Bryant 580G Smoke Control Modes, Smoke Detector, Indoor Air Quality Control, Time Guard Circuit

Page 23

controls up to 2 stages of power exhaust to maintain building pressure. The power exhaust package can be con®gured to deliver positive or negative building pressure. These power exhaust stages are staged according to a percentage of the economizer dampers position. Default values are 25% for Stage 1 and 75% for Stage 2.

D. Smoke Control Modes

The 580G,H units with an optional expansion board perform ®re and smoke control modes. The expansion board provides 4 modes which can be used to control smoke within the con- ditioned area. The modes of operation are ®re shutdown, pres- surization, evacuation, and smoke purge. See Table 7.

E. Smoke Detector

A smoke detector can be used to initiate ®re shutdown. This can be accomplished by a set of normally closed pilot relay contacts which will interrupt power from the 24-v trans- former, secondary ``B'' terminal to the control circuit breaker (CB4). See Fig. 33. The wire that connects these two points is white and labeled ``W78.''

NOTE: On standard gas models, the indoor fan will continue to run 45 seconds after the call for heat has been terminated. If ®re shutdown is initiated the fan will stop immediately. No 45-second delay will occur.

The smoke detector may be mounted in the return air duct or the supply duct.

F. Indoor Air Quality Control

The accessory expansion board and accessory IAQ sensor are required for IAQ control. The IAQ sensors operate with a 4 to 20 mA signal. The 4 to 20 mA signal is connected to T11 (+) and T12 (−) on the expansion board for the IAQ sen- sor, and T13 (+) and T14 (−) on the expansion board for the OAQ (Outdoor Air Quality) sensor. The sensor is ®eld- mounted and wired to the expansion board installed in the unit main control box. The IAQ sensor must be powered by a ®eld-supplied 24-v power supply (ungrounded). Do not use the unit 24-v power supply to power the sensor.

Once installed, the sensor must be enabled. The sensor is con- ®gured with default values which may be changed through network access software. To work properly, the IAQ sensor high and low reference points for the sensor that is used must match the con®gured values. The expansion board reacts to a 4 to 20 mA signal from the IAQ sensor. The low reference (4 mA output) must be con®gured to the minimum IAQ sensor reading. The high reference (20 mA output) must be con®gured to the maximum IAQ sensor reading.

The IAQ sensor can be con®gured to either low or high pri- ority. The priority value can be changed by the user. The default is low.

Low Priority

When the priority is set to low, the initial control is to the IAQ set point, but the outside air damper position will change to its minimum position when the space temperature is greater than the occupied cooling set point plus 2° F or when the space temperature is less than the occupied heating set point minus 2° F. The damper will also change to minimum posi- tion when the outdoor air quality is greater than the outdoor air quality set point (ppm).

High Priority

When the priority is set to high, the IAQ set point controls the outside air damper exclusively, with no regard to comfort conditioning.

G. Time Guard Circuit

The Time Guard function (built into the rooftop control board) maintains a minimum off time of 5 minutes, a minimum on time of 10 seconds, and a 10-second delay between compres- sor starts.

H. Crankcase Heater

Unit main power supply must remain on to provide crank- case heater operation. The crankcase heater in each compres- sor keeps oil free of refrigerant while compressor is off.

Table 7 Ð Smoke Control Modes

DEVICE

PRESSURIZATION

SMOKE PURGE

EVACUATION

FIRE SHUTDOWN

Economizer

100%

100%

100%

0%

Indoor Fan

ON

ON

OFF

OFF

Power Exhaust (all outputs)

