Bryant 581J specifications 23 09 33 Electric and Electronic Control System for Hvac

Page 58

581J

11.Shall include an EIA-485 protocol communication port, an access port for connection of either a computer or a Bryant technician tool, an EIA-485 port for network communication to intelligent space sensors and displays, and a port to connect an optional LonWorks plug-in communications card.

12.Shall have built-in support for Bryant technician tool.

13.Software upgrades will be accomplished by local download. Software upgrades through chip replacements are not allowed.

14.Shall be shock resistant in all planes to 5G peak, 11ms during operation, and 100G peak, 11ms during storage.

15.Shall be vibration resistant in all planes to 1.5G @ 20-300 Hz.

16.Shall support a bus length of 4000 ft (1219m) max, 60 devices per 1000 ft (305m) section, and 1 RS-485 repeater per 1000 ft (305m) sections.

23 09 23.13.B. RTU-MP - Open protocol, direct digital controller:

1.Shall be ASHRAE 62-2001 compliant.

2.Shall accept 18-30VAC, 50-60Hz, and consumer 15VA or less power.

3.Shall have an operating temperature range from -40_F (-40_C) to 130_F (54_C), 10% - 90% RH (non-condens- ing).

4.Shall include built-in protocol for BACNET (MS/TP and PTP modes), Modbus (RTU and ASCII), Johnson N2 and LonWorks. LonWorks Echelon processor required for all Lon applications shall be contained in separate com- munication board.

5.Shall allow access of up to 62 network variables (SNVT). Shall be compatible with all open controllers

6.Baud rate Controller shall be selectable using a dipswitch.

7.Shall have an LED display independently showing the status of serial communication, running, errors, power, all digital outputs, and all analog inputs.

8.Shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature, indoor air qu- ality, outdoor air quality, compressor lock-out, fire shutdown, enthalpy switch, and fan status/filter status/ humid- ity/ remote occupancy.

9.Shall provide the following outputs: economizer, fan, cooling stage 1, cooling stage 2, heat stage 1, heat stage 2, heat stage 3/ exhaust/ reversing valve.

10.Shall have built-in surge protection circuitry through solid state polyswitches. Polyswitches shall be used on in- coming power and network connections. Polyswitches will return to normal when the “trip” condition clears.

11.Shall have a battery back-up capable of a minimum of 10,000 hours of data and time clock retention during power outages.

12.Shall have built-in support for Bryant technician tool.

13.Shall include an EIA-485 protocol communication port, an access port for connection of either a computer or a Bryant technician tool, an EIA-485 port for network communication to intelligent space sensors and displays, and a port to connect an optional LonWorks communications card.

14.Software upgrades will be accomplished by either local or remote download. No software upgrades through chip replacements are allowed.

23 09 33 Electric and Electronic Control System for HVAC

23 09 33.13 Decentralized, Rooftop Units:

23 09 33.13.A. General:

1.Shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker on the 24-v transformer side. Transformer shall have 75VA capability.

2.Shall utilize color-coded wiring.

3.Shall include a central control terminal board to conveniently and safely provide connection points for vital con- trol functions such as: smoke detectors, phase monitor, gas controller, economizer, thermostat, DDC control op- tions, and low and high pressure switches.

4.The heat exchanger shall be controlled by an integrated gas controller (IGC) microprocessor. See heat exchanger section of this specification.

5.Unit shall include a minimum of one 8-pin screw terminal connection board for connection of control wiring.

23 09 33.23.B. Safeties:

1.Compressor over-temperature, over-current. High internal pressure differential.

2.Low-pressure switch.

a.Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high pres- sure switches. They shall physically prevent the cross-wiring of the safety switches between circuits 1 and 2.

b.Low pressure switch shall use different color wire than the high pressure switch. The purpose is to assist the installer and service technician to correctly wire and or troubleshoot the rooftop unit.

