Bryant 581J specifications Application Data, Stainless Steel

Page 23

APPLICATION DATA

Min operating ambient temp (cooling):

In mechanical cooling mode, your Bryant rooftop unit can safely operate down to an outdoor ambient temperature of 35_F (-2_C) and 25_F (-4_C), with an accessory winter start kit. It is possible to provide cooling at lower outdoor ambient temperatures by using less outside air, economizers, and/or accessory low ambient kits.

Max operating ambient temp (cooling):

The maximum operating ambient temperature for cooling mode is 125_F (52_C). While cooling operation above 125_F (52_C) may be possible, it could cause either a reduction in performance, reliability, or a protective action by the unit’s internal safety devices.

Min mixed air temp (heating):

Using the factory settings, the minimum temperatures for the mixed air (the combined temperature of the warm return air and the cold outdoor air) entering the dimpled, gas heat exchangers are:

Aluminized

Stainless Steel

50_F (10_C) continuous

40_F (4_C) continuous

45_F (7_C) intermittent

35_F (2_C) intermittent

Operating at lower mixed-air temperatures may be possible, if a field-supplied, outdoor air thermostat initiates both heat stages when the temperature is less than the minimum temperatures listed above. Please contact your local Bryant representative for assistance.

Min and max airflow (heating and cooling):

To maintain safe and reliable operation of your rooftop, operate within the heating airflow limits during heating mode and cooling airflow limits during cooling mode. Operating above the max may cause blow-off, undesired airflow noise, or airflow related problems with the rooftop unit. Operating below the min may cause problems with coil freeze-up and unsafe heating operation. Heating and cooling limitations differ when evaluating operating CFM, the minimum value is the HIGHER of the cooling and heating minimum CFM values published in Table 7 and the maximum value is the LOWER of the cooling and heating minimum values published in Table 7.

Heating-to-cooling changeover:

Your unit will automatically change from heating to cooling mode when using a thermostat with an auto-change-over feature.

Airflow:

All units are draw-though in cooling mode and blow-through in heating mode.

Outdoor air application strategies:

Economizers reduce operating expenses and compressor run time by providing a free source of cooling and a means of ventilation to match application changing needs. In fact, they should be considered for most applications. Also, consider the various economizer control methods and their benefits, as well as sensors required to accomplish your application goals. Please contact your local Bryant representative for assistance.

Motor limits, brake horsepower (BHP):

Due to internal design of Bryant units, the air path, and specially designed motors, the full horsepower (maximum continuous BHP) band, as listed in Table 8 and 10, can be used with the utmost confidence. There is no need for extra safety factors, as Bryant motors are designed and rigorously tested to use the entire, listed BHP range without either nuisance tripping or premature motor failure.

Propane heating:

Propane has different physical qualities than natural gas. As a result, Propane requires different fuel to air mixture. To optimize the fuel/air mixture for Propane, Bryant sells different burner orifices in an easy to install accessory kit. To select the correct burner orifices or determine the heat capacity for an Propane application, use either the selection software, or the unit’s service manual.

High altitude heating:

High altitudes have less oxygen, which affects the fuel/air mixture in heat exchangers. In order to maintain a proper fuel/air mixture, heat exchangers operating in altitudes above 2000 ft (610 m) require different orifices. To select the correct burner orifices or determine the heat capacity for a high altitude application, use either the selection software, or the unit’s service manual.

High altitudes have less oxygen, which means heat exchangers need less fuel. The new gas orifices in this field-installed kit make the necessary adjustment for high altitude applications. They restore the optimal fuel to air mixture and maintain healthy combustion on altitudes above 2000 ft (610 m).

NOTE: Typical natural gas heating value ranges from 975 to 1050 Btu/ft3 at sea level nationally. The heating value goes down approximately 1.7% per every thousand feet elevation. Standard factory orifices can typically be used up to 2000 ft (610m) elevation without any operational issues.

NOTE: For installations in Canada, the input rating should be derated by 10% for altitudes from 2000 ft (610m)to 4500 ft (1372m) above sea level.

