Bryant manual CURBS & WEIGHTS DIMENSIONS - 580J 14 cont, Service Clearance

Page 25
CURBS & WEIGHTS DIMENSIONS - 580J 14 (cont.)

CURBS & WEIGHTS DIMENSIONS - 580J 14 (cont.)

580J

C

B

C101224

D

A

C08337

 

 

 

Fig. 10 - Service Clearance

 

 

 

LOC

DIMENSION

CONDITION

 

48---

in (1219 mm)

Unit disconnect is mounted on panel

 

36---

in (914 mm)

If dimension--- B is 12--- in (305 mm)

A

18---

in (457 mm)

No disconnect, convenience outlet option

 

18---

in (457 mm)

Recommended service clearance (use electric screwdriver)

 

12---

in (305 mm)

Minimum clearance (use manual ratchet screwdriver)

 

 

 

 

 

36---

in (914 mm)

Unit has economizer

B

12---

in (305 mm)

If dimension--- A is 36--- in (914 mm)

 

 

Special

Check for sources of flue products within 10--- ft of unit fresh air intake hood

C

36---

in (914 mm)

Side condensate drain is used

18---

in (457 mm)

Minimum clearance

 

 

 

 

 

 

48---

in (1219 mm)

No flue discharge accessory installed, surface is combustible material

D

42---

in (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

36---

in (914 mm)

Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)

 

 

 

Special

Check for adjacent units or building fresh air intakes within 10--- ft of this unit’s flue outlet

 

 

 

 

