Bryant R-22 service manual VII. Pressure Switches, LOW-PRESSURE Switch

Page 17

OPERATING

 

 

5 MIN

TIME

 

 

 

 

 

T1

_

T2

BLK DENOTES CLOSED CONTACTS

HN67ZA002

A91436

3

OPERATING

5 MIN

SEC

TIME

 

T1

 

 

_

 

 

T2

 

 

BLK DENOTES CLOSED CONTACTS

HN67PA025, HN67ZA003, HN67ZA008

A91437

Fig. 16—Cycle-Protector Sequence

CUT YELLOW WIRE

BETWEEN CONTACTOR AND

LOW-PRESSURE SWITCH

Y

 

YEL

 

SAFETY

 

YEL

 

 

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINAL

 

YEL

 

BOARD

 

 

 

 

 

CONNECTION

 

 

 

 

 

 

 

 

 

 

 

YEL

C

BRN

C

VIO

 

TERMINAL

 

 

BOARD

 

 

CONNECTION

T1

LOGIC

T3

BLK

T2

A88415

Fig. 17—Cycle-Protector Wiring

DSV

CH

11

21

A91426

Fig. 18—Wiring for Single-Pole Contactor

thereby improving the efficiency of the system. The sequence of operation is that on closure of the wall thermostat and at the end of a fixed on-delay of 1 sec, the fan relay is energized. When the thermostat is satisfied, an off-delay is initiated. When the fixed delay of 90 ± 20 sec is completed, the fan relay is de-energized and fan motor stops. If the wall thermostat closes during this delay, the

—17—

TDR is reset, and the fan relay remains energized. The TDR is a 24v device that operates within a range of 15 to 30v and draws about 0.5 amps.

If the blower runs continuously instead of cycling off when the fan switch is set on AUTO, the TDR is probably defective and must be replaced.

VII. PRESSURE SWITCHES

Pressure switches are protective devices wired into control circuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. Depending on unit model, you may find a low- and/or high-pressure switch in system.

LOW-PRESSURE SWITCH

Located on suction line of condensing unit only, the low-pressure switch protects against low-suction pressures caused by such events as loss of charge, low airflow across indoor coil, dirty filters, etc. It opens on a pressure drop at about 27 psi. If system pressure is above this, switch should be closed. To check switch, turn off all power to unit, disconnect leads on switch, and apply ohmmeter leads across switch. You should have continuity on a good switch. Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gages read 0 psi.

Image 17
Contents Safety Considerations Table of ContentsAccessory Descriptions II. ADD-ON Replacement RetrofitVIII. LOW-AMBIENT Pressure Switch III. Seacoast for AIR Conditioners onlyIX. Wind Baffle II. Interconnecting Tubing SizingCoastal Filter XI. Support FeetMatl 20 GA Steel Matl 18 GA SteelSmall Unit Size Unit HeightMedium Baffle LeftIII. Metering Device Sizing Wind Baffle Dimensions for Cube UnitsEstimated Percentage of Nominal COOLING-CAPACITY Losses Fitting Losses in Equivalent FT IV. LIQUID-LINE Solenoid and Tubing CONFIGU- RationExample Calculation of Indoor Piston noLIQUID-LINE Solenoid KIT Part Numbers Common Piston SizesCharging Information VI -SPEED ApplicationsPositions 6 through 10-Serial Number II. Serial Number IdentificationCabinet II. Remove FAN-MOTOR ASSEMBLY-BEFORE 1/1/92Remove TOP COVER-BEFORE 1/1/92 III. Information PLATE-RELIANT ProductsVI. Remove FAN-MOTOR ASSEMBLY-AFTER 1/1/92 Basic Cabinet Designs Electrical Aluminum WireII. Contactors Information PlateStart Capacitors and PTC Devices III. CapacitorsIV. Cycle Protector Temporary Capacitance BoostCrankcase Heater VI. TIME-DELAY RelayLOW-PRESSURE Switch VII. Pressure SwitchesLIQUID-LINE Pressure Switch HIGH-PRESSURE SwitchVIII. Defrost Thermostats IX. DEFROST-CONTROL BoardCES0110063 CES0130024 CES0110063 Defrost ControlParameter Minimum Maximum Defrost Control SPEED-UP Timing SESPEED-UP FAN Motors Defrost Timer SettingsXI. Service Alarm Control Board XII. Outdoor Thermostats OF2 CESO130076-00Aeroquiet System and Aeromax TOP FAN PositionXIII. Compressor Plug Service Alarm Wiring ConnectionsMechanical Failures XIV. LOW-VOLTAGE TerminalsReciprocating Compressor II. Electrical Failures IV. Compressor Removal and Replacement III. System Cleanup After BurnoutII. Troubleshooting Copeland Scroll Compressor FeaturesCompressor OIL Recharge III. Discharge ThermostatIII. Troubleshooting Millennium Scroll Compressor FeaturesIV. Scroll COMPRESSOR, 3-PHASE Monitor II. Compressor ProtectionCont Equip GND CAP OFM Logic IFR Indoor External Power Supply 24CESO130075 Cont HPS LPSAmbient Temperature for HIGH- LOW-SPEED Operation Function Light Code and Display Location Factory Defaults III. Factory DefaultsCompressor PTC Ranges IV. Major ComponentsLED FUNCTION/MALFUNCTION Lights VI. TroubleshootingTWO-SPEED Compressor Winding Resistance AT 70F ± II. Leak Detection Refrigeration System Refrigeration CycleLow-Speed Windings III. Brazing 24V PIN Connection TroubleshootingCooling Cycle AllIV. Service Valves Service ValvesVI. Reversing Valve Reliant Products Except 1992 ProductionReliant and Cube Products Produced VII. THERMOSTATIC-EXPANSION Valves TXV Reversing ValveInstallation TXV Type Product Usage Superheat Setting TXV Superheat Setting AT Outlet of Evaporator CoilVIII. THERMOSTATIC-EXPANSION Valve BI-FLOW TXV IX. Coil RemovalTXV in Cooling Mode XII. Contaminant Removal XI. AccumulatorXIII. System Charging XIV. Checking ChargeSuperheat Charging Table Required Vapor Temperature FSuperheat Charging Method Subcooling Charging MethodReliant Heat Pumps Care and MaintenanceReliant AIR Conditioners Required LIQUID-LINE Temperature Page AIR Conditioner Troubleshooting Chart Heat Pump TROUBLESHOOTING-COOLING Cycle Heat Pump TROUBLESHOOTING-HEATING Cycle
Related manuals
Manual 84 pages 49.8 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.