Bryant 677C--A installation instructions Gas Heating Fan Speed Set-up, Continuous Fan Operation

Page 17

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before making any indoor wiring adjustments, shut off gas supply. Then disconnect electrical power to the unit and install lockout tag before changing blower speed.

This unit has independent fan speeds for gas heating and cooling. In addition, this unit has the field-selectable capability to run two different cooling fan speeds: A normal cooling fan speed (350~400 CFM/Ton) and an enhanced dehumidification fan speed (As low as 320 CFM/Ton) for use with either a dehumidistat or a thermostat that supports dehumidification.

This unit is factory-set up for use with a single cooling fan speed. The cooling speed is marked “LOW” on the interface fan board (IFB) (Fig. 14) . The factory-shipped settings are noted in Table

10.There are 3 additional speed tap wires available for use in either gas heating or cooling (For color coding on the indoor fan motor leads, see Table 6). The additional 3 speed tap wires are shipped loose with vinyl caps and are located in the control box, near the interface fan board (IFB) (Fig. 14).

Gas Heating Fan Speed Set-up

To change the gas heating speed:

1.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding). Table 10 shows the temperature rise associated with each fan speed for a given static pressure. Make sure that the speed chosen delivers a temperature rise within the rise range listed on the unit rating plate.

2.Remove the current speed tap wire from the “GAS HEAT” terminal on the interface fan board (IFB) (Fig.14) and place vinyl cap over the connector on the wire.

3.Connect the desired speed tap wire to the “GAS HEAT” terminal on the interface fan board (IFB).

Single Cooling Fan Speed Set-up (Dehumidification feature not used)

To change cooling speed:

1.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding). Add the wet coil pressure drop in Table 8 to the system static to determine the correct cooling airflow speed in Table 10 that will deliver the nominal cooling airflow as listed in Table 1 for each size.

2.Remove the current speed tap wire from the “LOW” terminal on the interface fan board (IFB) (Fig. 14) and place vinyl cap over the connector on the wire.

3.Connect the desired speed tap wire to the “LOW” terminal on the interface fan board (IFB).

Two Cooling Fan Speeds Set-up (Dehumidification feature used)

IMPORTANT: Dehumidification control must open control circuit on humidity rise above set point.

Use of the dehumidification cooling fan speed requires use of either a 24 VAC dehumidistat or a thermostat which includes control of a 24 VAC dehumidistat connection. In either case, the dehumidification control must open the control circuit on humidity rise above the dehumidification set point. Dehumidification controls are available with the reverse logic; these must not be used.

1.Remove fan speed tap wire from the “LOW” terminal on the interface fan board (IFB) (Fig. 14).

2.Determine correct normal cooling fan speed for unit and application. Add the wet coil pressure drop in Table 8 to the system static to determine the correct cooling airflow speed in Table 10 that will deliver the nominal cooling airflow as listed in Table 1 for each size.

3.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding) for the normal cooling fan speed and place desired speed tap wire on “HIGH” on the interface board.

4.Refer to airflow tables (Table 10) to determine allowable speeds for the dehumidification cooling fan speed. In Table 10, speeds that are not allowed for dehumidification cooling are shaded.

5.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding) for the dehumidification cooling fan speed and place desired speed tap wire on the “LOW” connection on the interface board (IFB). Verify that static pressure is in the acceptable range for the speed tap to be used for dehumidification cooling.

6.Use any spare vinyl plugs to cap any unused speed tap wires.

NOTE: For heat pump operation, the recommended airflow is 350 to 450 CFM for each 12,000 Btuh of rated cooling capacity.

Continuous Fan Operation

When the DEHUM feature is not used, the continuous fan speed will be the same as cooling fan speed. When the DEHUM feature is used, the continuous fan will operate on IFB “LOW” speed when the DH control lead is not energized, or IFB “HIGH” speed when the DH lead is energized (see Fig. 14).

Table 6 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med---High Speed

Red = Med Speed

Pink = Med---Low Speed

Blue = Low Speed

677C-- -- A

17

Image 17
Contents Safety Considerations Table of ContentsIntroduction Receiving and Installation677C--A24-30 Unit Dimensions 677C--A36-60 Unit Dimensions CPRFCURB010A00 Unit SizeCPRFCURB011A00 CPRFCURB012A00Rigging/Lifting of Unit See Fig Rig and Place UnitInspection Install Gas Piping Install Flue HoodConnect Condensate Drain Carbon Monoxide Poisoning HazardFire or Explosion Hazard Install Duct ConnectionsConfiguring Units for Downflow Vertical Discharge Refrigerant Metering CompressorsCFM Furnace SectionHeating Inputs Physical Data Unit 677C--A Cont’dMaximum Gas Flow Capacity Special Procedures for 208-V Operation Install Electrical ConnectionsHigh-Voltage Connections Control Voltage ConnectionsPRE-START-UP Balance Point Setting-Thermidistat or Hybrid ThermostatTransformer Protection FIRE, EXPLOSION, Electrical Shock HazardSTART-UP Start-up Heating and Make Adjust- mentsCheck for Refrigerant Leaks Unit Sequence of OperationCheck Heating Control Adjust Gas InputCheck Gas Input Unit Damage HazardLimit Switches Airflow and Temperature RiseCheck Burner Flame Normal OperationRollout Switch Start-up Cooling and Make Adjust- mentsChecking and Adjusting Refrigerant Charge Indoor Airflow and Airflow AdjustmentsGas Heating Fan Speed Set-up Two Cooling Fan Speeds Set-up Dehumidification feature usedContinuous Fan Operation Color Coding for Indoor Fan Motor LeadsFilter Size CFM 677C--A Wet Coil Pressure DropRise Speed Color Range Unit Heating Motor Wire1505 1452 1413 1358 1323 1282 1234 1169 1130 25 55oF Heating 1962 1915 1880 1843 1794 1753 1711 1675 1628 35 65oF Heating 1962 1915 1880 1843 1794 1753 1711 1675 1628 30 60oF Heating 1887 1847 1783 1726 1677 1625 1578 1527 1432 30 60oF Heating 677C a 208/230-3-60 Wiring Diagram, Unit 677C--A Cooling Charging Table-Subcooling Cleaning the Blower Motor and Wheel MaintenanceAir Filter Indoor Blower and MotorInduced Draft combustion air Blower Assembly Limit SwitchBurner Ignition Flue Gas PassagewaysOutdoor Fan Electrical Controls and WiringRefrigerant Circuit EXPLOSION, Personal Injury and Environmental HazardLoss of Charge Switch Pressure SwitchesGas Input Indoor AirflowExplosion Hazard High-Pressure SwitchCopeland Scroll Compressor Puron Refrigerant Refrigerant System Unit Operation and Safety HazardCompressor Oil Servicing Systems on Roofs and with Synthetic materialsPuronr R-410A Quick Reference Guide TroubleshootingSTART-UP Checklist Symptom Cause Remedy Troubleshooting Guide Cooling or Heat Pump Heating ModeLED OFF Troubleshooting Guide-HeatingTroubleshooting Guide-LED Status Codes Remove and Store in Job Files TemperaturesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor Amps