d.Shall have tool-less connection terminal access.

e.Shall have a recessed momentary switch for testing and resetting the detector.

f.Controller shall include:

(1.) One set of normally open alarm initiation contacts for connection to an initiating device circuit on a fire alarm control panel.

(2.) Two Form-C auxiliary alarm relays for interface with rooftop unit or other equipment.

(3.) One Form-C supervision (trouble) relay to control the operation of the Trouble LED on a remote test/reset station.

(4.) Capable of direct connection to two individual detector modules.

(5.) Can be wired to up to 14 other duct smoke detectors for multiple fan shutdown applications

19.Winter start kit

a.Shall contain a bypass device around the low pressure switch.

b.Shall be required when mechanical cooling is required down to 25_F (-4_C).

c.Shall not be required to operate on an economizer when below an outdoor ambient of 40_F (4_C).

20.Time Guard

a.Shall prevent compressor short cycling by providing a 5-minute delay (±2 minutes) before restarting a com- pressor after shutdown for any reason.

b.One device shall be required per compressor.

21.Hinged Access Panels

a.Shall provide easy access through integrated quarter turn latches.

b.Shall be on major panels of – filter, control box, fan motor and compressor

66

Image 66
Contents Product Data Catalog No.PDS581J---01Table of Contents Features and Benefits Model Number Nomenclature FACTORY-INSTALLED Options and FIELD-INSTALLED Accessories EconomizersEconomizer Sensors Factory Options AND/OR Accessories Economizer dry-bulb or enthalpyFactory Options AND/OR Accessories CON’T Motormaster Head Pressure ControllerUnit Ahri Cooling Rating -STAGE CoolingNOM NET Cooling Seer EER Ieer StagesUnits Heating Rating Table Natural GAS & PropaneAL/SS Heat Exchanger Temp Rise Thermal Afue EfficiencySound Performance Table Stages WeightedHeating Rating Table LOW NOX1 Unit CoolingMinimum Maximum Airflow Ratings Natural GAS & Propane Cooling Heating MinimumMinimum Maximum Physical Data CoolingTons 581J*04A 581J*05A 581J*06A 581J*07A Gas Connection Heat Anticipator Setting AmpsPhysical Data Heating Natural Gas, Propane HeatPhysical Data Cooling 8.5 Tons581J*08D 581J*09D Gas Connection # of Gas ValvesCurbs & Weights Dimensions 581J04-06 Curbs & Weights Dimensions 581J04-06 Dimension ConditionRoof Curb Details Curbs & Weights Dimensions 581J07-09 Dimensions 581J07-09Curbs & Weights Dimensions 581J07-09 Roofcurb Unit Size Accessory CRRFCURB003A01 Options & Accessory Weights Option / Accessory WeightsApplication Data Stainless SteelApplication Data Sizing a rooftopSelection Procedure with 581J*07A EXAMPLE1 Ambient Temperature Cooling Capacities Stage Cooling Tons105 115 125 EA dB 53.4 60.6 THC Cooling Capacities Stage Cooling 581J*08D115 125 EA dB General fan performance notes Static Pressure Adders Factory Options AND/OR AccessoriesEconomizer TonsFAN Performance Belt Drive Phase 3 TON Horizontal Supply581J*04 Phase TON Vertical SupplyFAN Performance Belt Drive Phase 4 TON Horizontal Supply581J*05 Phase 581J*05581J*06--3 PHASE--5 TON Horizontal Supply 581J*06 Phase581J*07--3 PHASE--6 TON Horizontal Supply 581J*07 PhaseFAN Performance Belt DRIVEcont Phase 7.5 TON Horizontal Supply581J*08 Phase 581J*08Phase 8.5 TON Horizontal Supply 581J*09 Phase581J*09 581J*04A Horizontal Unit-Direct Drive FAN PerformanceX13 Multi SPEED/TORQUE Motor 581J*04A Vertical Unit-Direct Drive581J*05A Horizontal Unit-Direct Drive 581J*05A Vertical Unit-Direct Drive581J*06A Horizontal Unit-Direct Drive 581J*06A Vertical Unit-Direct DrivePulley Adjustment PhaseECONOMIZER, Barometric Relief and PE Performance 5 TonStage Cooling Tons Electrical Information581J*04A 581J*05A581J*07A Electrical Information CON’T581J*06A--1-STAGE COOLING--5 Tons Stage Cooling 6 TonsRange RLA 581J*08D--2-STAGE COOLING--7.5 Tons581J*09D--2-STAGE COOLING--8.5 Tons MINMCA/MOCP MCA/MOCP Determination no C.O. or Unpwrd C.O.-3-5 TONMCA Hacr MCA/MOCP CON’TPwrd C.O Hacr Brkr FLA LRAMotor Exhaust No P.E MCA/MOCP Determination no C.O. or Unpwrd C.O.-6-8.5 TONIFM Combust FAN PWR DISC. Size Fuse TypeFuse DISC. Size Type Combust FAN PWRIFM Exhaus Motor No P.E Hacr FLA LRA BrkrTypical Wiring Diagrams Stage Cooling Typical Power DiagramTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Sequence of Operation CoolingHeating Sequence of Operation 23 07 16 Hvac Equipment Insulation Guide Specifications 581J*04-09Gas Heat/Electric Cooling Packaged Rooftop 23 09 13 Instrumentation and Control Devices for Hvac23 09 33 Electric and Electronic Control System for Hvac 23 09 93 Sequence of Operations for Hvac Controls 23 40 13 Panel Air Filters23 81 19 Self-Contained Air Conditioners 581J 581J 581J 581J 581J 581J 581J
Related manuals
Manual 40 pages 41.76 Kb

581J specifications

The Bryant 581J is a high-efficiency gas furnace that exemplifies advanced heating technology and innovative design. Known for its reliability and comfort, the Bryant 581J offers impressive performance features that cater to both residential and commercial heating needs. One of its standout characteristics is the two-stage heating system, which allows the furnace to operate at a lower stage when the heating demand is modest, providing improved comfort and energy efficiency. This feature also minimizes temperature fluctuations, ensuring a more consistent and comfortable indoor environment.

Energy efficiency is a critical aspect of the Bryant 581J. With an annual fuel utilization efficiency (AFUE) rating of up to 96%, this furnace is designed to convert a high percentage of fuel into usable heat, which helps homeowners save on energy bills. The high-efficiency design also contributes to a reduced carbon footprint, aligning with modern environmental concerns.

The Bryant 581J is equipped with technologically advanced features, including the ComfortTechâ„¢ control system. This system enables enhanced temperature regulation and integrates easily with smart home systems, allowing homeowners the convenience of remote control through smartphones and tablets. Additionally, the furnace includes an electronically commutated motor (ECM) blower, which optimizes airflow and reduces energy consumption while enhancing the overall comfort level within the space.

Noise reduction is another key characteristic of the Bryant 581J. The furnace is engineered with sound-dampening technology, resulting in quieter operation compared to conventional furnaces. This attention to noise management makes it an appealing choice for residential applications, where peace and tranquility are crucial.

The durable construction of the Bryant 581J ensures longevity and reliability. With a robust cabinet and quality materials, it is built to withstand the rigors of daily operation. Furthermore, the furnace comes with a warranty that provides peace of mind, protecting the investment over the years.

Overall, the Bryant 581J represents a blend of efficiency, advanced technology, and reliable performance. With its high AFUE rating, innovative features, and quiet operation, it stands out in the market as a top choice for anyone seeking a dependable heating solution. Whether for new installations or replacements, the Bryant 581J is designed to meet the heating demands of today's energy-conscious homeowners.