Bryant 581J specifications

Page 61

(2.) Optional, factory-approved, water-tight connection method must be used for thru-the-base electrical con- nections.

(3.) No basepan penetration, other than those authorized by the manufacturer, is permitted.

10.Component access panels (standard)

a.Cabinet panels shall be easily removable for servicing.

b.Unit shall have one factory installed, tool-less, removable, filter access panel.

c.Panels covering control box, indoor fan, indoor fan motor, gas components (where applicable), and com- pressors shall have a molded composite handles.

d.Handles shall be UV modified, composite. They shall be permanently attached, and recessed into the panel.

e.Screws on the vertical portion of all removable access panel shall engage into heat resistant, molded compos- ite collars.

f.Collars shall be removable and easily replaceable using manufacturer recommended parts.

23 81 19.13.I. Gas Heat

1.General

a.Heat exchanger shall be an induced draft design. Positive pressure heat exchanger designs shall not be al- lowed.

b.Shall incorporate a direct-spark ignition system and redundant main gas valve.

c.Gas supply pressure at the inlet to the rooftop unit gas valve must match that required by the manufacturer.

2.The heat exchanger shall be controlled by an integrated gas controller (IGC) microprocessor.

a.IGC board shall notify users of fault using an LED (light-emitting diode).

b.The LED shall be visible without removing the control box access panel.

c.IGC board shall contain algorithms that modify evaporator-fan operation to prevent future cycling on high temperature limit switch.

d.Unit shall be equipped with anti-cycle protection with one short cycle on unit flame rollout switch or 4 con- tinuous short cycles on the high temperature limit switch. Fault indication shall be made using an LED.

3.Standard Heat Exchanger construction

a.Heat exchanger shall be of the tubular-section type constructed of a minimum of 20-gauge steel coated with a nominal 1.2 mil aluminum-silicone alloy for corrosion resistance.

b.Burners shall be of the in-shot type constructed of aluminum-coated steel.

c.Burners shall incorporate orifices for rated heat output up to 2000 ft (610m) elevation. Additional accessory kits may be required for applications above 2000 ft (610m) elevation, depending on local gas supply condi- tions.

d.Each heat exchanger tube shall contain multiple dimples for increased heating effectiveness.

4.Optional Stainless Steel Heat Exchanger construction

a.Use energy saving, direct-spark ignition system.

b.Use a redundant main gas valve.

c.Burners shall be of the in-shot type constructed of aluminum-coated steel.

d.All gas piping shall enter the unit cabinet at a single location on side of unit (horizontal plane).

e.The optional stainless steel heat exchanger shall be of the tubular-section type, constructed of a minimum of 20-gauge type 409 stainless steel.

f.Type 409 stainless steel shall be used in heat exchanger tubes and vestibule plate.

g.Complete stainless steel heat exchanger allows for greater application flexibility.

5.Optional Low NOx Heat Exchanger construction

a.Low NOx reduction shall be provided to reduce nitrous oxide emissions to meet California’s Air Quality Man- agement District (SCAQMD) low-NOxemissions requirement of 40 nanograms per joule or less.

b.Primary tubes and vestibule plates on low NOx units shall be 409 stainless steel. Other components shall be aluminized steel.

6.Induced draft combustion motor and blower

a.Shall be a direct-drive, single inlet, forward-curved centrifugal type.

b.Shall be made from steel with a corrosion-resistant finish.

c.Shall have permanently lubricated sealed bearings.

d.Shall have inherent thermal overload protection.

e.Shall have an automatic reset feature.

