Bryant 677C--A Gas Input, Indoor Airflow, Check Defrost Thermostat, Puron Items

Page 30

If no refrigerant leaks are found and low cooling performance is suspected, refer to the Checking and Adjusting Refrigerant Charge section.

Gas Input

The gas input does not require checking unless improper heating performance is suspected. If a problem exists, refer to the Start-Up section.

Indoor Airflow

The heating and/or cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply- and return-air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to the Indoor Airflow and Airflow Adjustments section to check the system airflow.

Check Defrost Thermostat

The defrost thermostat is usually located on the lowest liquid leaving circuit of the left condenser coil (see Fig. 22). The thermostat closes at 32_F (0_C) and opens at 65_F (18_C).

Puron Items

Metering Device (Thermostatic Expansion Valve & Piston)

This unit uses both a hard shutoff, balance port TXV in the indoor coil and a piston in each side of the outdoor coil. The TXV maintains a constant superheat at the evaporator coil exit (cooling mode) resulting in higher overall system efficiency.

Pressure Switches

Pressure switches are protective devices wired into control circuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically designed to operate with Puron (R-410A) systems. R-22 pressure switches must not be used as replacements for the Puron (R-410A) system.

677C-- -- A

O

T2 C C O

DFT

 

 

 

 

 

OF2

OF1

R

T1

 

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

C

Y

 

 

 

 

 

 

 

 

SPEEDUP

P1

 

 

 

 

 

 

 

 

J1

P3

INTERVALTIMER

90

60 30

30 60

120

 

 

 

DFT

 

OFF

 

QUIET SHIFT

ON

 

 

 

Speedup

 

 

 

 

Quiet

Defrost interval

 

 

Pins

 

 

 

 

Shift

DIP switches

 

 

 

 

 

 

 

 

 

 

A08020

Fig. 23 - Defrost Control

Loss of Charge Switch

This switch is located on the liquid line and protects against low suction pressures caused by such events as loss of charge, low airflow across indoor coil, dirty filters, etc. It opens on a pressure drop at about 20 psig. If system pressure is above this, switch should be closed. To check switch:

1.Turn off all power to unit.

2.Disconnect leads on switch.

3.Apply ohm meter leads across switch. You should have continuity on a good switch.

NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psi. Never open system without breaking vacuum with dry nitrogen.

30

Image 30
Contents Table of Contents Safety ConsiderationsReceiving and Installation Introduction677C--A24-30 Unit Dimensions 677C--A36-60 Unit Dimensions CPRFCURB011A00 Unit SizeCPRFCURB010A00 CPRFCURB012A00Rig and Place Unit InspectionRigging/Lifting of Unit See Fig Connect Condensate Drain Install Flue HoodInstall Gas Piping Carbon Monoxide Poisoning HazardInstall Duct Connections Configuring Units for Downflow Vertical DischargeFire or Explosion Hazard CFM CompressorsRefrigerant Metering Furnace SectionPhysical Data Unit 677C--A Cont’d Maximum Gas Flow CapacityHeating Inputs High-Voltage Connections Install Electrical ConnectionsSpecial Procedures for 208-V Operation Control Voltage ConnectionsTransformer Protection Balance Point Setting-Thermidistat or Hybrid ThermostatPRE-START-UP FIRE, EXPLOSION, Electrical Shock HazardCheck for Refrigerant Leaks Start-up Heating and Make Adjust- mentsSTART-UP Unit Sequence of OperationCheck Gas Input Adjust Gas InputCheck Heating Control Unit Damage HazardCheck Burner Flame Airflow and Temperature RiseLimit Switches Normal OperationChecking and Adjusting Refrigerant Charge Start-up Cooling and Make Adjust- mentsRollout Switch Indoor Airflow and Airflow AdjustmentsContinuous Fan Operation Two Cooling Fan Speeds Set-up Dehumidification feature usedGas Heating Fan Speed Set-up Color Coding for Indoor Fan Motor Leads677C--A Wet Coil Pressure Drop Filter Size CFMUnit Heating Motor Wire Rise Speed Color Range1505 1452 1413 1358 1323 1282 1234 1169 1130 25 55oF Heating 1962 1915 1880 1843 1794 1753 1711 1675 1628 35 65oF Heating 1962 1915 1880 1843 1794 1753 1711 1675 1628 30 60oF Heating 1887 1847 1783 1726 1677 1625 1578 1527 1432 30 60oF Heating 677C a 208/230-3-60 Wiring Diagram, Unit 677C--A Cooling Charging Table-Subcooling Air Filter MaintenanceCleaning the Blower Motor and Wheel Indoor Blower and MotorBurner Ignition Limit SwitchInduced Draft combustion air Blower Assembly Flue Gas PassagewaysRefrigerant Circuit Electrical Controls and WiringOutdoor Fan EXPLOSION, Personal Injury and Environmental HazardGas Input Pressure SwitchesLoss of Charge Switch Indoor AirflowHigh-Pressure Switch Copeland Scroll Compressor Puron RefrigerantExplosion Hazard Compressor Oil Unit Operation and Safety HazardRefrigerant System Servicing Systems on Roofs and with Synthetic materialsTroubleshooting START-UP ChecklistPuronr R-410A Quick Reference Guide Troubleshooting Guide Cooling or Heat Pump Heating Mode Symptom Cause RemedyTroubleshooting Guide-Heating Troubleshooting Guide-LED Status CodesLED OFF Preliminary Information Model no TemperaturesRemove and Store in Job Files III. START-UP Electrical Supply Voltage Compressor Amps