Table 12 Ð Control Board LED Alarms

LED

 

ERROR

DESCRIPTION

TROUBLESHOOTING

BLINKS

 

CODE

COMMENTS

 

 

1

 

 

Normal Operation

The control board ¯ashes the red LED in one-second intervals

 

 

 

 

when the board is operating properly. Make sure DIP switch 3 is

 

 

 

 

closed.

2

 

HF-13

Compressor 1 Safety

The high or low pressure safety switch for compressor no. 1 has

 

 

 

 

opened for 3 seconds. The error will be cleared and compressor

 

 

 

 

no. 1 will be allowed to turn on in 15 minutes. If the safeties have

 

 

 

 

been tripped 3 times in 90 minutes, compressor no. 1 will be

 

 

 

 

locked out until the control board has been manually reset.

3

 

HF-14

Compressor 2 Safety

The high or low pressure safety switch for compressor no. 2 has

 

 

 

 

opened for 3 seconds. The error will be cleared and compressor

 

 

 

 

no. 2 will be allowed to turn on in 15 minutes. If the safeties have

 

 

 

 

been tripped 3 times in 90 minutes, compressor no. 2 will be

 

 

 

 

locked out until the control board has been manually reset.

4

 

HF-15

Thermostat Failure

The thermostat is calling for both heating and cooling at the same

 

 

 

 

time. The unit will operate on a ®rst call basis and will automati-

 

 

 

 

cally reset.

5

 

HF-05

SAT Thermistor Failure

The supply-air temperature (SAT) sensor has failed. First check for

 

 

 

 

wiring errors, then replace sensor.

6

 

HF-06

OAT Thermistor Failure

The outside-air temperature (OAT) sensor has failed. First check

 

 

 

 

for wiring errors, then replace sensor.

7

 

HF-03

DIP Switch 2 is Open

Close DIP switch 2.

8

 

HF-12

DIP Switch 1 is Open

Close DIP switch 1.

9

 

SE-05

Loss of Communications

Communications between the expansion board and the control

 

 

 

with Expansion Board

board have been interrupted. Ensure that an expansion board

 

 

 

 

is installed and wired using the wire harness supplied with the

 

 

 

 

expansion module. If an expansion board is not used, ensure that

 

 

 

 

DIP switch position 3 is in the closed position and reset power.

10

 

HF-16

Control Board Failure

Generated when hardware has failed on control board. Replace

 

 

 

 

the control board.

11

 

HF-17

Expansion Board Failure

Generated when hardware has failed on the expansion board.

 

 

 

 

Replace the expansion board.

LEGEND

 

 

 

DIP Ð Dual In-Line Package

 

 

LED Ð Light-Emitting Diode

 

 

II. ERROR CODE SUMMARY

A summary of the error codes is listed in Table 13. If more than one error code exists, they will be displayed on the LED of the IGC board in sequence. Fault history is deleted when power is turned off.

Table 13 Ð IGC Board Error Code Summary

INDICATION

ERROR MODE

ON

NORMAL OPERATION

OFF

HARDWARE FAILURE

1

FLASH

FAN ON/OFF DELAY MODIFIED

2

FLASHES

LIMIT SWITCH FAULT

3

FLASHES

FLAME SENSE FAULT

4

FLASHES

4 CONSECUTIVE LIMIT SWITCH FAULTS

5

FLASHES

IGNITION LOCKOUT FAULT

6

FLASHES

INDUCED DRAFT MOTOR FAULT

7

FLASHES

ROLLOUT SWITCH FAULT

8

FLASHES

INTERNAL CONTROL FAULT

 

 

 

III. INPUT AND OUTPUT CHANNEL DESIGNATIONS

Table 14 shows the input and output channel designations.

The Integrated Gas Controls for heating and cooling are shown in Fig. 45.

