Process Water Bypass
All SMC chillers have an internal bypass device (patent pending). If the process flow becomes blocked during chiller operation, this component allows water to flow through the chiller. This protects the chiller from
2-3 SMC Condenser Air Supply
SMC chillers use the surrounding air to cool the condenser.
;Condenser air entering the SMC unit should be at least 65°F (18°C). Operation with air below 65°F (18°C) can cause the low pressure cutout to shut down the chiller due to the low refrigerant pressure.
;Install the chiller in an area where there is free passage of air for condensing.
;Provide 18” (46 cm) or more clearance for the chiller’s air intake.
;Make provisions to exhaust the heated air discharged from the chiller.
;Do not put the SMC unit where steam, hot air or fume exhausts will be drawn into the condenser.
;
;Normal condensing pressure with 95°F (35°C) air is approximately 180 psi (1,241 kPa) for the SMC050A and SMC100A; 275 psi (1,897 kPa) for the SMC150A.
SMC Ambient Temperature Ranges
Ambient temperature range | Minimum temperature | Maximum temperature |
Operation | 65°F (18°C) | 100°F (38°C) |
Storage | 40°F (4°C) | 120°F (49°C) |
2-4 Water Reservoir
During startup and when additional solution is required, see Figure 5 on Page 17 for the recommended ethylene glycol/water solution. This chart shows the proportions needed to provide freeze protection to 20°F/°C below the desired process setpoint.
;Add a
;Use industrial quality (not automotive) ethylene glycol.
Page 14 |
| SMC Series Chillers |
| ||
|