Bryant 580G manual VI. Main Burners, VII. Power Exhaust Operation, VIII. Head Pressure Control

Page 28

VI. MAIN BURNERS

For all applications, main burners are factory set and should require no adjustment.

A.Main Burner Removal (Fig. 38)

1.Shut off (®eld-supplied) manual main gas valve.

2.Shut off power to unit.

3.Remove heating access panel.

4.Disconnect gas piping from gas valve inlet.

5.Remove wires from gas valve.

6.Remove wires from rollout switch.

7.Remove sensor wire and ignitor cable from IGC board.

8.Remove 2 screws securing manifold bracket to basepan.

9.Remove 4 screws that hold the burner support plate ¯ange to the vestibule plate.

10.Lift burner assembly out of unit.

Fig. 38 Ð Main Burner Removal

VII. POWER EXHAUST OPERATION

The power exhaust packages are factory- or ®eld-installed with vertical units and optionally installed in the return air duct- work for horizontal applications. The standard and the modu- lating power exhaust are the two packages offered. The modulating power exhaust package is equipped with a ®eld- adjustable static pressure controller to stage up to 4 power exhausts stages which will maintain a building static pres- sure. The blue sequencer located in the control box below the control board can be adjusted, by removing the covers and adjusting the set point dial to the desired building pressure. The standard power exhaust package controls up to 2 stages of power exhaust to maintain building pressure. These power exhaust stages are staged according to a percentage of the economizer dampers position.

VIII. HEAD PRESSURE CONTROL

Each unit has a fan cycling, outdoor thermostat to shut off the outdoor-fan motor at 55 F. The head pressure control per- mits unit to operate with correct condensing temperatures down to 35 F outdoor-air temperature.

IX. LOW AMBIENT KIT

Low Ambient Kit is a fan speed control device actuated by a temperature sensor. The ®eld-installed accessory is speci®- cally designed for use on this equipment and controls the condenser-fan motor speed in response to the saturated condensing temperature. For outdoor temperatures down to −20 F, it maintains condensing temperature at 100 F.

CARE AND MAINTENANCE

To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic mainte- nance must be performed on this equipment. This combina- tion heating/cooling unit should be inspected at least once each year by a quali®ed service person.

NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.

WARNING: The ability to properly perform mainte- nance on this equipment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any mainte- nance on this equipment other than those procedures recommended in the User's Manual. FAILURE TO HEED THIS WARNING COULD RESULT IN SERIOUS PER- SONAL INJURY AND POSSIBLE DAMAGE TO THIS EQUIPMENT.

The minimum maintenance requirements for this equipment are as follows:

1.Inspect air ®lters each month. Clean or replace when necessary.

2.Inspect cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.

3.Inspect blower motor and wheel each heating and cooling season. Clean and lubricate (if required) when necessary.

4.Lubricate bearings every 6 months if fan runs continu- ously or annually if fan runs intermittently.

5.Check electrical connections for tightness and controls for proper operation each heating and cooling season. Service when necessary.

6.Check and inspect heating section before each heating season.

7.Check and clean vent screen if needed.

WARNING: Failure to follow these warnings could re- sult in serious personal injury:

1.Turn off electrical power to the unit before perform- ing any maintenance or service on the unit.

2.Use extreme caution when removing panels and parts. As with any mechanical equipment, personal injury can result from sharp edges, etc.

3.Never place anything combustible either on, or in con- tact with, the unit.

4.Should overheating occur, shut off the electrical supply.

