Table 12 – Troubleshooting Guide–Heating

SYMPTOM

CAUSE

 

REMEDY

 

 

 

 

Water in gas line

Drain. Install drip leg.

 

No power to furnace

Check power supply fuses, wiring or circuit breaker.

 

 

Check transformer.

 

No 24--v power supply to control circuit

NOTE: Some transformers have internal over--current protection

 

 

that requires a cool--down period to reset.

Burners will not ignite

 

 

Mis--wired or loose connections

Check all wiring and wire nut connections

 

Misaligned spark electrodes

Check flame ignition and sense electrode positioning.

 

Adjust as necessary.

 

 

 

 

 

 

 

 

1.

Check gas line for air. Purge as necessary. NOTE: After purging

 

No gas at main burners

gas line of air, wait at least 5 minutes for any gas to dissipate be-

 

fore attempting to light unit.

 

 

 

 

2.

Check gas valve.

 

 

 

 

Dirty air filter

Clean or replace filter as necessary

 

Gas input to furnace too low

Check gas pressure at manifold match with that on unit nameplate

Inadequate heating

Unit undersized for application

Replace with proper unit or add additional unit

Restricted airflow

Clean or replace filter. Remove any restriction.

 

 

Limit switch cycles main burners

Check rotation of blower, temperature rise of unit. Adjust as neces-

 

sary.

 

 

 

 

 

 

 

 

1.

Tighten all screws around burner compartment

 

 

2.

Cracked heat exchanger. Replace.

 

Incomplete combustion results in: Aldehyde odors,

3.

Unit over--fired. Reduce input (change orifices or adjust gas line

Poor flame characteristics

or manifold pressure).

carbon monoxide, sooting flame, floating flame

 

4.

Check burner alignment.

 

 

 

 

5.

Inspect heat exchanger for blockage. Clean as necessary.

 

 

 

 

Table 13 – Troubleshooting Guide–LED Status Codes

SYMPTOM

CAUSE

REMEDY

 

 

 

 

 

 

 

Check 5--amp fuse son IGC*, power to unit, 24--v circuit breaker,

No Power Hardware failure

Loss of power to control module (IGC)*.

and transformer. Units without a 24--v circuit breaker have an

(LED OFF)

 

internal overload in the 24--v transformer. If the overload trips,

 

 

 

 

 

allow 10 minutes for automatic reset.

 

 

 

 

Limit switch faults

 

Check the operation of the indoor (evaporator) fan motor. Ensure

High temperature limit switch is open.

that the supply--air temperature rise is in accordance with the

(LED 2 flashes)

 

range on the unit nameplate. Clean or replace filters.

 

 

 

 

 

 

Flame sense fault

The IGC* sensed flame that should not be present.

Reset unit. If problem persists, replace control board.

(LED 3 flashes)

 

 

 

 

 

4 consecutive limit switch

 

Check the operation of the indoor (evaporator) fan motor and that

faults

 

Inadequate airflow to unit.

supply--air temperature rise agrees with range on unit nameplate

(LED 4 flashes)

 

information.

 

 

 

 

Ignition lockout

 

Check ignitor and flame sensor electrode spacing, gaps, etc.

Unit unsuccessfully attempted ignition for 15 minutes.

Ensure that fame sense and ignition wires are properly terminated.

(LED 5 flashes)

 

Verify that unit is obtaining proper amount of gas.

 

 

 

 

 

 

 

 

 

 

Verify wiring connections to pressure switch and inducer motor.

Pressure Switch motor fault

 

Verify pressure switch hose is tightly connected to both inducer

Open pressure switch.

housing and pressure switch. Verify inducer wheel is properly

(LED 6 flashes)

 

attached to inducer motor shaft. Verify inducer motor shaft is turn-

 

 

 

 

 

 

ing.

 

 

 

 

 

 

 

Rollout switch will automatically reset, but IGC* will continue to

Rollout switch fault

Rollout switch has opened.

lockout unit. Check gas valve operation. Ensure that induced--draft

(LED 7 flashes)

blower wheel is properly secured to motor shaft. Inspect heat

 

 

 

 

exchanger. Reset unit at unit disconnect.

