Bryant 580J manual Cooling Capacities, Stagecooling, Tons

Page 43
Table 23 – COOLING CAPACITIES

Table 23 – COOLING CAPACITIES

2-STAGE COOLING

 

 

 

 

 

 

7.5 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580J08 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

 

 

 

 

 

 

 

 

 

AIR ENTERING EVAPORATOR --- CFM

 

 

 

 

 

TEMP (F) AIR ENT

 

2250/0.05

 

 

 

 

3000/0.07

 

 

 

 

3750/0.09

 

 

CONDENSER (Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator --- Ewb (F)

 

 

 

 

 

 

 

 

 

72

 

67

 

62

 

72

 

67

 

62

 

72

 

67

 

62

 

 

TC

103.05

 

93.02

 

83.60

 

109.77

 

99.52

 

90.08

 

114.01

 

103.69

 

95.19

75

 

SHC

43.66

 

55.34

 

67.09

 

50.99

 

66.29

 

81.31

 

57.49

 

76.27

 

92.20

 

 

kW

4.90

 

4.83

 

4.77

 

4.82

 

4.88

 

4.96

 

4.99

 

4.91

 

4.85

 

 

TC

95.39

 

85.83

 

76.88

 

101.59

 

91.89

 

82.95

 

105.53

 

95.76

 

87.77

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

36.42

 

48.47

 

60.60

 

43.24

 

58.99

 

74.40

 

49.44

 

68.68

 

84.90

 

 

kW

5.49

 

5.42

 

5.36

 

5.40

 

5.47

 

5.54

 

5.58

 

5.50

 

5.44

 

 

TC

87.48

 

78.44

 

69.97

 

93.21

 

84.05

 

75.61

 

96.84

 

87.63

 

80.14

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

28.98

 

41.46

 

53.97

 

35.32

 

51.53

 

67.34

 

41.21

 

60.92

 

77.41

 

 

kW

6.16

 

6.09

 

6.03

 

6.08

 

6.14

 

6.21

 

6.24

 

6.17

 

6.11

 

 

TC

79.35

 

70.83

 

62.84

 

84.57

 

75.96

 

68.04

 

87.88

 

79.23

 

72.26

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

21.34

 

34.26

 

47.18

 

27.17

 

43.86

 

60.08

 

32.73

 

52.95

 

69.70

 

 

kW

6.93

 

6.86

 

6.81

 

6.85

 

6.91

 

6.97

 

7.00

 

6.93

 

6.88

 

 

TC

70.87

 

62.89

 

55.42

 

75.58

 

67.54

 

60.15

 

78.56

 

70.51

 

64.06

115

 

SHC

13.40

 

26.79

 

40.14

 

18.70

 

35.89

 

52.54

 

23.94

 

44.68

 

61.67

 

 

kW

7.79

 

7.74

 

7.69

 

7.73

 

7.78

 

7.83

 

7.86

 

7.80

 

7.76

 

 

 

 

580J08 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

 

 

 

 

 

 

 

 

 

AIR ENTERING EVAPORATOR --- Ewb (F)

 

 

 

 

 

 

 

 

 

 

75 Dry Bulb

 

 

 

 

75 Dry Bulb

 

 

 

 

75 Dry Bulb

 

TEMP (F) AIR ENT

 

62.5 Wet Bulb

 

 

 

64 Wet Bulb

 

 

 

65.3 Wet Bulb

 

CONDENSER (Edb)

 

(50% Relative)

 

 

 

(56% Relative)

 

 

 

(60% Relative)

 

 

 

 

 

 

 

 

 

Air Entering Evaporator --- Cfm

 

 

 

 

 

 

 

 

 

2250

3000

 

3750

2250

3000

 

3750

 

2250

3000

 

3750

 

 

TC

27.60

32.75

 

30.19

40.09

39.43

 

37.73

 

45.06

45.25

 

44.25

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

--- 3.12

5.20

 

6.71

3.75

5.24

 

6.75

 

3.77

5.26

 

6.78

 

 

kW

4.56

4.51

 

4.46

4.63

4.60

 

4.56

 

4.70

4.67

 

4.64

 

 

TC

35.40

33.78

 

31.20

41.14

40.51

 

38.80

 

46.15

46.37

 

45.38

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

4.67

6.17

 

7.69

4.71

6.21

 

7.73

 

4.74

6.24

 

7.76

 

 

kW

4.41

4.36

 

4.39

4.41

4.36

 

4.36

 

4.41

4.39

 

4.36

 

 

TC

36.36

34.71

 

32.18

42.10

41.47

 

39.77

 

47.08

47.31

 

46.32

70

 

SHC

5.63

7.14

 

8.66

5.67

7.18

 

8.71

 

5.70

7.21

 

8.74

 

 

kW

4.43

4.49

 

4.41

4.44

4.40

 

4.39

 

4.49

4.47

 

4.44

 

 

TC

38.25

36.64

 

34.15

43.97

43.37

 

41.72

 

48.98

49.22

 

48.26

60

 

SHC

7.56

9.09

 

