Bryant 580J manual Application Data

Page 30
APPLICATION DATA

APPLICATION DATA

580J

Min operating ambient temp (cooling):

In mechanical cooling mode, your Bryant rooftop unit can safely operate down to an outdoor ambient temperature of 40_F (4_C) and 25_F (-4_C), with an accessory winter start kit. It is possible to provide cooling at lower outdoor ambient temperatures by using less outside air, economizers, and/or accessory low ambient kits.

Max operating ambient temp (cooling):

The maximum operating ambient temperature for cooling mode is 115_F (46_C). While cooling operation above 115_F (46_C) may be possible, it could cause either a reduction in performance, reliability, or a protective action by the unit’s internal safety devices.

Min mixed air temp (heating):

Using the factory settings, the minimum temperatures for the mixed air (the combined temperature of the warm return air and the cold outdoor air) entering the dimpled, gas heat exchangers are:

Aluminized

Stainless Steel

50_F (10_C) continuous

40_F (4_C) continuous

45_F (7_C) intermittent

35_F (2_C) intermittent

Operating at lower mixed-air temperatures may be possible, if a field supplied, outdoor air thermostat initiates both heat stages when the temperature is less than the minimum temperatures listed above. Please contact your local Bryant representative for assistance.

Min and max airflow (heating and cooling):

To maintain safe and reliable operation of your rooftop, operate within the heating airflow limits during heating mode and cooling airflow limits during cooling mode. Operating above the max may cause blow-off, undesired airflow noise, or airflow related problems with the rooftop unit. Operating below the min may cause problems with coil freeze-up and unsafe heating operation. Heating and cooling limitations differ when evaluating operating CFM, the minimum value is the HIGHER of the cooling and heating minimum CFM values published in Table 7 and the maximum value is the LOWER of the cooling and heating maximum values published in Table 7.

Heating-to-cooling changeover:

Your unit will automatically change from heating to cooling mode when using a thermostat with an auto-changeover feature.

Airflow:

All units are draw-through in cooling mode and blow-through in heating mode.

Outdoor air application strategies:

Economizers reduce operating expenses and compressor run time by providing a free source of cooling and a means of ventilation to match application changing needs. In fact, they should be considered for most applications. Also, consider the various economizer control methods and their benefits, as well as sensors required to accomplish your application goals. Please contact your local Bryant representative for assistance.

Motor limits, Brake horsepower (BHP):

Due to internal design of Bryant units, the air path, and specially designed motors, the full horsepower (maximum continuous BHP) band, as listed in Table 8 and 10, can be used with the utmost confidence. There is no need for extra safety factors, as Bryant motors are designed and rigorously tested to use the entire, listed BHP range without either nuisance tripping or premature motor failure.

Propane heating:

Propane has different physical qualities than natural gas. As a result, propane requires different fuel to air mixture. To optimize the fuel/air mixture for propane, Bryant sells different burner orifices in an easy to install accessory kit. To select the correct burner orifices or determine the heat capacity for a propane application, use either the selection software, or the unit’s service manual.

High altitude heating:

High altitudes have less oxygen, which affects the fuel/air mixture in heat exchangers. In order to maintain a proper fuel/air mixture, heat exchangers operating in altitudes above 2000 ft (610 m) require different orifices. To select the correct burner orifices or determine the heat capacity for a high altitude application, use either the selection software, or the unit’s service manual.

High altitudes have less oxygen, which means heat exchangers need less fuel. The new gas orifices in this field installed kit make the necessary adjustment for high altitude applications. They restore the optimal fuel to air mixture and maintain healthy combustion on altitudes above 2000 ft (610 m).

NOTE: Typical natural gas heating value ranges from 975 to 1050 Btu/ft3 at sea level nationally. The heating value goes down approximately 1.7% per every thousand feet elevation. Standard factory orifices can typically be used up to 2000 ft (610m) elevation without any operational issues.

NOTE: For installations in Canada, the input rating should be derated by 10% for altitudes from 2000 ft (610m) to 4500 ft (1372m) above sea level.

