Bryant R-22 III. System Cleanup After Burnout, IV. Compressor Removal and Replacement

Page 27

Most common motor failures are due to either an open, grounded, or short circuit. Directions below are specifically for single-phase units, however, they also apply to 3-phase compressors. When a single-phase compressor fails to start or run, 3 tests can help determine the problem. First, all possible external causes should be eliminated, such as overloads, improper voltage, pressure equal- ization, defective capacitor(s), relays, wiring, and so forth. Com- pressor has internal line-break overload, so be certain it is closed.

OPEN CIRCUIT

To determine if any winding has a break in the internal wires and current is unable to pass through:

1.Be sure all power is off.

2.Discharge all capacitors.

3.Remove wires from terminals C, S and R.

4.Check resistance from C-R, C-S and R-S using an ohmme- ter on 0-1000 ohm scale.

Because winding resistances are usually less than 10 ohms, each reading appears to be approximately 0 ohm. If resistance remains at 1000 ohms, an open or break exists, and compressor should be replaced.

CAUTION: Be sure internal line-break overload is not temporarily open.

GROUND CIRCUIT

To determine if a wire has broken or come in direct contact with shell, causing a direct short to ground:

1.Be sure all power is off.

2.Discharge all capacitors.

3.Remove wires from terminals C, S, and R.

4.On hermetic compressors, allow crankcase heaters to re- main on for several hours before checking motor to ensure windings are not saturated with refrigerant.

5.Use an ohmmeter on R X 10,000 ohm scale. A megohm- meter may be used in place of ohmmeter. Follow manufac- turer’s instructions.

6.Place 1 meter probe on ground or on compressor shell. Make a good metal-to-metal contact. Place other probe on terminals C, S, and R in sequence.

7.Note meter scale.

8.If reading of zero or low resistance is obtained, motor is grounded. Replace compressor.

A 1 ton or less capacity compressor is probably grounded if resistance is below 1 million ohms. On larger-sized, single-phase compressors, resistance to ground should not be less than 1000 ohms per volt of operating voltage.

Example:

230 volts X 1000 ohms/volt = 230,000 ohms minimum.

SHORT CIRCUIT

To determine if any wires within windings have broken through their insulation and made contact with other wires, thereby shorting all or part of the winding(s), be sure the following conditions are met:

1.Correct motor-winding resistances must be known before testing, either from previous readings or from manufactur- er’s specifications.

2.Temperature of windings must be as specified, usually about 70°F.

3.Resistance-measuring instrument must have an accuracy within ± 5 to 10 percent. This requires an accurate ohmme- ter, such as a Wheatstone bridge or null balance-type instrument.

—27—

4.Motor must be dry or free from direct contact with liquid refrigerant.

MAKE THIS CRITICAL TEST

(Not advisable unless above conditions are met.)

1.Be sure all power is off.

2.Discharge all capacitors.

3.Remove wires from terminals C, S, and R.

4.Place instrument probes together and determine probe and lead wire resistance.

5.Check resistance readings from C-R, C-S, and R-S.

6.Subtract instrument probe and lead resistance from each reading.

If any reading is within ± 20 percent of known resistance, motor is probably normal. Usually a considerable difference in reading is noted if a turn-to-turn short is present.

III. SYSTEM CLEANUP AFTER BURNOUT

CAUTION: Turn off all power to unit before proceed- ing. Wear safety glasses and gloves when handling refrigerants. Acids formed as a result of motor burnout can cause burns.

NOTE: To analyze level of suspected contamination from com- pressor burnout, use Total Test. See your distributor/branch.

Some compressor electrical failures can cause motor to overheat. When this occurs, by-products, which include sludge, carbon, and acids, can contaminate system. If burnout is severe enough, system must be cleaned before replacement compressor is installed. The 2 types of motor burnout are classified as mild or severe.

In mild burnout, there is little or no detectable odor. Compressor oil is clear or slightly discolored. An acid test of compressor oil will be negative. This type of failure is treated the same as mechanical failure. Liquid-line strainer should be removed and liquid-line filter drier installed.

In a severe burnout, there is a strong, pungent, rotten-egg odor. Compressor oil is very dark. Evidence of burning may be present in tubing connected to compressor. An acid test of compressor oil will be positive. Complete system must be reverse flushed with refrigerant. Check-Flo-Rater™ or TXV must be cleaned or re- placed. In a heat pump, accumulator and reversing valve are replaced. These components are also removed and bypassed during reverse-flushing procedure. Remove and discard liquid-line strainer. After system is reassembled, install liquid-line and suction-line filter driers. Run system for 2 hrs. Discard both driers and install new liquid-line drier only.