Ð28Ð

Image 28
Contents Contents Safety ConsiderationsInstallation Provide Unit Support Roof CurbAlternate Unit Support II. RIG and Place UnitBase Unit Dimensions, 580G240-360 Unit Size Operating Corner WeightBase Unit Dimensions, 580H240-360 Must be in Place When Rigging Unit WeightSpecications Unit 580G,HIII. Field Fabricate Ductwork IV. Unit Duct ConnectionsVI. Trap Condensate Drain Flue HoodVII. GAS Piping Power Wiring Field Power SupplyVIII. Electrical Connections Controls OptionsSIO LEDField Control Wiring Electrical Data Ð 580G,H240-360 Ð13Ð IX. OUTDOOR-AIR Inlet Assembly EconomizerAdding Seal Strip to Mounting Flange Hood Sides Economizer Settings Mounting Angle With Tabs Attached to Filter Track AssemblyEnthalpy Control and Sensor Power EXHAUST/BAROMETRIC Relief Damper Hood Economizer DetailsXI. Accessories Motormaster III Control InstallationLow Ambient Kit Sensor Location PRE-START-UPDIP Switch Conguration DIP Switch Factory SettingsSTART-UP Cooling Section START-UP and Adjustments Checking Cooling Control OperationII. Heating Section START-UP and Adjustments Smoke Control Modes Smoke DetectorIndoor Air Quality Control Time Guard CircuitIV. Indoor Airflow and Airflow Adjustments Evaporator Fan Performance AdjustmentHead Pressure Control Motormaster III ControlGAS Valve Adjustment Condenser-Fan AdjustmentNatural Gas Airflow Fan Performance, 580G240-360 Ð Vertical Discharge UnitsAvailable External Static Pressure Airflow Motor Limitations Fan Performance Ð Power ExhaustAir Quantity Limits VII. Power Exhaust Operation Care and MaintenanceVI. Main Burners VIII. Head Pressure ControlCleaning ServiceII. Lubrication Spark Gap Adjustment III. Evaporator FAN Service and Replacement IV. EVAPORATOR-FAN Motor ReplacementPower Failure VI. Refrigerant ChargeXIII. Replacement Parts VII. Filter DrierVIII. Thermostatic Expansion Valve TXV IX. Protective DevicesTroubleshooting Control Board LED Alarms II. Error Code SummaryIGC Board Error Code Summary LED Error Description Troubleshooting Blinks Code CommentsTerminal Assignment I/O Channel Designations Base ModuleSAT IGC Control Heating and Cooling AHA IDMIFC IfcbTable a Table BPower Schematic 580G,H240-360 Ð 24 V Control Schematic 580G,H240-360 Component Arrangement 580G,H240-360 Packaged Service Training START-UP Checklist TemperaturesSTART-UP Electrical PressuresGeneral

580G specifications

The Bryant 580G is a high-efficiency gas furnace designed to deliver optimal heating performance while maximizing energy savings. This model stands out in the Bryant product lineup due to its advanced features and robust technology, making it a popular choice for homeowners seeking reliable comfort in colder climates.

One of the key characteristics of the Bryant 580G is its efficiency rating. With an annual fuel utilization efficiency (AFUE) of up to 92.1%, this furnace ensures that a substantial portion of the fuel consumed is converted into heat, minimizing energy waste and reducing utility bills. This high-efficiency performance is particularly beneficial for those looking to lower their environmental footprint and operate a more sustainable home heating system.

The 580G uses a two-stage heating process, which allows it to operate at two levels of output. During mild weather, the furnace can run on a lower setting, providing gentle warmth while conserving energy. When temperatures drop, the system automatically ramps up to a higher output to maintain comfort. This feature not only enhances energy efficiency but also helps to eliminate temperature fluctuations, ensuring consistent warmth throughout the home.

Noise reduction technology is another remarkable aspect of the Bryant 580G. Equipped with a variable speed blower motor, this furnace operates quietly, providing a more peaceful indoor environment. The motor allows for customizable airflow, which further aids in maintaining an even temperature across different rooms and spaces.

The furnace is built with high-quality materials and features a compact design, making it a suitable option for various installation locations. Additionally, it is compatible with Bryant’s EcoNet Smart Home Management System, which enables homeowners to monitor and control their heating system remotely via a smartphone app. This integration enhances convenience and allows for timely adjustments to heating schedules, promoting energy savings.

Safety is a priority with the 580G. It features an integrated safety switch and a reliable flame sensor to ensure safe operation. With its durable construction and thoughtful engineering, the Bryant 580G is designed to withstand the demands of everyday use while providing peace of mind to homeowners.

In summary, the Bryant 580G gas furnace combines high efficiency, advanced technology, and user-friendly features. Its ability to operate quietly, adapt to temperature changes, and integrate with smart home technology makes it a leading choice for efficient home heating solutions. This furnace not only provides comfort but also offers long-term energy savings, making it a smart investment for any household.