581J

61

Image 61
Contents Catalog No.PDS581J---01 Product DataTable of Contents Features and Benefits Model Number Nomenclature Economizers FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesEconomizer Sensors Economizer dry-bulb or enthalpy Factory Options AND/OR AccessoriesMotormaster Head Pressure Controller Factory Options AND/OR Accessories CON’TNOM NET Cooling Ahri Cooling Rating -STAGE CoolingUnit Seer EER Ieer StagesAL/SS Heat Exchanger Temp Rise Thermal Afue Heating Rating Table Natural GAS & PropaneUnits EfficiencyHeating Rating Table LOW NOX1 Stages WeightedSound Performance Table Unit CoolingCooling Heating Minimum Minimum Maximum Airflow Ratings Natural GAS & PropaneMinimum Maximum Cooling Physical DataTons Physical Data Heating Heat Anticipator Setting Amps581J*04A 581J*05A 581J*06A 581J*07A Gas Connection Natural Gas, Propane Heat8.5 Tons Physical Data Cooling# of Gas Valves 581J*08D 581J*09D Gas ConnectionCurbs & Weights Dimensions 581J04-06 Dimension Condition Curbs & Weights Dimensions 581J04-06Roof Curb Details Dimensions 581J07-09 Curbs & Weights Dimensions 581J07-09Curbs & Weights Dimensions 581J07-09 Roofcurb Unit Size Accessory CRRFCURB003A01 Option / Accessory Weights Options & Accessory WeightsStainless Steel Application DataSizing a rooftop Application DataSelection Procedure with 581J*07A EXAMPLE1 Cooling Capacities Stage Cooling Tons Ambient Temperature105 115 125 EA dB 53.4 60.6 THC 581J*08D Cooling Capacities Stage Cooling115 125 EA dB Economizer Static Pressure Adders Factory Options AND/OR AccessoriesGeneral fan performance notes Tons581J*04 Phase Phase 3 TON Horizontal SupplyFAN Performance Belt Drive TON Vertical Supply581J*05 Phase Phase 4 TON Horizontal SupplyFAN Performance Belt Drive 581J*05581J*06 Phase 581J*06--3 PHASE--5 TON Horizontal Supply581J*07 Phase 581J*07--3 PHASE--6 TON Horizontal Supply581J*08 Phase Phase 7.5 TON Horizontal SupplyFAN Performance Belt DRIVEcont 581J*08581J*09 Phase Phase 8.5 TON Horizontal Supply581J*09 X13 Multi SPEED/TORQUE Motor FAN Performance581J*04A Horizontal Unit-Direct Drive 581J*04A Vertical Unit-Direct Drive581J*05A Vertical Unit-Direct Drive 581J*05A Horizontal Unit-Direct Drive581J*06A Vertical Unit-Direct Drive 581J*06A Horizontal Unit-Direct DrivePhase Pulley Adjustment5 Ton ECONOMIZER, Barometric Relief and PE Performance581J*04A Electrical InformationStage Cooling Tons 581J*05A581J*06A--1-STAGE COOLING--5 Tons Electrical Information CON’T581J*07A Stage Cooling 6 Tons581J*09D--2-STAGE COOLING--8.5 Tons 581J*08D--2-STAGE COOLING--7.5 TonsRange RLA MINMCA/MOCP Determination no C.O. or Unpwrd C.O.-3-5 TON MCA/MOCPPwrd C.O MCA/MOCP CON’TMCA Hacr Hacr Brkr FLA LRAIFM Combust FAN PWR MCA/MOCP Determination no C.O. or Unpwrd C.O.-6-8.5 TONMotor Exhaust No P.E DISC. Size Fuse TypeIFM Exhaus Motor No P.E Combust FAN PWRFuse DISC. Size Type Hacr FLA LRA BrkrStage Cooling Typical Power Diagram Typical Wiring DiagramsTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Cooling Sequence of OperationHeating Sequence of Operation Gas Heat/Electric Cooling Packaged Rooftop Guide Specifications 581J*04-0923 07 16 Hvac Equipment Insulation 23 09 13 Instrumentation and Control Devices for Hvac 23 09 33 Electric and Electronic Control System for Hvac 23 40 13 Panel Air Filters 23 09 93 Sequence of Operations for Hvac Controls23 81 19 Self-Contained Air Conditioners 581J 581J 581J 581J 581J 581J 581J