APC SYBT3, 412 kVA Wiring the UPS, Power Cord Ratings Switch Setting North America, Japan 200

Page 26

CHAPTER 4: INSTALLATION

Wiring the UPS

Verify that all branch circuit (mains) and low voltage (control) circuits are de-energized, and locked out before installing cables or making connections, whether in the junction box or to the UPS.

Verify that the battery modules are not installed in the UPS.

Do not install battery modules until you are ready to power up the UPS. Batteries can be permanently damaged if loaded prematurely.

Check national and local codes before wiring.

Wiring by a qualified electrician is required.

Select wire size and connectors according to national and local codes.

Use flexible metal conduit to make maintenance and service easier.

1.Set the input selection switch ￿ according to the table shown below.

Table 4: Power Cord Ratings

 

Switch Setting

North America

Ø Ø

and 208/240V

200/208/240VAC

(Ø- Ø -G)

 

Europe and

Ø N

230V

220/230/240VAC

(Ø- N –G)

 

Japan and

Ø Ø

200 V

200/208/240VAC

(Ø- Ø -G)

 

2. Make sure the input circuit breaker ￿ is in the OFF position.

22

Image 26
Contents APC Symmetra RM KVA UPS Installation Manual Page Safety and General Information Installation Conventions Used in this Manual General Equipment SafetyHandling Safety Battery Safety Deenergizing SafetyElectrical Safety Japan and 200 V Countries North America and 208 V CountriesEurope and 230 V Countries Countries Regulatory Agency ApprovalsDeclaration of Conformity Europe and 230 V Countries Copyright and Trademark Information Limited WarrantyLife Support Policy APC Contact Numbers and SupportSafety and General Information Europe Replacement Modules Model Number DescriptionAbout Your UPS JapanOptions PowerDistribution Extended RunProduct Overview Front View Component IdentificationUPS- Rear View SYPD3 installed Rear View Component IdentificationSystem Block Diagram MIM RIMBasics Site Preparation Reminder ChecklistPurchase of System Electrical PreparationShipping & Receiving Short-Term Battery Module Storage RequirementsWeights Length Width Height Measurements Inches cm Lbs kgEnvironmental Requirements Installation RequirementsPhysical Requirements Thermal DissipationRemote Emergency Power Off Repo Electrical RequirementsMoving the UPS to the Installation Site Installing the UPSContents UnpackingInstallation Installing in a Four Post Rack Installation Installation Japan 200 Wiring the UPSPower Cord Ratings Switch Setting North America Installation Installation Completing the Installation Installation Connecting Load Equipment to the UPS Final Installation Checklist Replacing Power Modules Post Installation ProceduresReplacing Battery Modules Replacing Intelligence Modules Technical Reference Operational SpecificationsInput Specifications Compliance Specifications Output SpecificationsPhysical Specifications APC Symmetra RM 4-12 kVA UPS Page Messages Table of Contents Menu Description PowerViewNavigation Functions Navigation Name Sound Function KeysTurning on the UPS Powering Up the Load Equipment Powering Down the Load Equipment Bypass Operation Language Setting Shown connected to Symmetra RM 2-6 kVATypical Programming Cable Getting Started Getting Started Control Menu Command ReferenceAccessories Menu Menu Item FunctionDisplay Menu Display Function OptionsLogging Menu Diagnostics MenuHelp Menu Status Menu Setup Menu Menu Item Function OptionsUPS ID Troubleshooting PowerView Message Meaning Corrective ActionMessages Meaning Corrective Action Messages PowerView Message Meaning Corrective Action Messages Service Maintenance