25

Image 25
Contents 580J Product DataUnit shown with optional louvered hail guard the environmentally sound refrigerantEasy to install TABLE OF CONTENTSEasy to maintain Easy to use580J FEATURES AND BENEFITS580J MODEL NUMBER NOMENCLATURECATEGORY 580JFACTORY OPTIONS AND/OR ACCESSORIES FACTORY OPTIONS AND/OR ACCESSORIES cont 580J Table 2 – AHRI COOLING RATING TABLELEGEND NOTESAL/SS HEAT EXCHANGER 580JTable 4 - HEATING RATING TABLE - LOW NOx1 580JTable 5 – SOUND PERFORMANCE TABLE dB ---DecibelUNIT 580JCOOLING HEATINGTable 7 – PHYSICAL DATA 580JCOOLING 3 - 6 TONSTable 8 – PHYSICAL DATA Heat Anticipator setting AmpsHEATING 3 - 6 TONSTable 9 – PHYSICAL DATA 580JCOOLING 7.5 - 8.5 TONSHEATING Table 10 – PHYSICAL DATA7.5 - 8.5 TONS 580JCOOLING Table 11 – PHYSICAL DATA10 - 15 TONS 580JHEATING Table 12 – PHYSICAL DATA10 - 15 TONS 580JFig. 1 - Dimensions 580J CURBS & WEIGHTS DIMENSIONS - 580J580J Fig. 2 - Dimensions 580J CURBS & WEIGHTS DIMENSIONS - 580J 04-07contFig. 3 - Service Clearance 580JACCESSORY CURBS & WEIGHTS DIMENSIONS - 580J 04-07contACCESSORY 580JFig. 5 - Dimensions 580J CURBS & WEIGHTS DIMENSIONS - 580J580J C101217Fig. 7 - Service Clearance CURBS & WEIGHTS DIMENSIONS - 580J 08-12cont580J Fig. 6 - 580JACCESSORY CURBS & WEIGHTS DIMENSIONS - 580J580J Fig. 8 - Roof Curb DetailsFig. 9 - Dimensions 580J-14 CURBS & WEIGHTS DIMENSIONS - 580J580J C101223Fig. 10 - Service Clearance CURBS & WEIGHTS DIMENSIONS - 580J 14 cont580J 580J CURBS & WEIGHTS DIMENSIONS - 580JC101231 580J CURBS & WEIGHTS DIMENSIONS - 580J 16 contC101232 580J CURBS & WEIGHTS DIMENSIONS - 580JC10772 580J OPTIONS & ACCESSORY WEIGHTSAPPLICATION DATA Sizing a rooftop APPLICATION DATA contLow ambient applications 580J580J SELECTION PROCEDURE WITH 580J*07A EXAMPLE1I.Determine cooling and heating loads II.Make an initial guess at cooling tons1-STAGECOOLING Table 13 - COOLING CAPACITIES3 TONS 580JTable 14 – COOLING CAPACITIES 580J1-STAGECOOLING 3 TONS1-STAGECOOLING Table 15 – COOLING CAPACITIES4 TONS 580JTable 16 – COOLING CAPACITIES 580J1-STAGECOOLING 4 TONS1-STAGECOOLING Table 17 – COOLING CAPACITIES5 TONS 580JTable 18 – COOLING CAPACITIES 580J1-STAGECOOLING 5 TONS1-STAGECOOLING Table 19 – COOLING CAPACITIES6 TONS 580JTable 20 – COOLING CAPACITIES 580J1-STAGECOOLING 6 TONS1-STAGECOOLING Table 21 – COOLING CAPACITIES7.5 TONS 580JTable 22 – COOLING CAPACITIES 580J2-STAGECOOLING 7.5 TONS2-STAGECOOLING Table 23 – COOLING CAPACITIES7.5 TONS 580JTable 24 – COOLING CAPACITIES 580J1-STAGECOOLING 8.5 TONS2-STAGECOOLING Table 25 – COOLING CAPACITIES8.5 TONS 580JTable 26 – COOLING CAPACITIES 580J2-STAGECOOLING 8.5 TONS1-STAGECOOLING Table 27 - COOLING CAPACITIES10 TONS 580JTable 28 – COOLING CAPACITIES 580J2-STAGECOOLING 10 TONS2-STAGECOOLING Table 29 – COOLING CAPACITIES10 TONS 580JTable 30 - COOLING CAPACITIES 580J2-STAGECOOLING 12.5 TONS2-STAGECOOLING Table 31 – COOLING CAPACITIES12.5 TONS 580JTable 32 – COOLING CAPACITIES 580J2-STAGECOOLING 15 TONSHorizontal Power Exhaust ECONOMIZER, BAROMETRIC RELIEF AND PE PERFORMANCEFig. 14 - Horizontal Power Exhaust Performance PERFECT HUMIDITY580J Fig. 18 - Vertical Power Exhaust PerformanceFig. 15 - Barometric Relief Flow Capacity Fig. 19 - Barometric Relief Flow-Horizontal15 TonGeneral fan performance notes Fig. 23 - Horizontal Power Exhaust Performance580J 1 PHASE FAN PERFORMANCE1 PHASE 580J3 PHASE FAN PERFORMANCE cont3 PHASE Table 36 - 580J**041 PHASE 1 PHASEFAN PERFORMANCE cont 580J3 PHASE 3 PHASEFAN PERFORMANCE cont Table 40 – 580J**051 PHASE 1 PHASEFAN PERFORMANCE cont 580J3 PHASE 3 PHASEFAN PERFORMANCE cont Table 44 – 580J**063 PHASE 3 PHASEFAN PERFORMANCE cont 580J3 PHASE 3 PHASEFAN PERFORMANCE cont Table 48 – 580J**083 PHASE 3 PHASEFAN PERFORMANCE cont 580J3 PHASE 3 PHASEFAN PERFORMANCE cont Table 52 – 580J**123 PHASE 3 PHASEFAN PERFORMANCE cont 580J3 PHASE 3 PHASETable 56 – 580J*16 15 TON VERTICAL SUPPLYFactory settings Table 58 - PULLEY ADJUSTMENTFAN PERFORMANCE cont 580JTable 59 – 580J*04A ELECTRICAL INFORMATION1-StageCooling 3 TONS580J ELECTRICAL INFORMATION contTable 62 – 580J*07A 1-StageCoolingTable 65 – 580J*09A ELECTRICAL INFORMATION cont1-StageCooling 8.5 TONS580J ELECTRICAL INFORMATION contTable 68 – 580J*12D 2-StageCoolingCOMBUSTION 580JCOMBUSTION 580J580J Table 72 – MCA/MOCP DETERMINATION W/ PWRD C.O580J TABLE 68 cont. MCA/MOCP DETERMINATION W/ PWRD C.OFig. 24 - 1-StageCooling Typical Power Diagram TYPICAL WIRING DIAGRAMS580J 580J Fig. 25 - 2-StageCooling Typical Power DiagramC08577B 580J Fig. 26 - 1-StageTypical Wiring DiagramC08524 580J Fig. 27 - 2-StageTypical Wiring DiagramC08578 Electromechanical units with no economizer SEQUENCE OF OPERATIONElectromechanical units with an economizer Cooling —Normal Cooling SEQUENCE OF OPERATION contReheat1 Subcooling Mode - 580J04-16 Reheat2 Hot Gas Reheat Mode - 580J04-16RH2.x 580JGas Heat/Electric Cooling Packaged Rooftop GUIDE SPECIFICATIONS - 580J**04-16580J Size Range23 40 13 Panel Air Filters 23 09 93 Sequence of Operations for HVAC Controls23 81 19 Self-ContainedAir Conditioners 580J3.Unit shall be designed to conform to ASHRAE 15, 580J580J 5.Base Rail3.Standard Heat Exchanger construction 580J580J 5.Standard All Aluminum Novation Coils2.Belt-drivenEvaporator Fan 580J580J 3.Manual damper580J c.Disconnect Switch Bracket580J 21.Winter start kitCatalog No. PDS580J---10 580JPrinted in U.S.A Edition Date: 01/11