Emerson SZV32, SZO44, SZV44, SZO56 manual Check for These Conditions Under Normal Operation

Page 22

Dual-Compressor Module

Operation

 

 

3.2Initial Startup - Compressor Package

Refer to your Packager’s user manual for information on procedures to start up the Compressor Package, which includes equipment added to the Compressor Module by the Packager.

3.3Normal Operation Checklist

Observe the following conditions after startup—when power is applied to the VFD and the VFD receives the signal from the Compressor Package control system to run:

CHECK FOR THESE CONDITIONS UNDER NORMAL OPERATION:

___ 1. Compressor speed should range from 2400 to 4800 rpm during normal operation.

___ 2. Suction pressure should range from 0.75 psig to 25 psig.

___ 3. Discharge pressure should range from 70 psig to 190 psig, depending on the model (see Compressor Module Nomenclature on page iv).

___ 4. Pressure differential between suction and discharge is at least 70 psi.

___ 5. First-stage separator temperature should be between 170°F and 220°F (77-104°C).

___ 6. Oil cooler fans should either run continuously or cycle periodically under normal conditions.

If any of these conditions are not met during normal operation, shut down the unit and refer to 5.0 - Troubleshooting on page 25.

16

2006SSD-75 R4 (10/10)

Image 22
Contents Copeland Scroll Compressor Module Page Table of Contents Appendix A Material Data Safety Sheet Figures Compressor Module Nomenclature Important Safety Information Safety Alert Symbol Safety Symbols Used in This ManualIntroduction Compressor ModuleOil coolers with fans Compressor Package CompressorInlet gas scrubber for liquid removal Inlet and Discharge Pressures Installation GuidelinesGeneral Installation Guidelines Required Component-Inlet Gas ScrubberBarg Setting Ambient Temperature RangeModule Weight Lbs. kg Installation Clearance and Dimensions Compressor Module Dimensions, in. mmProcess and Instrumentation Diagrams P&IDs Code DescriptionElectrical Controls SwitchesSwitchStatus General ConsiderationsOil Cooler Fan Control Brushless DC FanTemperature Control SZO44Variable Speed DriveCompressor Power data based on 480VAC Variable Speed Typical Compressor Module power supply requirementsElectrical Requirements Wiring Control Circuit TerminationsInitial Startup Compressor Module Pre-Startup ChecklistPost-Startup Checklist OperationCheck for These Conditions Under Normal Operation Maintenance Routine MaintenanceMaintenance summary Maintenance Tools Maintenance ToolsOil Level Guidelines Minimum Speed Checking the Oil LevelOil Capacity and Type Oil Level Guidelines Maximum SpeedTopping Off the Oil Level Adding and Removing OilAdding Oil Changing the Oil Draining OilReplacing Oil Cleaning the Inlet Screen Servicing the Scavenge Line OrificeChanging the Second-Stage Separator Element Changing the Oil Filter ElementMotor Winding Resistance Troubleshooting GuideTroubleshooting Motor winding resistancePlatform Symptoms Diagnosis Platform troubleshooting guidelinesSpecifications Compressor Module Specifications Dual-Compressor Module Technical Support and Service Configuration Suction Max Flow/HP as a function of discharge110 130 140150 Flow rate110 120 180Emergency Number 989 Product Name and Information Appendix A - Material Data Safety SheetSupplier Components and Hazard StatementReactivity Data Spill or Leak ProceduresFire and Explosion Hazards Health Hazard DataPage Page EmersonClimate.com
Related manuals
Manual 44 pages 48.85 Kb