Bryant R-22 service manual TXV Superheat Setting AT Outlet of Evaporator Coil, IX. Coil Removal

Page 41

TABLE 20—TXV SUPERHEAT SETTING AT OUTLET OF EVAPORATOR COIL

INSTALLATION

TXV TYPE

PRODUCT USAGE

SUPERHEAT SETTING

Field Accessory

RPB/HSO

Air Conditioner Indoor Unit

10°

Field Accessory

RPB/HSO

Heat Pump Indoor Unit

Field Accessory/Factory-Installed

HSO

Indoor Fan Coil Unit

Factory-Installed

HSO

2-Speed Heat Pump Outdoor Unit

Factory-Shipped/Field-Installed

HSO

2-Speed Indoor Unit

 

 

 

 

FROM

 

TO

 

TO INDOOR COIL

ACCUMULATOR

 

OUTDOOR

 

 

VIA SERVICE VALVE

COIL

 

 

ON OUTDOOR COIL

 

 

INSULATE

 

 

 

 

FOR

TP-2

TP-4

TP-3

ACCURATE

 

READING

INSULATE FOR

ACCURATE TP-1

READING

FROM COMPRESSOR

DISCHARGE LINE

ELECTRONIC

THERMOMETER

A88341

Fig. 48—Reversing Valve (Heating Mode, Solenoid De-

Energized)

Hard Shutoff (HSO)—Has no bleed port and allows no bleed- through after system shutdown. No pressure equalization occurs. Because of unequalized system pressures, a start capacitor and relay must be installed on single-phase reciprocating compressors to start the compressor.

See Table 20 for TXV superheat settings. These settings are factory set and are not field adjustable. Table 17 settings are for Bryant-approved accessories and factory-installed TXVs only.

VIII. THERMOSTATIC-EXPANSION VALVE (BI-FLOW TXV)

The standard TXV is a metering device that is used in condensing and heat pump systems to adjust to changing load conditions by maintaining a preset superheat temperature at the outlet of the evaporator coil. The volume of refrigerant metered through the valve seat is dependent upon:

1.Superheat temperature sensed by cap-tube sensing bulb on suction tube at outlet of evaporator coil. As long as this bulb and cap tube contains some liquid refrigerant, this tempera- ture is converted into suction pressure pushing downward on the diaphragm, which tends to open the valve via the pushrods.

2.The suction pressure at the outlet of the evaporator coil is transferred via the external equalizer tube to the underside of the diaphragm.

3.The needle valve on the pin Bryant is spring-loaded, which also exerts pressure on the underside of the diaphragm via the pushrods, which tends to close the valve. Therefore, bulb pressure equals evaporator pressure (at outlet of coil) plus spring pressure. If the load increases, the temperature increases at the bulb, which increases the pressure on the topside of the diaphragm, which pushes the pin Bryant away from the seat, opening the valve and increasing the flow of refrigerant. The increased refrigerant flow causes

—41—

increased leaving evaporator pressure, which is transferred via the equalizer tube to the underside of the diaphragm. This tends to cause the pin-Bryant spring pressure to close the valve. The refrigerant flow is effectively stabilized to the load demand with negligible change in superheat. The bi-flow TXV is used on split-system heat pumps. In the cooling mode, the TXV operates the same as the standard TXV previously explained. (See Fig. 49.)

However, when the system is switched to the heating mode of operation, the refrigerant flow is reversed. The bi-flow TXV has an additional internal-check valve and external tubing. (See Fig. 50.) These additions allow the refrigerant to bypass the TXV when refrigerant flow is reversed with only a 1- to 2-psig pressure drop through the device. When the heat pump switches to the defrost mode, the refrigerant flows through a completely open (unthrottled) TXV, and the bulb senses the residual heat of the outlet tube of the coil that had been operating in the heating mode (about 85°F and 155 psig). This temporary, unthrottled valve decreases the indoor-pressure drop, which in turn increases the refrigerant-flow rate, decreases overall defrost time, and enhances defrost efficiency.

IX. COIL REMOVAL

Coils on this family of units are easy to remove, if required for compressor removal or replacement coil.

CAUTION: Wear safety glasses and gloves when han- dling refrigerants.

To remove or replace coil:

1.Shut off all power to unit.

2.Remove and recover refrigerant from system through ser- vice valves.

3.Remove top cover. (See Remove Top Cover section.)

4.Remove screws in base pan to coil grille.

5.Remove coil grille from unit.

6.Remove screws on corner-post (Reliant) service-valve panel (Cube unit) holding coil-tube sheet.

CAUTION: Cut tubes to reduce the possibility of fire and personal injury.

