CURBS & WEIGHTS DIMENSIONS - 580J 08-12 (cont.)

CURBS & WEIGHTS DIMENSIONS - 580J 08-12 (cont.)

580J

C

B

C101218

Fig. 6 - 580J 08-12

D

A

C08337

 

 

 

Fig. 7 - Service Clearance

 

 

 

LOC

DIMENSION

CONDITION

 

48---

in (1219 mm)

Unit disconnect is mounted on panel

 

36---

in (914 mm)

If dimension--- B is 12--- in (305 mm)

A

18---

in (457 mm)

No disconnect, convenience outlet option

 

18---

in (457 mm)

Recommended service clearance (use electric screwdriver)

 

12---

in (305 mm)

Minimum clearance (use manual ratchet screwdriver)

 

 

 

 

 

36---

in (914 mm)

Unit has economizer

B

12---

in (305 mm)

If dimension--- A is 36--- in (914 mm)

 

 

Special

Check for sources of flue products within 10--- ft of unit fresh air intake hood

 

 

 

 

C

36---

in (914 mm)

Side condensate drain is used

18---

in (457 mm)

Minimum clearance

 

 

 

 

 

 

48---

in (1219 mm)

No flue discharge accessory installed, surface is combustible material

D

42---

in (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

36---

in (914 mm)

Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)

 

 

 

Special

Check for adjacent units or building fresh air intakes within 10--- ft of this unit’s flue outlet

