Bryant R-22 Fitting Losses in Equivalent FT, Example, Calculation of Indoor Piston no

Page 7

A

90° STD

B

90° LONG RAD

C

 

45° STD

 

A92498

Fig. 3—Tube Bend Losses

 

TABLE 5—FITTING LOSSES IN EQUIVALENT FT

 

 

 

 

TUBE SIZE OD

REFERENCE DIAGRAM IN FIG. 1

(IN.)

A

B

C

5/8

1.6

1.0

0.8

3/4

1.8

1.2

0.9

7/8

2.0

1.4

1.0

1-1/8

2.6

1.7

1.3

 

 

 

 

NOTE: If total equivalent horizontal length is 100 ft or longer, both indoor and outdoor pistons must be increased 1 full piston size, in addition to changes required by Tables 6 and 7.

After finding appropriate change in piston size, add or subtract the change from original piston number. If piston size is decreased, round new piston number down to nearest common piston number found in Table 8. If piston size is increased, round new piston number up to nearest common piston number found in Table 8.

—7—

EXAMPLE:

An 042 size heat pump is 75 ft above an 042 size fan coil. The 042 size heat-pump presale literature specifies a size 80 indoor piston and size 63 outdoor piston.

To establish correct indoor piston size for a 75 ft vertical separation, refer to Table 6. For a 75 ft equivalent line length, the piston change is -5. Therefore subtract 5 from the original indoor piston size of 80:

80 – 5 = 75

Table 8 provides common piston sizes. In this instance, 75 is not listed, therefore round DOWN to next piston size, which would be 74.

To establish correct outdoor piston size for a 75 ft vertical separation, refer to Table 7. For a 75 ft equivalent line length, the piston change is +4. Therefore add 4 to the original outdoor piston size of 63:

63 + 4 = 67

Since 67 is listed in Table 8, that is the piston which should be used. If a 67 size piston were not listed, it would be necessary to round UP to next piston size.

TXVs may be used instead of pistons for indoor-metering devices. Some fan coils are equipped with a hard-shutoff, bi-flow TXV standard, and no change is required. When sizing an accessory TXV for long-line applications, TXV should be the same nominal tonnage as outdoor unit. Refer to presale literature for kit part numbers.

TABLE 6—CALCULATION OF INDOOR PISTON NO.

OUTDOOR UNIT ABOVE INDOOR

FT

PISTON CHANGE

0-25

0

26-50

-3

51-75

-5

76-100

-7

101-125

-9

126-150

-10

OUTDOOR UNIT BELOW INDOOR

FT

PISTON CHANGE

0-25

0

26-50

+4

TABLE 7—CALCULATION OF OUTDOOR PISTON NO.

OUTDOOR UNIT ABOVE INDOOR

FT

PISTON CHANGE

0-50

0

51-75

+4

76-100

+6

101-125

+8

126-150

+10

OUTDOOR UNIT BELOW INDOOR

FT

PISTON CHANGE

0-50

0

 

 

IV. LIQUID-LINE SOLENOID AND TUBING CONFIGU- RATION

There are 2 types of liquid-line solenoids: 1 for single-flow applications and the other for bi-flow applications. The purpose of having 2 solenoids is to minimize the valve internal-pressure drop in accordance with refrigerant flow direction and liquid migration to the compressor. The bi-flow solenoid is designed to have minimal refrigerant-pressure drop in either flow direction, which makes it suitable for heat pump usage. Refer to Table 9 for liquid-line solenoid kit part numbers.

Image 7
Contents Safety Considerations Table of ContentsIII. Seacoast for AIR Conditioners only II. ADD-ON Replacement RetrofitAccessory Descriptions VIII. LOW-AMBIENT Pressure SwitchXI. Support Feet II. Interconnecting Tubing SizingIX. Wind Baffle Coastal FilterMatl 20 GA Steel Matl 18 GA SteelBaffle Left Unit Size Unit HeightSmall MediumEstimated Percentage of Nominal COOLING-CAPACITY Losses Wind Baffle Dimensions for Cube UnitsIII. Metering Device Sizing Calculation of Indoor Piston no IV. LIQUID-LINE Solenoid and Tubing CONFIGU- RationFitting Losses in Equivalent FT ExampleVI -SPEED Applications Common Piston SizesLIQUID-LINE Solenoid KIT Part Numbers Charging InformationPositions 6 through 10-Serial Number II. Serial Number IdentificationIII. Information PLATE-RELIANT Products II. Remove FAN-MOTOR ASSEMBLY-BEFORE 1/1/92Cabinet Remove TOP COVER-BEFORE 1/1/92VI. Remove FAN-MOTOR ASSEMBLY-AFTER 1/1/92 Basic Cabinet Designs Electrical Aluminum WireII. Contactors Information PlateStart Capacitors and PTC Devices III. CapacitorsIV. Cycle Protector Temporary Capacitance BoostCrankcase Heater VI. TIME-DELAY RelayLOW-PRESSURE Switch VII. Pressure SwitchesIX. DEFROST-CONTROL Board HIGH-PRESSURE SwitchLIQUID-LINE Pressure Switch VIII. Defrost ThermostatsCES0110063 CES0130024 CES0110063 Defrost ControlSPEED-UP Defrost Control SPEED-UP Timing SEParameter Minimum Maximum XI. Service Alarm Control Board Defrost Timer SettingsFAN Motors XII. Outdoor Thermostats OF2 CESO130076-00Aeroquiet System and Aeromax TOP FAN PositionXIII. Compressor Plug Service Alarm Wiring ConnectionsReciprocating Compressor XIV. LOW-VOLTAGE TerminalsMechanical Failures II. Electrical Failures IV. Compressor Removal and Replacement III. System Cleanup After BurnoutIII. Discharge Thermostat Copeland Scroll Compressor FeaturesII. Troubleshooting Compressor OIL RechargeII. Compressor Protection Millennium Scroll Compressor FeaturesIII. Troubleshooting IV. Scroll COMPRESSOR, 3-PHASE MonitorCont HPS LPS IFR Indoor External Power Supply 24Cont Equip GND CAP OFM Logic CESO130075Ambient Temperature for HIGH- LOW-SPEED Operation Function Light Code and Display Location IV. Major Components III. Factory DefaultsFactory Defaults Compressor PTC RangesTWO-SPEED Compressor Winding Resistance AT 70F ± VI. TroubleshootingLED FUNCTION/MALFUNCTION Lights II. Leak Detection Refrigeration System Refrigeration CycleLow-Speed Windings All 24V PIN Connection TroubleshootingIII. Brazing Cooling CycleIV. Service Valves Service ValvesReliant and Cube Products Produced Reliant Products Except 1992 ProductionVI. Reversing Valve VII. THERMOSTATIC-EXPANSION Valves TXV Reversing ValveIX. Coil Removal TXV Superheat Setting AT Outlet of Evaporator CoilInstallation TXV Type Product Usage Superheat Setting VIII. THERMOSTATIC-EXPANSION Valve BI-FLOW TXVTXV in Cooling Mode XIV. Checking Charge XI. AccumulatorXII. Contaminant Removal XIII. System ChargingSubcooling Charging Method Required Vapor Temperature FSuperheat Charging Table Superheat Charging MethodReliant AIR Conditioners Care and MaintenanceReliant Heat Pumps Required LIQUID-LINE Temperature Page AIR Conditioner Troubleshooting Chart Heat Pump TROUBLESHOOTING-COOLING Cycle Heat Pump TROUBLESHOOTING-HEATING Cycle
Related manuals
Manual 84 pages 49.8 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.