Ð34Ð

Image 34
Contents Contents Safety ConsiderationsAlternate Unit Support Installation Provide Unit SupportRoof Curb II. RIG and Place UnitBase Unit Dimensions, 580G240-360 Unit Size Operating Corner WeightBase Unit Dimensions, 580H240-360 Must be in Place When Rigging Unit WeightSpecications Unit 580G,HIII. Field Fabricate Ductwork IV. Unit Duct ConnectionsVI. Trap Condensate Drain Flue HoodVII. GAS Piping VIII. Electrical Connections Power WiringField Power Supply Controls OptionsSIO LEDField Control Wiring Electrical Data Ð 580G,H240-360 Ð13Ð IX. OUTDOOR-AIR Inlet Assembly EconomizerAdding Seal Strip to Mounting Flange Hood Sides Economizer Settings Mounting Angle With Tabs Attached to Filter Track AssemblyEnthalpy Control and Sensor Power EXHAUST/BAROMETRIC Relief Damper Hood Economizer DetailsXI. Accessories Motormaster III Control InstallationLow Ambient Kit Sensor Location PRE-START-UPSTART-UP Cooling Section START-UP and Adjustments DIP Switch CongurationDIP Switch Factory Settings Checking Cooling Control OperationII. Heating Section START-UP and Adjustments Indoor Air Quality Control Smoke Control ModesSmoke Detector Time Guard CircuitHead Pressure Control IV. Indoor Airflow and Airflow AdjustmentsEvaporator Fan Performance Adjustment Motormaster III ControlGAS Valve Adjustment Condenser-Fan AdjustmentNatural Gas Airflow Fan Performance, 580G240-360 Ð Vertical Discharge UnitsAvailable External Static Pressure Airflow Motor Limitations Fan Performance Ð Power ExhaustAir Quantity Limits VI. Main Burners VII. Power Exhaust OperationCare and Maintenance VIII. Head Pressure ControlCleaning ServiceII. Lubrication Spark Gap Adjustment Power Failure III. Evaporator FAN Service and ReplacementIV. EVAPORATOR-FAN Motor Replacement VI. Refrigerant ChargeVIII. Thermostatic Expansion Valve TXV XIII. Replacement PartsVII. Filter Drier IX. Protective DevicesTroubleshooting IGC Board Error Code Summary Control Board LED AlarmsII. Error Code Summary LED Error Description Troubleshooting Blinks Code CommentsTerminal Assignment I/O Channel Designations Base ModuleSAT IGC Control Heating and Cooling IFC AHAIDM IfcbTable a Table BPower Schematic 580G,H240-360 Ð 24 V Control Schematic 580G,H240-360 Component Arrangement 580G,H240-360 Packaged Service Training START-UP Electrical START-UP ChecklistTemperatures PressuresGeneral

580G specifications

The Bryant 580G is a high-efficiency gas furnace designed to deliver optimal heating performance while maximizing energy savings. This model stands out in the Bryant product lineup due to its advanced features and robust technology, making it a popular choice for homeowners seeking reliable comfort in colder climates.

One of the key characteristics of the Bryant 580G is its efficiency rating. With an annual fuel utilization efficiency (AFUE) of up to 92.1%, this furnace ensures that a substantial portion of the fuel consumed is converted into heat, minimizing energy waste and reducing utility bills. This high-efficiency performance is particularly beneficial for those looking to lower their environmental footprint and operate a more sustainable home heating system.

The 580G uses a two-stage heating process, which allows it to operate at two levels of output. During mild weather, the furnace can run on a lower setting, providing gentle warmth while conserving energy. When temperatures drop, the system automatically ramps up to a higher output to maintain comfort. This feature not only enhances energy efficiency but also helps to eliminate temperature fluctuations, ensuring consistent warmth throughout the home.

Noise reduction technology is another remarkable aspect of the Bryant 580G. Equipped with a variable speed blower motor, this furnace operates quietly, providing a more peaceful indoor environment. The motor allows for customizable airflow, which further aids in maintaining an even temperature across different rooms and spaces.

The furnace is built with high-quality materials and features a compact design, making it a suitable option for various installation locations. Additionally, it is compatible with Bryant’s EcoNet Smart Home Management System, which enables homeowners to monitor and control their heating system remotely via a smartphone app. This integration enhances convenience and allows for timely adjustments to heating schedules, promoting energy savings.

Safety is a priority with the 580G. It features an integrated safety switch and a reliable flame sensor to ensure safe operation. With its durable construction and thoughtful engineering, the Bryant 580G is designed to withstand the demands of everyday use while providing peace of mind to homeowners.

In summary, the Bryant 580G gas furnace combines high efficiency, advanced technology, and user-friendly features. Its ability to operate quietly, adapt to temperature changes, and integrate with smart home technology makes it a leading choice for efficient home heating solutions. This furnace not only provides comfort but also offers long-term energy savings, making it a smart investment for any household.