10.62

7.60

9.13

 

10.66

 

7.62

9.15

 

10.69

 

 

kW

4.56

4.55

 

4.43

4.57

4.53

 

4.46

 

4.56

4.55

 

4.50

 

 

TC

40.15

38.60

 

36.14

45.95

45.37

 

43.73

 

50.57

50.97

 

49.56

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

9.48

11.03

 

12.58

9.52

11.07

 

12.62

 

9.54

11.10

 

12.64

 

 

kW

4.63

4.52

 

4.38

4.45

4.41

 

4.33

 

5.25

4.91

 

5.60

 

 

TC

42.18

40.62

 

38.11

47.80

47.25

 

45.43

 

52.65

52.75

 

51.83

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

11.41

12.98

 

14.54

11.45

13.02

 

14.58

 

11.47

13.04

 

14.60

 

 

kW

4.32

4.37

 

4.37

4.65

4.60

 

4.89

 

4.96

5.20

 

5.12

 

 

 

 

NOTE: Perfect Humidity only available on 2--- stage RTPF models.

NOTES:

 

 

LEGEND

 

 

 

Edb

---

Entering Dry--- Bulb

1. Direct interpolation is permissible. Do not extrapolate.

Ewb

---

Entering Wet--- Bulb

2. The following formulas may be used:

kW

---

Compressor Motor Power Input

 

sensible capacity (Btuh)

 

Idb

---

Leaving Dry--- Bulb

tldb = tedb

1.10 x cfm

Iwb

---

Leaving Wet--- Bulb

tlwb = Wet--- bulb temperature corresponding to enthalpy of air

SHC ---

Sensible Heat Capacity (1000 Btuh) Gross

leaving evaporator coil (hlwb)

TC

---

Total Capacity (1000 Btuh) Gross

 

total capacity (Btuh)

 

 

 

 

hlwb = hewb

 

 

 