OFF

ON

ON

OFF

Heat Stages

OFF

OFF

OFF

OFF

Fig. 33 Ð Field-Supplied Smoke Detector Wiring

Ð23Ð

Image 23
Contents Safety Considerations ContentsII. RIG and Place Unit Installation Provide Unit SupportRoof Curb Alternate Unit SupportUnit Size Operating Corner Weight Base Unit Dimensions, 580G240-360Base Unit Dimensions, 580H240-360 Unit Weight Must be in Place When RiggingUnit 580G,H SpecicationsIV. Unit Duct Connections III. Field Fabricate DuctworkVII. GAS Piping Flue HoodVI. Trap Condensate Drain Controls Options Power WiringField Power Supply VIII. Electrical ConnectionsLED SIOField Control Wiring Electrical Data Ð 580G,H240-360 Ð13Ð Economizer IX. OUTDOOR-AIR Inlet AssemblyAdding Seal Strip to Mounting Flange Hood Sides Mounting Angle With Tabs Attached to Filter Track Assembly Economizer SettingsEnthalpy Control and Sensor Economizer Details Power EXHAUST/BAROMETRIC Relief Damper HoodMotormaster III Control Installation XI. AccessoriesPRE-START-UP Low Ambient Kit Sensor LocationChecking Cooling Control Operation DIP Switch CongurationDIP Switch Factory Settings START-UP Cooling Section START-UP and AdjustmentsII. Heating Section START-UP and Adjustments Time Guard Circuit Smoke Control ModesSmoke Detector Indoor Air Quality ControlMotormaster III Control IV. Indoor Airflow and Airflow AdjustmentsEvaporator Fan Performance Adjustment Head Pressure ControlNatural Gas Condenser-Fan AdjustmentGAS Valve Adjustment Available External Static Pressure Airflow Fan Performance, 580G240-360 Ð Vertical Discharge UnitsAirflow Air Quantity Limits Fan Performance Ð Power ExhaustMotor Limitations VIII. Head Pressure Control VII. Power Exhaust OperationCare and Maintenance VI. Main BurnersII. Lubrication ServiceCleaning Spark Gap Adjustment VI. Refrigerant Charge III. Evaporator FAN Service and ReplacementIV. EVAPORATOR-FAN Motor Replacement Power FailureIX. Protective Devices XIII. Replacement PartsVII. Filter Drier VIII. Thermostatic Expansion Valve TXVTroubleshooting LED Error Description Troubleshooting Blinks Code Comments Control Board LED AlarmsII. Error Code Summary IGC Board Error Code SummarySAT I/O Channel Designations Base ModuleTerminal Assignment IGC Control Heating and Cooling Ifcb AHAIDM IFCTable B Table aPower Schematic 580G,H240-360 Ð 24 V Control Schematic 580G,H240-360 Component Arrangement 580G,H240-360 Packaged Service Training Pressures START-UP ChecklistTemperatures START-UP ElectricalGeneral

580G specifications

The Bryant 580G is a high-efficiency gas furnace designed to deliver optimal heating performance while maximizing energy savings. This model stands out in the Bryant product lineup due to its advanced features and robust technology, making it a popular choice for homeowners seeking reliable comfort in colder climates.

One of the key characteristics of the Bryant 580G is its efficiency rating. With an annual fuel utilization efficiency (AFUE) of up to 92.1%, this furnace ensures that a substantial portion of the fuel consumed is converted into heat, minimizing energy waste and reducing utility bills. This high-efficiency performance is particularly beneficial for those looking to lower their environmental footprint and operate a more sustainable home heating system.

The 580G uses a two-stage heating process, which allows it to operate at two levels of output. During mild weather, the furnace can run on a lower setting, providing gentle warmth while conserving energy. When temperatures drop, the system automatically ramps up to a higher output to maintain comfort. This feature not only enhances energy efficiency but also helps to eliminate temperature fluctuations, ensuring consistent warmth throughout the home.

Noise reduction technology is another remarkable aspect of the Bryant 580G. Equipped with a variable speed blower motor, this furnace operates quietly, providing a more peaceful indoor environment. The motor allows for customizable airflow, which further aids in maintaining an even temperature across different rooms and spaces.

The furnace is built with high-quality materials and features a compact design, making it a suitable option for various installation locations. Additionally, it is compatible with Bryant’s EcoNet Smart Home Management System, which enables homeowners to monitor and control their heating system remotely via a smartphone app. This integration enhances convenience and allows for timely adjustments to heating schedules, promoting energy savings.

Safety is a priority with the 580G. It features an integrated safety switch and a reliable flame sensor to ensure safe operation. With its durable construction and thoughtful engineering, the Bryant 580G is designed to withstand the demands of everyday use while providing peace of mind to homeowners.

In summary, the Bryant 580G gas furnace combines high efficiency, advanced technology, and user-friendly features. Its ability to operate quietly, adapt to temperature changes, and integrate with smart home technology makes it a leading choice for efficient home heating solutions. This furnace not only provides comfort but also offers long-term energy savings, making it a smart investment for any household.