IV. COMPRESSOR REMOVAL AND REPLACEMENT

Once it is determined that compressor has failed and the reason established, compressor must be replaced.

CAUTION: Wear safety glasses and gloves when han- dling refrigerants and when using brazing torch.

1.Shut off all power to unit.

2.Remove and recover all refrigerant from system until pressure gages read zero psi. Use all service ports.

3.Disconnect electrical leads from compressor. Disconnect or remove crankcase heater and remove compressor-holddown bolts.

4.Cut compressor from system with tubing cutters. Do not use brazing torch for compressor removal. Oil vapor may ignite when compressor is disconnected.

Image 27
Contents Safety Considerations Table of ContentsIII. Seacoast for AIR Conditioners only II. ADD-ON Replacement RetrofitAccessory Descriptions VIII. LOW-AMBIENT Pressure SwitchXI. Support Feet II. Interconnecting Tubing SizingIX. Wind Baffle Coastal FilterMatl 20 GA Steel Matl 18 GA SteelBaffle Left Unit Size Unit HeightSmall MediumWind Baffle Dimensions for Cube Units Estimated Percentage of Nominal COOLING-CAPACITY LossesIII. Metering Device Sizing Calculation of Indoor Piston no IV. LIQUID-LINE Solenoid and Tubing CONFIGU- RationFitting Losses in Equivalent FT ExampleVI -SPEED Applications Common Piston SizesLIQUID-LINE Solenoid KIT Part Numbers Charging InformationPositions 6 through 10-Serial Number II. Serial Number IdentificationIII. Information PLATE-RELIANT Products II. Remove FAN-MOTOR ASSEMBLY-BEFORE 1/1/92Cabinet Remove TOP COVER-BEFORE 1/1/92VI. Remove FAN-MOTOR ASSEMBLY-AFTER 1/1/92 Basic Cabinet Designs Electrical Aluminum WireII. Contactors Information PlateStart Capacitors and PTC Devices III. CapacitorsIV. Cycle Protector Temporary Capacitance BoostCrankcase Heater VI. TIME-DELAY RelayLOW-PRESSURE Switch VII. Pressure SwitchesIX. DEFROST-CONTROL Board HIGH-PRESSURE SwitchLIQUID-LINE Pressure Switch VIII. Defrost ThermostatsCES0110063 CES0130024 CES0110063 Defrost ControlDefrost Control SPEED-UP Timing SE SPEED-UPParameter Minimum Maximum Defrost Timer Settings XI. Service Alarm Control BoardFAN Motors XII. Outdoor Thermostats OF2 CESO130076-00Aeroquiet System and Aeromax TOP FAN Position XIII. Compressor Plug Service Alarm Wiring ConnectionsXIV. LOW-VOLTAGE Terminals Reciprocating CompressorMechanical Failures II. Electrical Failures IV. Compressor Removal and Replacement III. System Cleanup After BurnoutIII. Discharge Thermostat Copeland Scroll Compressor FeaturesII. Troubleshooting Compressor OIL RechargeII. Compressor Protection Millennium Scroll Compressor FeaturesIII. Troubleshooting IV. Scroll COMPRESSOR, 3-PHASE MonitorCont HPS LPS IFR Indoor External Power Supply 24Cont Equip GND CAP OFM Logic CESO130075Ambient Temperature for HIGH- LOW-SPEED Operation Function Light Code and Display Location IV. Major Components III. Factory DefaultsFactory Defaults Compressor PTC RangesVI. Troubleshooting TWO-SPEED Compressor Winding Resistance AT 70F ±LED FUNCTION/MALFUNCTION Lights II. Leak Detection Refrigeration System Refrigeration CycleLow-Speed Windings All 24V PIN Connection TroubleshootingIII. Brazing Cooling CycleIV. Service Valves Service ValvesReliant Products Except 1992 Production Reliant and Cube Products ProducedVI. Reversing Valve VII. THERMOSTATIC-EXPANSION Valves TXV Reversing ValveIX. Coil Removal TXV Superheat Setting AT Outlet of Evaporator CoilInstallation TXV Type Product Usage Superheat Setting VIII. THERMOSTATIC-EXPANSION Valve BI-FLOW TXVTXV in Cooling Mode XIV. Checking Charge XI. AccumulatorXII. Contaminant Removal XIII. System ChargingSubcooling Charging Method Required Vapor Temperature FSuperheat Charging Table Superheat Charging MethodCare and Maintenance Reliant AIR ConditionersReliant Heat Pumps Required LIQUID-LINE Temperature Page AIR Conditioner Troubleshooting Chart Heat Pump TROUBLESHOOTING-COOLING Cycle Heat Pump TROUBLESHOOTING-HEATING Cycle
Related manuals
Manual 84 pages 49.8 Kb