30

Image 30
Contents Unit shown with optional louvered hail guard Product Data580J the environmentally sound refrigerantEasy to maintain TABLE OF CONTENTSEasy to install Easy to useFEATURES AND BENEFITS 580JMODEL NUMBER NOMENCLATURE 580J580J CATEGORYFACTORY OPTIONS AND/OR ACCESSORIES FACTORY OPTIONS AND/OR ACCESSORIES cont LEGEND Table 2 – AHRI COOLING RATING TABLE580J NOTES580J AL/SS HEAT EXCHANGERTable 5 – SOUND PERFORMANCE TABLE 580JTable 4 - HEATING RATING TABLE - LOW NOx1 dB ---DecibelCOOLING 580JUNIT HEATINGCOOLING 580JTable 7 – PHYSICAL DATA 3 - 6 TONSHEATING Heat Anticipator setting AmpsTable 8 – PHYSICAL DATA 3 - 6 TONSCOOLING 580JTable 9 – PHYSICAL DATA 7.5 - 8.5 TONS7.5 - 8.5 TONS Table 10 – PHYSICAL DATAHEATING 580J10 - 15 TONS Table 11 – PHYSICAL DATACOOLING 580J10 - 15 TONS Table 12 – PHYSICAL DATAHEATING 580JCURBS & WEIGHTS DIMENSIONS - 580J Fig. 1 - Dimensions 580J580J Fig. 3 - Service Clearance CURBS & WEIGHTS DIMENSIONS - 580J 04-07contFig. 2 - Dimensions 580J 580JACCESSORY CURBS & WEIGHTS DIMENSIONS - 580J 04-07contACCESSORY 580J580J CURBS & WEIGHTS DIMENSIONS - 580JFig. 5 - Dimensions 580J C101217580J CURBS & WEIGHTS DIMENSIONS - 580J 08-12contFig. 7 - Service Clearance Fig. 6 - 580J580J CURBS & WEIGHTS DIMENSIONS - 580JACCESSORY Fig. 8 - Roof Curb Details580J CURBS & WEIGHTS DIMENSIONS - 580JFig. 9 - Dimensions 580J-14 C101223CURBS & WEIGHTS DIMENSIONS - 580J 14 cont Fig. 10 - Service Clearance580J CURBS & WEIGHTS DIMENSIONS - 580J 580JC101231 CURBS & WEIGHTS DIMENSIONS - 580J 16 cont 580JC101232 CURBS & WEIGHTS DIMENSIONS - 580J 580JC10772 OPTIONS & ACCESSORY WEIGHTS 580JAPPLICATION DATA Low ambient applications APPLICATION DATA contSizing a rooftop 580JI.Determine cooling and heating loads SELECTION PROCEDURE WITH 580J*07A EXAMPLE1580J II.Make an initial guess at cooling tons3 TONS Table 13 - COOLING CAPACITIES1-STAGECOOLING 580J1-STAGECOOLING 580JTable 14 – COOLING CAPACITIES 3 TONS4 TONS Table 15 – COOLING CAPACITIES1-STAGECOOLING 580J1-STAGECOOLING 580JTable 16 – COOLING CAPACITIES 4 TONS5 TONS Table 17 – COOLING CAPACITIES1-STAGECOOLING 580J1-STAGECOOLING 580JTable 18 – COOLING CAPACITIES 5 TONS6 TONS Table 19 – COOLING CAPACITIES1-STAGECOOLING 580J1-STAGECOOLING 580JTable 20 – COOLING CAPACITIES 6 TONS7.5 TONS Table 21 – COOLING CAPACITIES1-STAGECOOLING 580J2-STAGECOOLING 580JTable 22 – COOLING CAPACITIES 7.5 TONS7.5 TONS Table 23 – COOLING CAPACITIES2-STAGECOOLING 580J1-STAGECOOLING 580JTable 24 – COOLING CAPACITIES 8.5 TONS8.5 TONS Table 25 – COOLING CAPACITIES2-STAGECOOLING 580J2-STAGECOOLING 580JTable 26 – COOLING CAPACITIES 8.5 TONS10 TONS Table 27 - COOLING CAPACITIES1-STAGECOOLING 580J2-STAGECOOLING 580JTable 28 – COOLING CAPACITIES 10 TONS10 TONS Table 29 – COOLING CAPACITIES2-STAGECOOLING 580J2-STAGECOOLING 580JTable 30 - COOLING CAPACITIES 12.5 TONS12.5 TONS Table 31 – COOLING CAPACITIES2-STAGECOOLING 580J2-STAGECOOLING 580JTable 32 – COOLING CAPACITIES 15 TONSFig. 