Bryant 677C--A High-Pressure Switch, Copeland Scroll Compressor Puron Refrigerant

Page 31

High-Pressure Switch

The high-pressure switch is located in the discharge line and protects against excessive condenser coil pressure. It opens at 650 psig.

High pressure may be caused by a dirty outdoor coil, failed fan motor, or outdoor air recirculation. To check switch:

1.Turn off all power to unit.

2.Disconnect leads on switch.

3.Apply ohm meter leads across switch. You should have continuity on a good switch.

Copeland Scroll Compressor (Puron Refrigerant)

The compressor used in this product is specifically designed to operate with Puron (R-410A) refrigerant and cannot be interchanged.

The compressor is an electrical (as well as mechanical) device. Exercise extreme caution when working near compressors. Power should be shut off, if possible, for most troubleshooting techniques. Refrigerants present additional safety hazards.

!WARNING

EXPLOSION HAZARD

Failure to follow this warning could result in personal injury or death and/or property damage.

Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.

The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll. The scroll compressor has no dynamic suction or discharge valves, and it is more tolerant of stresses caused by debris, liquid slugging, and flooded starts. The compressor is equipped with an internal pressure relief port. The pressure relief port is a safety device, designed to protect against extreme high pressure. The relief port has an operating range between 550 and 625 psi differential pressure.

677C-- -- A

C99097

Fig. 24 - Refrigerant Circuit

31

Image 31
Contents Safety Considerations Table of ContentsIntroduction Receiving and Installation677C--A24-30 Unit Dimensions 677C--A36-60 Unit Dimensions CPRFCURB012A00 Unit SizeCPRFCURB010A00 CPRFCURB011A00Inspection Rig and Place UnitRigging/Lifting of Unit See Fig Carbon Monoxide Poisoning Hazard Install Flue HoodInstall Gas Piping Connect Condensate DrainConfiguring Units for Downflow Vertical Discharge Install Duct ConnectionsFire or Explosion Hazard Furnace Section CompressorsRefrigerant Metering CFMMaximum Gas Flow Capacity Physical Data Unit 677C--A Cont’dHeating Inputs Control Voltage Connections Install Electrical ConnectionsSpecial Procedures for 208-V Operation High-Voltage ConnectionsFIRE, EXPLOSION, Electrical Shock Hazard Balance Point Setting-Thermidistat or Hybrid ThermostatPRE-START-UP Transformer ProtectionUnit Sequence of Operation Start-up Heating and Make Adjust- mentsSTART-UP Check for Refrigerant LeaksUnit Damage Hazard Adjust Gas InputCheck Heating Control Check Gas InputNormal Operation Airflow and Temperature RiseLimit Switches Check Burner FlameIndoor Airflow and Airflow Adjustments Start-up Cooling and Make Adjust- mentsRollout Switch Checking and Adjusting Refrigerant ChargeColor Coding for Indoor Fan Motor Leads Two Cooling Fan Speeds Set-up Dehumidification feature usedGas Heating Fan Speed Set-up Continuous Fan OperationFilter Size CFM 677C--A Wet Coil Pressure DropRise Speed Color Range Unit Heating Motor Wire1505 1452 1413 1358 1323 1282 1234 1169 1130 25 55oF Heating 1962 1915 1880 1843 1794 1753 1711 1675 1628 35 65oF Heating 1962 1915 1880 1843 1794 1753 1711 1675 1628 30 60oF Heating 1887 1847 1783 1726 1677 1625 1578 1527 1432 30 60oF Heating 677C a 208/230-3-60 Wiring Diagram, Unit 677C--A Cooling Charging Table-Subcooling Indoor Blower and Motor MaintenanceCleaning the Blower Motor and Wheel Air FilterFlue Gas Passageways Limit SwitchInduced Draft combustion air Blower Assembly Burner IgnitionEXPLOSION, Personal Injury and Environmental Hazard Electrical Controls and WiringOutdoor Fan Refrigerant CircuitIndoor Airflow Pressure SwitchesLoss of Charge Switch Gas InputCopeland Scroll Compressor Puron Refrigerant High-Pressure SwitchExplosion Hazard Servicing Systems on Roofs and with Synthetic materials Unit Operation and Safety HazardRefrigerant System Compressor OilSTART-UP Checklist TroubleshootingPuronr R-410A Quick Reference Guide Symptom Cause Remedy Troubleshooting Guide Cooling or Heat Pump Heating ModeTroubleshooting Guide-LED Status Codes Troubleshooting Guide-HeatingLED OFF III. START-UP Electrical Supply Voltage Compressor Amps TemperaturesRemove and Store in Job Files Preliminary Information Model no