Bryant R-22 service manual Refrigeration System Refrigeration Cycle, II. Leak Detection

Page 35

NOTE: To ensure accurate ohm measurements, place ohmmeter probes on flat surface of compressor-terminal tabs, not the brass mounting screw.

Open

To determine if a winding has an actual break in the internal wires and current is unable to pass through:

1.Be sure all power is off.

2.Discharge all capacitors.

3.Remove wires from terminals T1, T2, T3, T7, and T8.

4.Use an ohmmeter on 0-1000 ohm scale to check resistance. (See Fig. 38, 40, and 41 and Table 18.)

Because winding resistances are usually less than 10 ohm, each reading will appear to be approximately zero ohm. If during any check the resistance remains at 1000 ohm, an open or break exists, and the motor or compressor should be replaced.

Ground

To determine if any wire has broken and come in direct contact with the housing or shell, causing a direct short to ground:

1.Be sure all power is off.

2.Discharge all capacitors.

3.Remove wires from T1, T2, T3, T7, and T8.

4.Allow crankcase heater to remain on for several hrs before checking motor to ensure that windings are not saturated with refrigerant.

5.Using an ohmmeter on R X 10,000 ohm scale, place 1 meter probe on groundmotor or compressor frame. Make a good metal-to-metal contact. Place other probe on terminals T1, T2, T3, T7, and T8 in sequence. Note meter scale.

If any reading of zero or low resistance is obtained, the motor is grounding. Replace the compressor.

Short

NOTE: This is an extremely critical test and is not advised unless the following conditions are met.

The correct motor-winding resistances must be known before testing. See Table 18 for cold-motor winding resistance.

The temperature of the windings must be specified, 70°F ± 2 °F.

The resistance-measuring instrument must have an accurate ohm- meter (such as a Wheatstone bridge or null balance-type instru- ment).

The motor must be dry or free from direct contact with liquid refrigerant.

To determine if any wires have broken through their insulation and come in direct contact with each other, thereby shortingall or part of the winding(s):

1.Be sure all power is off.

2.Discharge all capacitors.

3.Remove wires from terminals T1, T2, T3, T7, and T8.

4.Subtract instrument probe and lead resistance from each reading. If any reading is within ± 20 percent of the known resistance from Table 18, the motor probably does not have a short. Usually a considerable difference will be noted if a turn-to-turn short is present.

CONTROL BOARD FAILURE

The control board continuously monitors its own operation and the operation of the system. The diagnostic feature allows easy troubleshooting of the control and system in the field. If a failure occurs, the LED light on the control will flash a failure code. If the failure is internal to the control board, the light will stay on continuously (no flash). Before replacing control board, reset the

—35—

24v power. If the fault clears, check to ensure the indoor and outdoor unit and electrical service are properly grounded. If the entire system is grounded, the control board should be replaced, as the control is not field reparable. If the control-board light is flashing, see LED and Table 15 for function/malfunction defini- tion. Cycling 24 vac to control board resets previous error messages and any lockouts which have occurred. See Table 19 for more information regarding control-board operation.

CONTROL-BOARD POWER INPUTS AND OUTPUTS

See Fig. 33 and 37 for inputs and outputs.

BLEED RESISTOR

The bleed resistor is a 150k, 2–watt resistor across the compressor- run capacitor to protect service technician from injury by electrical shock. Capacitor will bleed-off approximately 1 minute after power to outdoor unit is turned off. If run capacitor is changed out, be sure to place bleed resistor on new capacitor. If bleed resistor is damaged, replace resistor.

START CAPACITOR AND RELAY

The 2-speed system has a second start relay in the control box. One start relay is for low-speed start, and the second is for high-speed start. Both start relays use a common-start capacitor. When servicing this equipment, be certain system starts in both low- and high-speed operation.

REFRIGERATION SYSTEM

I. REFRIGERATION CYCLE

In a refrigeration system, refrigerant moves heat from one place to another. It is useful to understand flow of refrigerant in a system.

In a straight cooling system, compressed hot gas leaves compres- sor and enters condensing coil. As gas passes through condenser coil, it rejects heat and condenses into liquid. The liquid leaves condensing unit through liquid line and enters metering device at indoor coil. As it passes through metering device, it becomes a gas-liquid mixture. As it passes through indoor coil, it absorbs heat and refrigerant and is again compressed to a hot gas. The cycle then repeats.

In a heat pump, the basic cycle is the same. (See Fig. 42.) Reversing valve in system decides which coil, indoor or outdoor, becomes evaporator or condenser. It rejects heat into the home after heat is absorbed by outdoor evaporator coil, thus the home is heated.

In cooling cycle, the indoor coil becomes the evaporator. It absorbs heat from the home and rejects it through the outdoor condenser coil, thus the home is cooled.