22

Image 22
Contents Unit shown with optional louvered hail guard Product Data580J the environmentally sound refrigerantEasy to maintain TABLE OF CONTENTSEasy to install Easy to useFEATURES AND BENEFITS 580JMODEL NUMBER NOMENCLATURE 580J580J CATEGORYFACTORY OPTIONS AND/OR ACCESSORIES FACTORY OPTIONS AND/OR ACCESSORIES cont LEGEND Table 2 – AHRI COOLING RATING TABLE580J NOTES580J AL/SS HEAT EXCHANGERTable 5 – SOUND PERFORMANCE TABLE 580JTable 4 - HEATING RATING TABLE - LOW NOx1 dB ---DecibelCOOLING 580JUNIT HEATINGCOOLING 580JTable 7 – PHYSICAL DATA 3 - 6 TONSHEATING Heat Anticipator setting AmpsTable 8 – PHYSICAL DATA 3 - 6 TONSCOOLING 580JTable 9 – PHYSICAL DATA 7.5 - 8.5 TONS7.5 - 8.5 TONS Table 10 – PHYSICAL DATAHEATING 580J10 - 15 TONS Table 11 – PHYSICAL DATACOOLING 580J10 - 15 TONS Table 12 – PHYSICAL DATAHEATING 580JFig. 1 - Dimensions 580J CURBS & WEIGHTS DIMENSIONS - 580J580J Fig. 3 - Service Clearance CURBS & WEIGHTS DIMENSIONS - 580J 04-07contFig. 2 - Dimensions 580J 580JACCESSORY CURBS & WEIGHTS DIMENSIONS - 580J 04-07contACCESSORY 580J580J CURBS & WEIGHTS DIMENSIONS - 580JFig. 5 - Dimensions 580J C101217580J CURBS & WEIGHTS DIMENSIONS - 580J 08-12contFig. 7 - Service Clearance Fig. 6 - 580J580J CURBS & WEIGHTS DIMENSIONS - 580JACCESSORY Fig. 8 - Roof Curb Details580J CURBS & WEIGHTS DIMENSIONS - 580JFig. 9 - Dimensions 580J-14 C101223Fig. 10 - Service Clearance CURBS & WEIGHTS DIMENSIONS - 580J 14 cont580J 580J CURBS & WEIGHTS DIMENSIONS - 580JC101231 580J CURBS & WEIGHTS DIMENSIONS - 580J 16 contC101232 580J CURBS & WEIGHTS DIMENSIONS - 580JC10772 OPTIONS & ACCESSORY WEIGHTS 580JAPPLICATION DATA Low ambient applications APPLICATION DATA contSizing a rooftop 580JI.Determine cooling and heating loads SELECTION PROCEDURE WITH 580J*07A EXAMPLE1580J II.Make an initial guess at cooling tons3 TONS Table 13 - COOLING CAPACITIES1-STAGECOOLING 580J1-STAGECOOLING 580JTable 14 – COOLING CAPACITIES 3 TONS4 TONS Table 15 – COOLING CAPACITIES1-STAGECOOLING 580J1-STAGECOOLING 580JTable 16 – COOLING CAPACITIES 4 TONS5 TONS Table 17 – COOLING CAPACITIES1-STAGECOOLING 580J1-STAGECOOLING 580JTable 18 – COOLING CAPACITIES 5 TONS6 TONS Table 19 – COOLING CAPACITIES1-STAGECOOLING 580J1-STAGECOOLING 580JTable 20 – COOLING CAPACITIES 6 TONS7.5 TONS Table 21 – COOLING CAPACITIES1-STAGECOOLING 580J2-STAGECOOLING 580JTable 22 – COOLING CAPACITIES 7.5 TONS7.5 TONS Table 23 – COOLING CAPACITIES2-STAGECOOLING 580J1-STAGECOOLING 580JTable 24 – COOLING CAPACITIES 8.5 TONS8.5 TONS Table 25 – COOLING CAPACITIES2-STAGECOOLING 580J2-STAGECOOLING 580JTable 26 – COOLING CAPACITIES 8.5 TONS10 TONS Table 27 - COOLING CAPACITIES1-STAGECOOLING 580J2-STAGECOOLING 580JTable 28 – COOLING CAPACITIES 10 TONS10 TONS Table 29 – COOLING CAPACITIES2-STAGECOOLING 580J2-STAGECOOLING 580JTable 30 - COOLING CAPACITIES 12.5 TONS12.5 TONS Table 31 – COOLING CAPACITIES2-STAGECOOLING 580J2-STAGECOOLING 580JTable 32 – COOLING CAPACITIES 15 TONSFig. 14 - Horizontal Power Exhaust Performance ECONOMIZER, BAROMETRIC RELIEF AND PE PERFORMANCEHorizontal Power Exhaust PERFECT HUMIDITYFig. 15 - Barometric Relief Flow Capacity Fig. 18 - Vertical Power Exhaust Performance580J Fig. 19 - Barometric Relief Flow-Horizontal15 TonGeneral fan performance notes Fig. 23 - Horizontal Power Exhaust Performance580J 1 PHASE FAN PERFORMANCE1 PHASE 580J3 PHASE FAN PERFORMANCE cont3 PHASE Table 36 - 580J**04FAN PERFORMANCE cont 1 PHASE1 PHASE 580JFAN PERFORMANCE cont 3 PHASE3 PHASE Table 40 – 580J**05FAN PERFORMANCE cont 1 PHASE1 PHASE 580JFAN PERFORMANCE cont 3 PHASE3 PHASE Table 44 – 580J**06FAN PERFORMANCE cont 3 PHASE3 PHASE 580JFAN PERFORMANCE cont 3 PHASE3 PHASE Table 48 – 580J**08FAN PERFORMANCE cont 3 PHASE3 PHASE 580JFAN PERFORMANCE cont 3 PHASE3 PHASE Table 52 – 580J**12FAN PERFORMANCE cont 3 PHASE3 PHASE 580JTable 56 – 580J*16 3 PHASE3 PHASE 15 TON VERTICAL SUPPLYFAN PERFORMANCE cont Table 58 - PULLEY ADJUSTMENTFactory settings 580J1-StageCooling ELECTRICAL INFORMATIONTable 59 – 580J*04A 3 TONSTable 62 – 580J*07A ELECTRICAL INFORMATION cont580J 1-StageCooling1-StageCooling ELECTRICAL INFORMATION contTable 65 – 580J*09A 8.5 TONSTable 68 – 580J*12D ELECTRICAL INFORMATION cont580J 2-StageCooling580J COMBUSTION580J COMBUSTIONTable 72 – MCA/MOCP DETERMINATION W/ PWRD C.O 580JTABLE 68 cont. MCA/MOCP DETERMINATION W/ PWRD C.O 580JFig. 24 - 1-StageCooling Typical Power Diagram TYPICAL WIRING DIAGRAMS580J 580J Fig. 25 - 2-StageCooling Typical Power DiagramC08577B 580J Fig. 26 - 1-StageTypical Wiring DiagramC08524 580J Fig. 27 - 2-StageTypical Wiring DiagramC08578 Electromechanical units with an economizer SEQUENCE OF OPERATIONElectromechanical units with no economizer Cooling —Reheat1 Subcooling Mode - 580J04-16 SEQUENCE OF OPERATION contNormal Cooling Reheat2 Hot Gas Reheat Mode - 580J04-16580J RH2.x580J GUIDE SPECIFICATIONS - 580J**04-16Gas Heat/Electric Cooling Packaged Rooftop Size Range23 81 19 Self-ContainedAir Conditioners 23 09 93 Sequence of Operations for HVAC Controls23 40 13 Panel Air Filters 580J580J 3.Unit shall be designed to conform to ASHRAE 15,5.Base Rail 580J580J 3.Standard Heat Exchanger construction5.Standard All Aluminum Novation Coils 580J580J 2.Belt-drivenEvaporator Fan3.Manual damper 580Jc.Disconnect Switch Bracket 580J21.Winter start kit 580JPrinted in U.S.A 580JCatalog No. PDS580J---10 Edition Date: 01/11