581J

23

Image 23
Contents Catalog No.PDS581J---01 Product DataTable of Contents Features and Benefits Model Number Nomenclature Economizer Sensors FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesEconomizers Economizer dry-bulb or enthalpy Factory Options AND/OR AccessoriesMotormaster Head Pressure Controller Factory Options AND/OR Accessories CON’TSeer EER Ieer Stages Ahri Cooling Rating -STAGE CoolingNOM NET Cooling UnitEfficiency Heating Rating Table Natural GAS & PropaneAL/SS Heat Exchanger Temp Rise Thermal Afue UnitsUnit Cooling Stages WeightedHeating Rating Table LOW NOX1 Sound Performance TableMinimum Maximum Minimum Maximum Airflow Ratings Natural GAS & PropaneCooling Heating Minimum Tons Physical DataCooling Natural Gas, Propane Heat Heat Anticipator Setting AmpsPhysical Data Heating 581J*04A 581J*05A 581J*06A 581J*07A Gas Connection8.5 Tons Physical Data Cooling# of Gas Valves 581J*08D 581J*09D Gas ConnectionCurbs & Weights Dimensions 581J04-06 Dimension Condition Curbs & Weights Dimensions 581J04-06Roof Curb Details Dimensions 581J07-09 Curbs & Weights Dimensions 581J07-09Curbs & Weights Dimensions 581J07-09 Roofcurb Unit Size Accessory CRRFCURB003A01 Option / Accessory Weights Options & Accessory WeightsStainless Steel Application DataSizing a rooftop Application DataSelection Procedure with 581J*07A EXAMPLE1 Cooling Capacities Stage Cooling Tons Ambient Temperature105 115 125 EA dB 53.4 60.6 THC 581J*08D Cooling Capacities Stage Cooling115 125 EA dB Tons Static Pressure Adders Factory Options AND/OR AccessoriesEconomizer General fan performance notesTON Vertical Supply Phase 3 TON Horizontal Supply581J*04 Phase FAN Performance Belt Drive581J*05 Phase 4 TON Horizontal Supply581J*05 Phase FAN Performance Belt Drive581J*06 Phase 581J*06--3 PHASE--5 TON Horizontal Supply581J*07 Phase 581J*07--3 PHASE--6 TON Horizontal Supply581J*08 Phase 7.5 TON Horizontal Supply581J*08 Phase FAN Performance Belt DRIVEcont581J*09 Phase 8.5 TON Horizontal Supply581J*09 Phase 581J*04A Vertical Unit-Direct Drive FAN PerformanceX13 Multi SPEED/TORQUE Motor 581J*04A Horizontal Unit-Direct Drive581J*05A Vertical Unit-Direct Drive 581J*05A Horizontal Unit-Direct Drive581J*06A Vertical Unit-Direct Drive 581J*06A Horizontal Unit-Direct DrivePhase Pulley Adjustment5 Ton ECONOMIZER, Barometric Relief and PE Performance581J*05A Electrical Information581J*04A Stage Cooling TonsStage Cooling 6 Tons Electrical Information CON’T581J*06A--1-STAGE COOLING--5 Tons 581J*07AMIN 581J*08D--2-STAGE COOLING--7.5 Tons581J*09D--2-STAGE COOLING--8.5 Tons Range RLAMCA/MOCP Determination no C.O. or Unpwrd C.O.-3-5 TON MCA/MOCPHacr Brkr FLA LRA MCA/MOCP CON’TPwrd C.O MCA HacrDISC. Size Fuse Type MCA/MOCP Determination no C.O. or Unpwrd C.O.-6-8.5 TONIFM Combust FAN PWR Motor Exhaust No P.EHacr FLA LRA Brkr Combust FAN PWRIFM Exhaus Motor No P.E Fuse DISC. Size TypeStage Cooling Typical Power Diagram Typical Wiring DiagramsTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Heating Sequence of OperationCooling Sequence of Operation 23 09 13 Instrumentation and Control Devices for Hvac Guide Specifications 581J*04-09Gas Heat/Electric Cooling Packaged Rooftop 23 07 16 Hvac Equipment Insulation23 09 33 Electric and Electronic Control System for Hvac 23 81 19 Self-Contained Air Conditioners 23 09 93 Sequence of Operations for Hvac Controls23 40 13 Panel Air Filters 581J 581J 581J 581J 581J 581J 581J
Related manuals
Manual 40 pages 41.76 Kb

581J specifications

The Bryant 581J is a high-efficiency gas furnace that exemplifies advanced heating technology and innovative design. Known for its reliability and comfort, the Bryant 581J offers impressive performance features that cater to both residential and commercial heating needs. One of its standout characteristics is the two-stage heating system, which allows the furnace to operate at a lower stage when the heating demand is modest, providing improved comfort and energy efficiency. This feature also minimizes temperature fluctuations, ensuring a more consistent and comfortable indoor environment.

Energy efficiency is a critical aspect of the Bryant 581J. With an annual fuel utilization efficiency (AFUE) rating of up to 96%, this furnace is designed to convert a high percentage of fuel into usable heat, which helps homeowners save on energy bills. The high-efficiency design also contributes to a reduced carbon footprint, aligning with modern environmental concerns.

The Bryant 581J is equipped with technologically advanced features, including the ComfortTechâ„¢ control system. This system enables enhanced temperature regulation and integrates easily with smart home systems, allowing homeowners the convenience of remote control through smartphones and tablets. Additionally, the furnace includes an electronically commutated motor (ECM) blower, which optimizes airflow and reduces energy consumption while enhancing the overall comfort level within the space.

Noise reduction is another key characteristic of the Bryant 581J. The furnace is engineered with sound-dampening technology, resulting in quieter operation compared to conventional furnaces. This attention to noise management makes it an appealing choice for residential applications, where peace and tranquility are crucial.

The durable construction of the Bryant 581J ensures longevity and reliability. With a robust cabinet and quality materials, it is built to withstand the rigors of daily operation. Furthermore, the furnace comes with a warranty that provides peace of mind, protecting the investment over the years.

Overall, the Bryant 581J represents a blend of efficiency, advanced technology, and reliable performance. With its high AFUE rating, innovative features, and quiet operation, it stands out in the market as a top choice for anyone seeking a dependable heating solution. Whether for new installations or replacements, the Bryant 581J is designed to meet the heating demands of today's energy-conscious homeowners.