

 

 

 

 

 

 

 

 

 

UPS in bypass due to

 

The load exceeded the system power

 

Option 1: Decrease the load.

 

 

overload.

 

capacity. The UPS has switched to

 

 

 

 

 

 

bypass mode.

 

Option 2: If possible, add power

 

 

 

 

 

 

modules to the system.

 

 

 

 

 

 

 

 

 

System is in Maintenance

 

The UPS is in bypass because the

 

No corrective action necessary.

 

 

Bypass.

 

maintenance bypass switch is in the On

 

 

 

 

 

 

position.

 

 

 

 

 

 

 

 

 

 

20

Image 60
Contents APC Symmetra RM KVA UPS Installation Manual Page Safety and General Information Installation General Equipment Safety Handling SafetyConventions Used in this Manual Deenergizing Safety Electrical SafetyBattery Safety North America and 208 V Countries Europe and 230 V CountriesJapan and 200 V Countries Regulatory Agency Approvals Declaration of Conformity Europe and 230 V CountriesCountries Limited Warranty Life Support PolicyCopyright and Trademark Information APC Contact Numbers and SupportSafety and General Information Replacement Modules Model Number Description About Your UPSEurope JapanPower DistributionOptions Extended RunProduct Overview Front View Component IdentificationUPS- Rear View SYPD3 installed Rear View Component IdentificationSystem Block Diagram MIM RIMBasics Reminder Checklist Purchase of SystemSite Preparation Electrical PreparationShort-Term Battery Module Storage Requirements Weights Length Width Height Measurements Inches cmShipping & Receiving Lbs kgInstallation Requirements Physical RequirementsEnvironmental Requirements Thermal DissipationRemote Emergency Power Off Repo Electrical RequirementsInstalling the UPS ContentsMoving the UPS to the Installation Site UnpackingInstallation Installing in a Four Post Rack Installation Installation Wiring the UPS Power Cord Ratings Switch Setting North AmericaJapan 200 Installation Installation Completing the Installation Installation Connecting Load Equipment to the UPS Final Installation Checklist Post Installation Procedures Replacing Battery ModulesReplacing Power Modules Replacing Intelligence Modules Operational Specifications Input SpecificationsTechnical Reference Output Specifications Physical SpecificationsCompliance Specifications APC Symmetra RM 4-12 kVA UPS Page Messages Table of Contents PowerView NavigationMenu Description Functions Navigation Name Sound Function KeysTurning on the UPS Powering Up the Load Equipment Powering Down the Load Equipment Bypass Operation Language Setting Shown connected to Symmetra RM 2-6 kVATypical Programming Cable Getting Started Getting Started Command Reference Accessories MenuControl Menu Menu Item FunctionDisplay Menu Display Function OptionsDiagnostics Menu Help MenuLogging Menu Status Menu Setup Menu Menu Item Function OptionsUPS ID Troubleshooting PowerView Message Meaning Corrective ActionMessages Meaning Corrective Action Messages PowerView Message Meaning Corrective Action Messages Service Maintenance

412 kVA, SYBT3 specifications

The APC SYBT3 412 kVA is a high-performance uninterruptible power supply (UPS) system designed to provide reliable power solutions for critical applications in various industries. Ideal for data centers, telecom infrastructures, and other mission-critical operations, the APC SYBT3 is engineered to deliver a robust power backup to prevent downtime.

One of the main features of the APC SYBT3 is its impressive capacity of 412 kVA. This high power output ensures that it can support large loads while maintaining stable operations even during power fluctuations. The system is designed to handle essential equipment, guaranteeing that your operations continue without interruption.

The APC SYBT3 utilizes advanced technologies to optimize performance and energy efficiency. This includes an intelligent battery management system that prolongs battery life while ensuring reliable energy delivery. The UPS is equipped with a modern inverter that efficiently converts DC battery power to AC power, enabling seamless transitions during power outages.

Another key characteristic of the APC SYBT3 is its modular design, which allows for easy integration into existing systems. This modularity supports scalability, enabling users to expand their power capacity as needed without significant infrastructure changes. This feature is particularly beneficial for organizations that anticipate growth or fluctuations in power requirements.

The APC SYBT3 also boasts superior communications features, including an advanced monitoring interface. This feature allows for real-time tracking of power parameters, battery health, and operational status, ensuring users can address potential issues before they escalate. Remote monitoring capabilities enable IT personnel to manage the UPS from anywhere, enhancing operational efficiency.

In addition to its robust power performance, the APC SYBT3 offers a compact footprint, making it suitable for environments where space is limited. This design consideration ensures that large power needs can be met without sacrificing valuable real estate.

Overall, the APC SYBT3 412 kVA UPS represents a blend of advanced engineering, efficient power management, and user-friendly features. Its ability to provide seamless power continuity makes it an indispensable asset for organizations seeking to safeguard their critical operations against power interruptions.