14 - Horizontal Power Exhaust Performance ECONOMIZER, BAROMETRIC RELIEF AND PE PERFORMANCEHorizontal Power Exhaust PERFECT HUMIDITYFig. 15 - Barometric Relief Flow Capacity Fig. 18 - Vertical Power Exhaust Performance580J Fig. 19 - Barometric Relief Flow-Horizontal15 TonFig. 23 - Horizontal Power Exhaust Performance General fan performance notes580J 1 PHASE FAN PERFORMANCE1 PHASE 580J3 PHASE FAN PERFORMANCE cont3 PHASE Table 36 - 580J**04FAN PERFORMANCE cont 1 PHASE1 PHASE 580JFAN PERFORMANCE cont 3 PHASE3 PHASE Table 40 – 580J**05FAN PERFORMANCE cont 1 PHASE1 PHASE 580JFAN PERFORMANCE cont 3 PHASE3 PHASE Table 44 – 580J**06FAN PERFORMANCE cont 3 PHASE3 PHASE 580JFAN PERFORMANCE cont 3 PHASE3 PHASE Table 48 – 580J**08FAN PERFORMANCE cont 3 PHASE3 PHASE 580JFAN PERFORMANCE cont 3 PHASE3 PHASE Table 52 – 580J**12FAN PERFORMANCE cont 3 PHASE3 PHASE 580JTable 56 – 580J*16 3 PHASE3 PHASE 15 TON VERTICAL SUPPLYFAN PERFORMANCE cont Table 58 - PULLEY ADJUSTMENTFactory settings 580J1-StageCooling ELECTRICAL INFORMATIONTable 59 – 580J*04A 3 TONSTable 62 – 580J*07A ELECTRICAL INFORMATION cont580J 1-StageCooling1-StageCooling ELECTRICAL INFORMATION contTable 65 – 580J*09A 8.5 TONSTable 68 – 580J*12D ELECTRICAL INFORMATION cont580J 2-StageCooling580J COMBUSTION580J COMBUSTIONTable 72 – MCA/MOCP DETERMINATION W/ PWRD C.O 580JTABLE 68 cont. MCA/MOCP DETERMINATION W/ PWRD C.O 580JTYPICAL WIRING DIAGRAMS Fig. 24 - 1-StageCooling Typical Power Diagram580J Fig. 25 - 2-StageCooling Typical Power Diagram 580JC08577B Fig. 26 - 1-StageTypical Wiring Diagram 580JC08524 Fig. 27 - 2-StageTypical Wiring Diagram 580JC08578 Electromechanical units with an economizer SEQUENCE OF OPERATIONElectromechanical units with no economizer Cooling —Reheat1 Subcooling Mode - 580J04-16 SEQUENCE OF OPERATION contNormal Cooling Reheat2 Hot Gas Reheat Mode - 580J04-16580J RH2.x580J GUIDE SPECIFICATIONS - 580J**04-16Gas Heat/Electric Cooling Packaged Rooftop Size Range23 81 19 Self-ContainedAir Conditioners 23 09 93 Sequence of Operations for HVAC Controls23 40 13 Panel Air Filters 580J580J 3.Unit shall be designed to conform to ASHRAE 15,5.Base Rail 580J580J 3.Standard Heat Exchanger construction5.Standard All Aluminum Novation Coils 580J580J 2.Belt-drivenEvaporator Fan3.Manual damper 580Jc.Disconnect Switch Bracket 580J21.Winter start kit 580JPrinted in U.S.A 580JCatalog No. PDS580J---10 Edition Date: 01/11
Related manuals
Manual 86 pages 11.72 Kb