Bryant 580G manual Economizer Settings, Mounting Angle With Tabs Attached to Filter Track Assembly

Page 16

4.Remove screws along bottom of damper assembly. Lo- cate and mount blockoff baffle using these screws.

5.Assemble 2 ®lter tracks side-by-side with the as- sembled ends together.

6.a. Attach mounting angle (without tabs) to the as- sembled end of the ®lter track. See Fig. 23.

b.Attach 6 green clips (provided) to mounting angles. Engagement section of clip faces inside of rack.

c.Attach remaining mounting angle (with tabs) to other end of the ®lter track with no. 10 screws provided. See Fig. 24.

7.a. Place ®lter track assembly in bottom of hood by plac- ing tabbed end into slotted side (with tab on bottom) and attaching opposite end to hood with speed clips and gasketed screws provided. Tabs can be hand bent after inserted into the side.

NOTE: The ®lter track assembly end with screws should face away from the other hood when mounted on the unit.

NOTE: Tabs from both ®lter tracks will be in the same space. After one ®lter track has been inserted into board, bend the tabs so they will not interfere with installation of the second hood.

b.Attach black seal strip to ®lter cover. Seal strip should be applied to ¯ange (covering holes) and center of large ¯ange. See Fig. 25.

8.Slide two 20 x 25-in. ®lters into cross members of hood assembly. Attach ®lter cover over ®lters with screws and speed clips provided.

Minimum Damper Position Setting

Setting of the outdoor air damper position is performed in conjunction with a shortened version of the ®eld run test. This is performed by ®rst opening DIP switch no. 4 then no. 6.

The outdoor-air damper closes. The control allows 90 seconds for the damper to close in case it is in the full open position. Next, the indoor-fan contactor will energize. The outdoor air damper will remain at 0% for 30 seconds. It will then move to the 10% position for another 30 seconds. This will be repeated at every 10% increment for 30 seconds until the damper reaches 100% open. Close DIP switch no. 4 during the 30 seconds immediately after the desired outdoor air mini- mum damper position. The 30-second time period is to allow time where DIP switch no. 4 can be closed. The default value of the minimum outdoor air damper position is 20%. If the desired minimum position is 30%, allow the damper posi- tion to go to 10% for 30 seconds, then 20% for 30 seconds, and when it reaches 30% close DIP switch no. 4 during the 30-second period following the 30% position.

The minimum outdoor air damper position is now set. Close DIP switch no. 6.

B. Economizer Settings

Accessory Enthalpy Control (Fig. 26)

The control (HH57AC077) is mounted in the economizer hood. See Fig. 17. The enthalpy setting adjustment is on the en- thalpy control. For maximum bene®t of outdoor air, set en- thalpy sensor control to A. See Fig. 27 and 28.

Enthalpy Control Installation

The outdoor air enthalpy control is installed on the inside panel of the outdoor air hood. The enthalpy control should be mounted when the outdoor air hoods are assembled. To install the con- trol, perform the following procedure:

1.Turn off all power. Ensure disconnect is locked out.

2.Remove the economizer inlet ®lters from the bottom of the right hand economizer hood. See Fig. 29.

MOUNTING ANGLE (WITHOUT TABS)

FILTER TRACK

ASSEMBLY

Fig. 23 Ð Mounting Angle (Without Tabs)

Attached to Filter Track Assembly

MOUNTING ANGLE (WITH TABS)

Fig. 24 Ð Mounting Angle (With Tabs)

Attached to Filter Track Assembly

BLACK SEAL STRIP (CENTERED)