58

Image 58
Contents Product Data Catalog No.PDS581J---01Table of Contents Features and Benefits Model Number Nomenclature Economizers FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesEconomizer Sensors Factory Options AND/OR Accessories Economizer dry-bulb or enthalpyFactory Options AND/OR Accessories CON’T Motormaster Head Pressure ControllerUnit Ahri Cooling Rating -STAGE CoolingNOM NET Cooling Seer EER Ieer StagesUnits Heating Rating Table Natural GAS & PropaneAL/SS Heat Exchanger Temp Rise Thermal Afue EfficiencySound Performance Table Stages WeightedHeating Rating Table LOW NOX1 Unit CoolingCooling Heating Minimum Minimum Maximum Airflow Ratings Natural GAS & PropaneMinimum Maximum Cooling Physical DataTons 581J*04A 581J*05A 581J*06A 581J*07A Gas Connection Heat Anticipator Setting AmpsPhysical Data Heating Natural Gas, Propane HeatPhysical Data Cooling 8.5 Tons581J*08D 581J*09D Gas Connection # of Gas ValvesCurbs & Weights Dimensions 581J04-06 Curbs & Weights Dimensions 581J04-06 Dimension ConditionRoof Curb Details Curbs & Weights Dimensions 581J07-09 Dimensions 581J07-09Curbs & Weights Dimensions 581J07-09 Roofcurb Unit Size Accessory CRRFCURB003A01 Options & Accessory Weights Option / Accessory WeightsApplication Data Stainless SteelApplication Data Sizing a rooftopSelection Procedure with 581J*07A EXAMPLE1 Ambient Temperature Cooling Capacities Stage Cooling Tons105 115 125 EA dB 53.4 60.6 THC Cooling Capacities Stage Cooling 581J*08D115 125 EA dB General fan performance notes Static Pressure Adders Factory Options AND/OR AccessoriesEconomizer TonsFAN Performance Belt Drive Phase 3 TON Horizontal Supply581J*04 Phase TON Vertical SupplyFAN Performance Belt Drive Phase 4 TON Horizontal Supply581J*05 Phase 581J*05581J*06--3 PHASE--5 TON Horizontal Supply 581J*06 Phase581J*07--3 PHASE--6 TON Horizontal Supply 581J*07 PhaseFAN Performance Belt DRIVEcont Phase 7.5 TON Horizontal Supply581J*08 Phase 581J*08581J*09 Phase Phase 8.5 TON Horizontal Supply581J*09 581J*04A Horizontal Unit-Direct Drive FAN PerformanceX13 Multi SPEED/TORQUE Motor 581J*04A Vertical Unit-Direct Drive581J*05A Horizontal Unit-Direct Drive 581J*05A Vertical Unit-Direct Drive581J*06A Horizontal Unit-Direct Drive 581J*06A Vertical Unit-Direct DrivePulley Adjustment PhaseECONOMIZER, Barometric Relief and PE Performance 5 TonStage Cooling Tons Electrical Information581J*04A 581J*05A581J*07A Electrical Information CON’T581J*06A--1-STAGE COOLING--5 Tons Stage Cooling 6 TonsRange RLA 581J*08D--2-STAGE COOLING--7.5 Tons581J*09D--2-STAGE COOLING--8.5 Tons MINMCA/MOCP MCA/MOCP Determination no C.O. or Unpwrd C.O.-3-5 TONMCA Hacr MCA/MOCP CON’TPwrd C.O Hacr Brkr FLA LRAMotor Exhaust No P.E MCA/MOCP Determination no C.O. or Unpwrd C.O.-6-8.5 TONIFM Combust FAN PWR DISC. Size Fuse TypeFuse DISC. Size Type Combust FAN PWRIFM Exhaus Motor No P.E Hacr FLA LRA BrkrTypical Wiring Diagrams Stage Cooling Typical Power DiagramTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Cooling Sequence of OperationHeating Sequence of Operation 23 07 16 Hvac Equipment Insulation Guide Specifications 581J*04-09Gas Heat/Electric Cooling Packaged Rooftop 23 09 13 Instrumentation and Control Devices for Hvac23 09 33 Electric and Electronic Control System for Hvac 23 40 13 Panel Air Filters 23 09 93 Sequence of Operations for Hvac Controls23 81 19 Self-Contained Air Conditioners 581J 581J 581J 581J 581J 581J 581J
Related manuals
Manual 40 pages 41.76 Kb

581J specifications

The Bryant 581J is a high-efficiency gas furnace that exemplifies advanced heating technology and innovative design. Known for its reliability and comfort, the Bryant 581J offers impressive performance features that cater to both residential and commercial heating needs. One of its standout characteristics is the two-stage heating system, which allows the furnace to operate at a lower stage when the heating demand is modest, providing improved comfort and energy efficiency. This feature also minimizes temperature fluctuations, ensuring a more consistent and comfortable indoor environment.

Energy efficiency is a critical aspect of the Bryant 581J. With an annual fuel utilization efficiency (AFUE) rating of up to 96%, this furnace is designed to convert a high percentage of fuel into usable heat, which helps homeowners save on energy bills. The high-efficiency design also contributes to a reduced carbon footprint, aligning with modern environmental concerns.

The Bryant 581J is equipped with technologically advanced features, including the ComfortTechâ„¢ control system. This system enables enhanced temperature regulation and integrates easily with smart home systems, allowing homeowners the convenience of remote control through smartphones and tablets. Additionally, the furnace includes an electronically commutated motor (ECM) blower, which optimizes airflow and reduces energy consumption while enhancing the overall comfort level within the space.

Noise reduction is another key characteristic of the Bryant 581J. The furnace is engineered with sound-dampening technology, resulting in quieter operation compared to conventional furnaces. This attention to noise management makes it an appealing choice for residential applications, where peace and tranquility are crucial.

The durable construction of the Bryant 581J ensures longevity and reliability. With a robust cabinet and quality materials, it is built to withstand the rigors of daily operation. Furthermore, the furnace comes with a warranty that provides peace of mind, protecting the investment over the years.

Overall, the Bryant 581J represents a blend of efficiency, advanced technology, and reliable performance. With its high AFUE rating, innovative features, and quiet operation, it stands out in the market as a top choice for anyone seeking a dependable heating solution. Whether for new installations or replacements, the Bryant 581J is designed to meet the heating demands of today's energy-conscious homeowners.