;A corrosion inhibitor suitable for the materials in the system should be added to the glycol/water solution.
;If straight water use is desired, contact the Sterlco Engineering Department.
;The six gallon (23 liter) reservoir is not designed to withstand water pressure above 5 psi (34 kPa).
;The fill opening and vent line must be vented to the atmosphere for proper operation.
Figure 5
Ethylene Glycol Curve
30%
Ethylene glycol required
for evaporator freeze protection
Ethylene glycol percent by volume
20%
10%
0%
0º | 30º | 40º | 50º | 60º | 70º |
Chilled water
operating temperature °F
(set point)
Normal operating range is between 30°F and 70°F
SMC Series Chillers | Page 15 |