7.Use midget-tubing cutter to cut liquid and vapor lines at both sides of coil. Cut in convenient location for easy reassembly with copper-slip couplings.

8.Lift coil vertically from basepan. Place aside carefully.

9.Reverse procedure to reinstall coil.

X. LIQUID-LINE STRAINER (HEAT PUMPS ONLY)

The liquid-line strainer is upstream of the heating piston. The strainer catches debris in the liquid line during heating mode. If it becomes plugged, system operation and pressure become abnor- mal, and the compressor may become hot and cycle off on the overloads or pressure relief.

Image 41
Contents Safety Considerations Table of ContentsAccessory Descriptions II. ADD-ON Replacement RetrofitVIII. LOW-AMBIENT Pressure Switch III. Seacoast for AIR Conditioners onlyIX. Wind Baffle II. Interconnecting Tubing SizingCoastal Filter XI. Support FeetMatl 20 GA Steel Matl 18 GA SteelSmall Unit Size Unit HeightMedium Baffle LeftIII. Metering Device Sizing Wind Baffle Dimensions for Cube UnitsEstimated Percentage of Nominal COOLING-CAPACITY Losses Fitting Losses in Equivalent FT IV. LIQUID-LINE Solenoid and Tubing CONFIGU- RationExample Calculation of Indoor Piston noLIQUID-LINE Solenoid KIT Part Numbers Common Piston SizesCharging Information VI -SPEED ApplicationsPositions 6 through 10-Serial Number II. Serial Number IdentificationCabinet II. Remove FAN-MOTOR ASSEMBLY-BEFORE 1/1/92Remove TOP COVER-BEFORE 1/1/92 III. Information PLATE-RELIANT ProductsVI. Remove FAN-MOTOR ASSEMBLY-AFTER 1/1/92 Basic Cabinet Designs Electrical Aluminum WireII. Contactors Information PlateStart Capacitors and PTC Devices III. CapacitorsIV. Cycle Protector Temporary Capacitance BoostCrankcase Heater VI. TIME-DELAY RelayLOW-PRESSURE Switch VII. Pressure SwitchesLIQUID-LINE Pressure Switch HIGH-PRESSURE SwitchVIII. Defrost Thermostats IX. DEFROST-CONTROL BoardCES0110063 CES0130024 CES0110063 Defrost ControlParameter Minimum Maximum Defrost Control SPEED-UP Timing SESPEED-UP FAN Motors Defrost Timer SettingsXI. Service Alarm Control Board XII. Outdoor Thermostats OF2 CESO130076-00Aeroquiet System and Aeromax TOP FAN PositionXIII. Compressor Plug Service Alarm Wiring ConnectionsMechanical Failures XIV. LOW-VOLTAGE TerminalsReciprocating Compressor II. Electrical Failures IV. Compressor Removal and Replacement III. System Cleanup After BurnoutII. Troubleshooting Copeland Scroll Compressor FeaturesCompressor OIL Recharge III. Discharge ThermostatIII. Troubleshooting Millennium Scroll Compressor FeaturesIV. Scroll COMPRESSOR, 3-PHASE Monitor II. Compressor ProtectionCont Equip GND CAP OFM Logic IFR Indoor External Power Supply 24CESO130075 Cont HPS LPSAmbient Temperature for HIGH- LOW-SPEED Operation Function Light Code and Display Location Factory Defaults III. Factory DefaultsCompressor PTC Ranges IV. Major ComponentsLED FUNCTION/MALFUNCTION Lights VI. TroubleshootingTWO-SPEED Compressor Winding Resistance AT 70F ± II. Leak Detection Refrigeration System Refrigeration CycleLow-Speed Windings III. Brazing 24V PIN Connection TroubleshootingCooling Cycle AllIV. Service Valves Service ValvesVI. Reversing Valve Reliant Products Except 1992 ProductionReliant and Cube Products Produced VII. THERMOSTATIC-EXPANSION Valves TXV Reversing ValveInstallation TXV Type Product Usage Superheat Setting TXV Superheat Setting AT Outlet of Evaporator CoilVIII. THERMOSTATIC-EXPANSION Valve BI-FLOW TXV IX. Coil RemovalTXV in Cooling Mode XII. Contaminant Removal XI. AccumulatorXIII. System Charging XIV. Checking ChargeSuperheat Charging Table Required Vapor Temperature FSuperheat Charging Method Subcooling Charging MethodReliant Heat Pumps Care and MaintenanceReliant AIR Conditioners Required LIQUID-LINE Temperature Page AIR Conditioner Troubleshooting Chart Heat Pump TROUBLESHOOTING-COOLING Cycle Heat Pump TROUBLESHOOTING-HEATING Cycle
Related manuals
Manual 84 pages 49.8 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.