 

 

 

Internal control fault

Microprocessor has sensed an error in the software

If error code is not cleared by resetting unit power, replace the

(LED 8 flashes)

or hardware.

IGC*.

Temporary 1 hr auto reset

Electrical interference impeding IGC software

Reset 24--v. to control board or turn thermostat off, then on again.

(LED 9 flashes)

Fault will automatically reset itself in one (1) hour.

 

*WARNING

: If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that my be present before handling new control

board. The IGC is sensitive to static electricity and my be damaged if the necessary precautions are not taken. IMPORTANT: Refer to Table 12---Troubleshooting Guide---Heating for additional troubleshooting analysis.

LEGEND

IGC—Integrated Gas Unit Controller

LED—Light---Emitting Diode

677C-- -- A

35

Image 35
Contents Safety Considerations Table of ContentsIntroduction Receiving and Installation677C--A24-30 Unit Dimensions 677C--A36-60 Unit Dimensions CPRFCURB012A00 Unit SizeCPRFCURB010A00 CPRFCURB011A00Rigging/Lifting of Unit See Fig Rig and Place UnitInspection Carbon Monoxide Poisoning Hazard Install Flue HoodInstall Gas Piping Connect Condensate DrainFire or Explosion Hazard Install Duct ConnectionsConfiguring Units for Downflow Vertical Discharge Furnace Section CompressorsRefrigerant Metering CFMHeating Inputs Physical Data Unit 677C--A Cont’dMaximum Gas Flow Capacity Control Voltage Connections Install Electrical ConnectionsSpecial Procedures for 208-V Operation High-Voltage ConnectionsFIRE, EXPLOSION, Electrical Shock Hazard Balance Point Setting-Thermidistat or Hybrid ThermostatPRE-START-UP Transformer ProtectionUnit Sequence of Operation Start-up Heating and Make Adjust- mentsSTART-UP Check for Refrigerant LeaksUnit Damage Hazard Adjust Gas InputCheck Heating Control Check Gas InputNormal Operation Airflow and Temperature RiseLimit Switches Check Burner FlameIndoor Airflow and Airflow Adjustments Start-up Cooling and Make Adjust- mentsRollout Switch Checking and Adjusting Refrigerant ChargeColor Coding for Indoor Fan Motor Leads Two Cooling Fan Speeds Set-up Dehumidification feature usedGas Heating Fan Speed Set-up Continuous Fan OperationFilter Size CFM 677C--A Wet Coil Pressure DropRise Speed Color Range Unit Heating Motor Wire1505 1452 1413 1358 1323 1282 1234 1169 1130 25 55oF Heating 1962 1915 1880 1843 1794 1753 1711 1675 1628 35 65oF Heating 1962 1915 1880 1843 1794 1753 1711 1675 1628 30 60oF Heating 1887 1847 1783 1726 1677 1625 1578 1527 1432 30 60oF Heating 677C a 208/230-3-60 Wiring Diagram, Unit 677C--A Cooling Charging Table-Subcooling Indoor Blower and Motor MaintenanceCleaning the Blower Motor and Wheel Air FilterFlue Gas Passageways Limit SwitchInduced Draft combustion air Blower Assembly Burner IgnitionEXPLOSION, Personal Injury and Environmental Hazard Electrical Controls and WiringOutdoor Fan Refrigerant CircuitIndoor Airflow Pressure SwitchesLoss of Charge Switch Gas InputExplosion Hazard High-Pressure SwitchCopeland Scroll Compressor Puron Refrigerant Servicing Systems on Roofs and with Synthetic materials Unit Operation and Safety HazardRefrigerant System Compressor OilPuronr R-410A Quick Reference Guide TroubleshootingSTART-UP Checklist Symptom Cause Remedy Troubleshooting Guide Cooling or Heat Pump Heating ModeLED OFF Troubleshooting Guide-HeatingTroubleshooting Guide-LED Status Codes III. START-UP Electrical Supply Voltage Compressor Amps TemperaturesRemove and Store in Job Files Preliminary Information Model no