FILTER COVER

Fig. 25 Ð Attaching Seal Strip to Filter Cover

Ð16Ð

Image 16
Contents Contents Safety ConsiderationsInstallation Provide Unit Support Roof CurbAlternate Unit Support II. RIG and Place UnitBase Unit Dimensions, 580G240-360 Unit Size Operating Corner WeightBase Unit Dimensions, 580H240-360 Must be in Place When Rigging Unit WeightSpecications Unit 580G,HIII. Field Fabricate Ductwork IV. Unit Duct ConnectionsVI. Trap Condensate Drain Flue HoodVII. GAS Piping Power Wiring Field Power SupplyVIII. Electrical Connections Controls OptionsSIO LEDField Control Wiring Electrical Data Ð 580G,H240-360 Ð13Ð IX. OUTDOOR-AIR Inlet Assembly EconomizerAdding Seal Strip to Mounting Flange Hood Sides Economizer Settings Mounting Angle With Tabs Attached to Filter Track AssemblyEnthalpy Control and Sensor Power EXHAUST/BAROMETRIC Relief Damper Hood Economizer DetailsXI. Accessories Motormaster III Control InstallationLow Ambient Kit Sensor Location PRE-START-UPDIP Switch Conguration DIP Switch Factory SettingsSTART-UP Cooling Section START-UP and Adjustments Checking Cooling Control OperationII. Heating Section START-UP and Adjustments Smoke Control Modes Smoke DetectorIndoor Air Quality Control Time Guard CircuitIV. Indoor Airflow and Airflow Adjustments Evaporator Fan Performance AdjustmentHead Pressure Control Motormaster III ControlGAS Valve Adjustment Condenser-Fan AdjustmentNatural Gas Airflow Fan Performance, 580G240-360 Ð Vertical Discharge UnitsAvailable External Static Pressure Airflow Motor Limitations Fan Performance Ð Power ExhaustAir Quantity Limits VII. Power Exhaust Operation Care and MaintenanceVI. Main Burners VIII. Head Pressure ControlCleaning ServiceII. Lubrication Spark Gap Adjustment III. Evaporator FAN Service and Replacement IV. EVAPORATOR-FAN Motor ReplacementPower Failure VI. Refrigerant ChargeXIII. Replacement Parts VII. Filter DrierVIII. Thermostatic Expansion Valve TXV IX. Protective DevicesTroubleshooting Control Board LED Alarms II. Error Code SummaryIGC Board Error Code Summary LED Error Description Troubleshooting Blinks Code CommentsTerminal Assignment I/O Channel Designations Base ModuleSAT IGC Control Heating and Cooling AHA IDMIFC IfcbTable a Table BPower Schematic 580G,H240-360 Ð 24 V Control Schematic 580G,H240-360 Component Arrangement 580G,H240-360 Packaged Service Training START-UP Checklist TemperaturesSTART-UP Electrical PressuresGeneral

580G specifications

The Bryant 580G is a high-efficiency gas furnace designed to deliver optimal heating performance while maximizing energy savings. This model stands out in the Bryant product lineup due to its advanced features and robust technology, making it a popular choice for homeowners seeking reliable comfort in colder climates.

One of the key characteristics of the Bryant 580G is its efficiency rating. With an annual fuel utilization efficiency (AFUE) of up to 92.1%, this furnace ensures that a substantial portion of the fuel consumed is converted into heat, minimizing energy waste and reducing utility bills. This high-efficiency performance is particularly beneficial for those looking to lower their environmental footprint and operate a more sustainable home heating system.

The 580G uses a two-stage heating process, which allows it to operate at two levels of output. During mild weather, the furnace can run on a lower setting, providing gentle warmth while conserving energy. When temperatures drop, the system automatically ramps up to a higher output to maintain comfort. This feature not only enhances energy efficiency but also helps to eliminate temperature fluctuations, ensuring consistent warmth throughout the home.

Noise reduction technology is another remarkable aspect of the Bryant 580G. Equipped with a variable speed blower motor, this furnace operates quietly, providing a more peaceful indoor environment. The motor allows for customizable airflow, which further aids in maintaining an even temperature across different rooms and spaces.

The furnace is built with high-quality materials and features a compact design, making it a suitable option for various installation locations. Additionally, it is compatible with Bryant’s EcoNet Smart Home Management System, which enables homeowners to monitor and control their heating system remotely via a smartphone app. This integration enhances convenience and allows for timely adjustments to heating schedules, promoting energy savings.

Safety is a priority with the 580G. It features an integrated safety switch and a reliable flame sensor to ensure safe operation. With its durable construction and thoughtful engineering, the Bryant 580G is designed to withstand the demands of everyday use while providing peace of mind to homeowners.

In summary, the Bryant 580G gas furnace combines high efficiency, advanced technology, and user-friendly features. Its ability to operate quietly, adapt to temperature changes, and integrate with smart home technology makes it a leading choice for efficient home heating solutions. This furnace not only provides comfort but also offers long-term energy savings, making it a smart investment for any household.