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

580J

43

Image 43
Contents the environmentally sound refrigerant Product Data580J Unit shown with optional louvered hail guardEasy to use TABLE OF CONTENTSEasy to install Easy to maintain580J FEATURES AND BENEFITS580J MODEL NUMBER NOMENCLATURECATEGORY 580JFACTORY OPTIONS AND/OR ACCESSORIES FACTORY OPTIONS AND/OR ACCESSORIES cont NOTES Table 2 – AHRI COOLING RATING TABLE580J LEGENDAL/SS HEAT EXCHANGER 580JdB ---Decibel 580JTable 4 - HEATING RATING TABLE - LOW NOx1 Table 5 – SOUND PERFORMANCE TABLEHEATING 580JUNIT COOLING3 - 6 TONS 580JTable 7 – PHYSICAL DATA COOLING3 - 6 TONS Heat Anticipator setting AmpsTable 8 – PHYSICAL DATA HEATING7.5 - 8.5 TONS 580JTable 9 – PHYSICAL DATA COOLING580J Table 10 – PHYSICAL DATAHEATING 7.5 - 8.5 TONS580J Table 11 – PHYSICAL DATACOOLING 10 - 15 TONS580J Table 12 – PHYSICAL DATAHEATING 10 - 15 TONSFig. 1 - Dimensions 580J CURBS & WEIGHTS DIMENSIONS - 580J580J 580J CURBS & WEIGHTS DIMENSIONS - 580J 04-07contFig. 2 - Dimensions 580J Fig. 3 - Service Clearance580J CURBS & WEIGHTS DIMENSIONS - 580J 04-07contACCESSORY ACCESSORYC101217 CURBS & WEIGHTS DIMENSIONS - 580JFig. 5 - Dimensions 580J 580JFig. 6 - 580J CURBS & WEIGHTS DIMENSIONS - 580J 08-12contFig. 7 - Service Clearance 580JFig. 8 - Roof Curb Details CURBS & WEIGHTS DIMENSIONS - 580JACCESSORY 580JC101223 CURBS & WEIGHTS DIMENSIONS - 580JFig. 9 - Dimensions 580J-14 580JFig. 10 - Service Clearance CURBS & WEIGHTS DIMENSIONS - 580J 14 cont580J 580J CURBS & WEIGHTS DIMENSIONS - 580JC101231 580J CURBS & WEIGHTS DIMENSIONS - 580J 16 contC101232 580J CURBS & WEIGHTS DIMENSIONS - 580JC10772 580J OPTIONS & ACCESSORY WEIGHTSAPPLICATION DATA 580J APPLICATION DATA contSizing a rooftop Low ambient applicationsII.Make an initial guess at cooling tons SELECTION PROCEDURE WITH 580J*07A EXAMPLE1580J I.Determine cooling and heating loads580J Table 13 - COOLING CAPACITIES1-STAGECOOLING 3 TONS3 TONS 580JTable 14 – COOLING CAPACITIES 1-STAGECOOLING580J Table 15 – COOLING CAPACITIES1-STAGECOOLING 4 TONS4 TONS 580JTable 16 – COOLING CAPACITIES 1-STAGECOOLING580J Table 17 – COOLING CAPACITIES1-STAGECOOLING 5 TONS5 TONS 580JTable 18 – COOLING CAPACITIES 1-STAGECOOLING580J Table 19 – COOLING CAPACITIES1-STAGECOOLING 6 TONS6 TONS 580JTable 20 – COOLING CAPACITIES 1-STAGECOOLING580J Table 21 – COOLING CAPACITIES1-STAGECOOLING 7.5 TONS7.5 TONS 580JTable 22 – COOLING CAPACITIES 2-STAGECOOLING580J Table 23 – COOLING CAPACITIES2-STAGECOOLING 7.5 TONS8.5 TONS 580JTable 24 – COOLING CAPACITIES 1-STAGECOOLING580J Table 25 – COOLING CAPACITIES2-STAGECOOLING 8.5 TONS8.5 TONS 580JTable 26 – COOLING CAPACITIES 2-STAGECOOLING580J Table 27 - COOLING CAPACITIES1-STAGECOOLING 10 TONS10 TONS 580JTable 28 – COOLING CAPACITIES 2-STAGECOOLING580J Table 29 – COOLING CAPACITIES2-STAGECOOLING 10 TONS12.5 TONS 580JTable 30 - COOLING CAPACITIES 2-STAGECOOLING580J Table 31 – COOLING CAPACITIES2-STAGECOOLING 12.5 TONS15 TONS 580JTable 32 – COOLING CAPACITIES 2-STAGECOOLINGPERFECT HUMIDITY ECONOMIZER, BAROMETRIC RELIEF AND PE PERFORMANCEHorizontal Power Exhaust Fig. 14 - Horizontal Power Exhaust PerformanceFig. 19 - Barometric Relief Flow-Horizontal15 Ton Fig. 18 - Vertical Power Exhaust Performance580J Fig. 15 - Barometric Relief Flow CapacityGeneral fan performance notes Fig. 23 - Horizontal Power Exhaust Performance580J 580J FAN PERFORMANCE1 PHASE 1 PHASETable 36 - 580J**04 FAN PERFORMANCE cont3 PHASE 3 PHASE580J 1 PHASE1 PHASE FAN PERFORMANCE contTable 40 – 580J**05 3 PHASE3 PHASE FAN PERFORMANCE cont580J 1 PHASE1 PHASE FAN PERFORMANCE contTable 44 – 580J**06 3 PHASE3 PHASE FAN PERFORMANCE cont580J 3 PHASE3 PHASE FAN PERFORMANCE contTable 48 – 580J**08 3 PHASE3 PHASE FAN PERFORMANCE cont580J 3 PHASE3 PHASE FAN PERFORMANCE contTable 52 – 580J**12 3 PHASE3 PHASE FAN PERFORMANCE cont580J 3 PHASE3 PHASE FAN PERFORMANCE cont15 TON VERTICAL SUPPLY 3 PHASE3 PHASE Table 56 – 580J*16580J Table 58 - PULLEY ADJUSTMENTFactory settings FAN PERFORMANCE cont3 TONS ELECTRICAL INFORMATIONTable 59 – 580J*04A 1-StageCooling1-StageCooling ELECTRICAL INFORMATION cont580J Table 62 – 580J*07A8.5 TONS ELECTRICAL INFORMATION contTable 65 – 580J*09A 1-StageCooling2-StageCooling ELECTRICAL INFORMATION cont580J Table 68 – 580J*12DCOMBUSTION 580JCOMBUSTION 580J580J Table 72 – MCA/MOCP DETERMINATION W/ PWRD C.O580J TABLE 68 cont. MCA/MOCP DETERMINATION W/ PWRD C.OFig. 24 - 1-StageCooling Typical Power Diagram TYPICAL WIRING DIAGRAMS580J 580J Fig. 25 - 2-StageCooling Typical Power DiagramC08577B 580J Fig. 26 - 1-StageTypical Wiring DiagramC08524 580J Fig. 27 - 2-StageTypical Wiring DiagramC08578 Cooling — SEQUENCE OF OPERATIONElectromechanical units with no economizer Electromechanical units with an economizerReheat2 Hot Gas Reheat Mode - 580J04-16 SEQUENCE OF OPERATION contNormal Cooling Reheat1 Subcooling Mode - 580J04-16RH2.x 580JSize Range GUIDE SPECIFICATIONS - 580J**04-16Gas Heat/Electric Cooling Packaged Rooftop 580J580J 23 09 93 Sequence of Operations for HVAC Controls23 40 13 Panel Air Filters 23 81 19 Self-ContainedAir Conditioners3.Unit shall be designed to conform to ASHRAE 15, 580J580J 5.Base Rail3.Standard Heat Exchanger construction 580J580J 5.Standard All Aluminum Novation Coils2.Belt-drivenEvaporator Fan 580J580J 3.Manual damper580J c.Disconnect Switch Bracket580J 21.Winter start kitEdition Date: 01/11 580JCatalog No. PDS580J---10 Printed in U.S.A
Related manuals
Manual 86 pages 11.72 Kb