A unique feature of the heat pump is that metering devices are designed to meter refrigerant in one direction of flow and allow refrigerant to pass unhindered in the other direction. If indoor- metering device is metering refrigerant, the outdoor device by- passes refrigerant and vice versa. This allows both coils to serve a dual function.

II. LEAK DETECTION

CAUTION: Always wear safety glasses and gloves when handling refrigerants.

New installations should be checked for leaks prior to complete charging.

If a system has lost all or most of its charge, system must be pressurized again, up to approximately 150 lb minimum. This can be done by adding refrigerant using normal charging procedures, or it may be pressurized with nitrogen (less expensive than refrigerant). Nitrogen also leaks faster than R-22 and is not absorbed by refrigeration oil. Nitrogen cannot, however, be detected by a leak detector. (See Fig. 43.)

Image 35
Contents Safety Considerations Table of ContentsIII. Seacoast for AIR Conditioners only II. ADD-ON Replacement RetrofitAccessory Descriptions VIII. LOW-AMBIENT Pressure SwitchXI. Support Feet II. Interconnecting Tubing SizingIX. Wind Baffle Coastal FilterMatl 20 GA Steel Matl 18 GA SteelBaffle Left Unit Size Unit HeightSmall MediumIII. Metering Device Sizing Wind Baffle Dimensions for Cube UnitsEstimated Percentage of Nominal COOLING-CAPACITY Losses Calculation of Indoor Piston no IV. LIQUID-LINE Solenoid and Tubing CONFIGU- RationFitting Losses in Equivalent FT ExampleVI -SPEED Applications Common Piston SizesLIQUID-LINE Solenoid KIT Part Numbers Charging InformationPositions 6 through 10-Serial Number II. Serial Number IdentificationIII. Information PLATE-RELIANT Products II. Remove FAN-MOTOR ASSEMBLY-BEFORE 1/1/92Cabinet Remove TOP COVER-BEFORE 1/1/92VI. Remove FAN-MOTOR ASSEMBLY-AFTER 1/1/92 Basic Cabinet Designs Electrical Aluminum WireII. Contactors Information PlateStart Capacitors and PTC Devices III. CapacitorsIV. Cycle Protector Temporary Capacitance BoostCrankcase Heater VI. TIME-DELAY RelayLOW-PRESSURE Switch VII. Pressure SwitchesIX. DEFROST-CONTROL Board HIGH-PRESSURE SwitchLIQUID-LINE Pressure Switch VIII. Defrost ThermostatsCES0110063 CES0130024 CES0110063 Defrost ControlParameter Minimum Maximum Defrost Control SPEED-UP Timing SESPEED-UP FAN Motors Defrost Timer SettingsXI. Service Alarm Control Board XII. Outdoor Thermostats OF2 CESO130076-00Aeroquiet System and Aeromax TOP FAN PositionXIII. Compressor Plug Service Alarm Wiring ConnectionsMechanical Failures XIV. LOW-VOLTAGE TerminalsReciprocating Compressor II. Electrical Failures IV. Compressor Removal and Replacement III. System Cleanup After BurnoutIII. Discharge Thermostat Copeland Scroll Compressor FeaturesII. Troubleshooting Compressor OIL RechargeII. Compressor Protection Millennium Scroll Compressor FeaturesIII. Troubleshooting IV. Scroll COMPRESSOR, 3-PHASE MonitorCont HPS LPS IFR Indoor External Power Supply 24Cont Equip GND CAP OFM Logic CESO130075Ambient Temperature for HIGH- LOW-SPEED Operation Function Light Code and Display Location IV. Major Components III. Factory DefaultsFactory Defaults Compressor PTC RangesLED FUNCTION/MALFUNCTION Lights VI. TroubleshootingTWO-SPEED Compressor Winding Resistance AT 70F ± II. Leak Detection Refrigeration System Refrigeration CycleLow-Speed Windings All 24V PIN Connection TroubleshootingIII. Brazing Cooling CycleIV. Service Valves Service ValvesVI. Reversing Valve Reliant Products Except 1992 ProductionReliant and Cube Products Produced VII. THERMOSTATIC-EXPANSION Valves TXV Reversing ValveIX. Coil Removal TXV Superheat Setting AT Outlet of Evaporator CoilInstallation TXV Type Product Usage Superheat Setting VIII. THERMOSTATIC-EXPANSION Valve BI-FLOW TXVTXV in Cooling Mode XIV. Checking Charge XI. AccumulatorXII. Contaminant Removal XIII. System ChargingSubcooling Charging Method Required Vapor Temperature FSuperheat Charging Table Superheat Charging MethodReliant Heat Pumps Care and MaintenanceReliant AIR Conditioners Required LIQUID-LINE Temperature Page AIR Conditioner Troubleshooting Chart Heat Pump TROUBLESHOOTING-COOLING Cycle Heat Pump TROUBLESHOOTING-HEATING Cycle
Related manuals
Manual 84 pages 49.8 Kb

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.