Bryant 581J Static Pressure Adders Factory Options AND/OR Accessories, Economizer, Tons

Page 32

581J

TABLE 18 – STATIC PRESSURE ADDERS (FACTORY OPTIONS AND/OR ACCESSORIES)

Economizer

 

 

 

 

3 --- 5 TONS

 

 

 

 

 

 

CFM (in. wg)

600

800

1000

1250

1500

 

1750

2000

2250

2500

2750

3000

Vertical

0.01

0.02

0.04

0.05

0.07

 

0.09

0.12

0.15

0.18

0.22

0.26

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

0.02

0.03

0.04

0.06

0.08

 

0.10

0.13

0.15

0.18

0.23

0.28

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 --- 8.5 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM (in. wg)

1800

2000

2250

2500

2750

3000

3250

 

3500

3750

4000

4250

4500

4750

5000

5250

5500

5750

6000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical

0.04

0.05

0.06

0.08

0.09

0.12

0.13

 

0.15

0.17

0.20

0.22

0.25

0.29

0.33

0.36

0.40

0.44

0.48

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

0.07

0.07

0.08

0.10

0.13

0.15

0.18

 

0.21

0.25

0.28

0.30

0.34

0.39

0.43

0.47

0.51

0.56

0.60

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

General fan performance notes:

1.Interpolation is permissible. Do not extrapolate.

2.External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure caused by any FIOPs or accessories.

3.Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories may add static pressure losses, as shown in Table 24. Selection software is available, through your salesperson, to help you select the best motor/drive combination for your application.

4.The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would work, Bryant recommended the lower horsepower option.

5.For information on the electrical properties of Bryant motors, please see the Electrical information section of this book.

6.For more information on the performance limits of Bryant motors, see the application data section of this book.

7.The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regulated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT compliant energy-efficient motor. Variable-speed motors are exempt from EPACT compliance require- ments. Therefore, the indoor fan motors for Bryant 581J04-09 units are exempt from these requirements.

32

Image 32
Contents Product Data Catalog No.PDS581J---01Table of Contents Features and Benefits Model Number Nomenclature Economizer Sensors FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesEconomizers Factory Options AND/OR Accessories Economizer dry-bulb or enthalpyFactory Options AND/OR Accessories CON’T Motormaster Head Pressure ControllerAhri Cooling Rating -STAGE Cooling NOM NET CoolingUnit Seer EER Ieer StagesHeating Rating Table Natural GAS & Propane AL/SS Heat Exchanger Temp Rise Thermal AfueUnits EfficiencyStages Weighted Heating Rating Table LOW NOX1Sound Performance Table Unit CoolingMinimum Maximum Minimum Maximum Airflow Ratings Natural GAS & PropaneCooling Heating Minimum Tons Physical DataCooling Heat Anticipator Setting Amps Physical Data Heating581J*04A 581J*05A 581J*06A 581J*07A Gas Connection Natural Gas, Propane HeatPhysical Data Cooling 8.5 Tons581J*08D 581J*09D Gas Connection # of Gas ValvesCurbs & Weights Dimensions 581J04-06 Curbs & Weights Dimensions 581J04-06 Dimension ConditionRoof Curb Details Curbs & Weights Dimensions 581J07-09 Dimensions 581J07-09Curbs & Weights Dimensions 581J07-09 Roofcurb Unit Size Accessory CRRFCURB003A01 Options & Accessory Weights Option / Accessory WeightsApplication Data Stainless SteelApplication Data Sizing a rooftopSelection Procedure with 581J*07A EXAMPLE1 Ambient Temperature Cooling Capacities Stage Cooling Tons105 115 125 EA dB 53.4 60.6 THC Cooling Capacities Stage Cooling 581J*08D115 125 EA dB Static Pressure Adders Factory Options AND/OR Accessories EconomizerGeneral fan performance notes TonsPhase 3 TON Horizontal Supply 581J*04 PhaseFAN Performance Belt Drive TON Vertical SupplyPhase 4 TON Horizontal Supply 581J*05 PhaseFAN Performance Belt Drive 581J*05581J*06--3 PHASE--5 TON Horizontal Supply 581J*06 Phase581J*07--3 PHASE--6 TON Horizontal Supply 581J*07 PhasePhase 7.5 TON Horizontal Supply 581J*08 PhaseFAN Performance Belt DRIVEcont 581J*08581J*09 Phase 8.5 TON Horizontal Supply581J*09 Phase FAN Performance X13 Multi SPEED/TORQUE Motor581J*04A Horizontal Unit-Direct Drive 581J*04A Vertical Unit-Direct Drive581J*05A Horizontal Unit-Direct Drive 581J*05A Vertical Unit-Direct Drive581J*06A Horizontal Unit-Direct Drive 581J*06A Vertical Unit-Direct DrivePulley Adjustment PhaseECONOMIZER, Barometric Relief and PE Performance 5 TonElectrical Information 581J*04AStage Cooling Tons 581J*05AElectrical Information CON’T 581J*06A--1-STAGE COOLING--5 Tons581J*07A Stage Cooling 6 Tons581J*08D--2-STAGE COOLING--7.5 Tons 581J*09D--2-STAGE COOLING--8.5 TonsRange RLA MINMCA/MOCP MCA/MOCP Determination no C.O. or Unpwrd C.O.-3-5 TONMCA/MOCP CON’T Pwrd C.OMCA Hacr Hacr Brkr FLA LRAMCA/MOCP Determination no C.O. or Unpwrd C.O.-6-8.5 TON IFM Combust FAN PWRMotor Exhaust No P.E DISC. Size Fuse TypeCombust FAN PWR IFM Exhaus Motor No P.EFuse DISC. Size Type Hacr FLA LRA BrkrTypical Wiring Diagrams Stage Cooling Typical Power DiagramTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Heating Sequence of OperationCooling Sequence of Operation Guide Specifications 581J*04-09 Gas Heat/Electric Cooling Packaged Rooftop23 07 16 Hvac Equipment Insulation 23 09 13 Instrumentation and Control Devices for Hvac23 09 33 Electric and Electronic Control System for Hvac 23 81 19 Self-Contained Air Conditioners 23 09 93 Sequence of Operations for Hvac Controls23 40 13 Panel Air Filters 581J 581J 581J 581J 581J 581J 581J