Sterling A0544325 installation manual Optional Graphic Panel, Indicator Lights, Switches

Page 27

6

Optional Graphic Panel

 

 

6-1 Indicator Lights

PUMP ON (green)

This indicator is lit when the pump runs.

COMPRESSOR ON (green)

This indicator is lit when the compressor operates.

HIGH REFRIGERANT PRESSURE (red)

This indicator lights if the condensing pressure exceeds a safe level. The chiller goes to Idle mode until the high refrigerant pressure cutout resets. The light then goes out and the chiller automatically restarts. Call a qualified refrigeration service technician for service.

LOW REFRIGERANT PRESSURE (red)

This indicator lights if the refrigerant pressure drops below a safe level. The compressor will stop and remain off until the pressure reaches a safe level. The light will go out and the chiller will then resume operation automatically.

LOW WATER FLOW (red), SMC units without pump only

This indicator lights if the flow switch senses chilled water/glycol flow through the evaporator dropping to an unacceptable level. The compressor will stop until the flow switch senses adequate flow and restarts the chiller.

6-2 Switches

POWER

This switch energizes the control circuit; it also turns off the chiller.

SMC Series Chillers

Page 27

Image 27
Contents SMC-050 to SMC-150 Series SMC Series Chillers Safety Considerations Table of Contents Table of Contents Charts and Figures Models Covered General InformationIntroduction Necessary DocumentsUncrating Your New Chiller Available OptionsEvent of Shipping Damages If the Shipment is Not CompleteIf the Shipment is Incorrect Returns SMC050A Process Pump CurvesSMC100A Process Pump Curves SMC150A Process Pump Curves SMC-150 25,400 16,000 12A 345 SMC Series Chiller SpecificationsChiller Installation Electrical ConnectionsProcess Water Connections Water Reservoir SMC Condenser Air SupplyEthylene Glycol Curve Overhead Piping Overhead Process ConsiderationsSequence of Operation Chilled Water CircuitRefrigeration Circuit High Pressure Cutout Low Pressure CutoutRemote Start/Stop Interlock SMC Component Identification End of unit piping Piping Schematic 1 Pump with ReservoirPiping Schematic 1 Pump without Reservoir Piping Schematic No Pump, No Reservoir SMC Startup Checklist SMC Pre-Startup ChecklistSMC Water Circuit Pressure Drop Table Setting the Process Water Temperature Setting the Alarm ValueMicroprocessor Control SP AL SMC ControlIndicator Lights SwitchesOptional Graphic Panel Optional Graphic Panel SMC SeriesTypical SMC Subpanel Routine MaintenanceCondenser Maintenance LubricationTypical SMC Wiring Schematic SMC Wiring Schematic for Chillers with No Pump or Reservoir SMC Series Chillers Problem Possible cause Solution Troubleshooting GuideProblem Possible cause Solution Description SMC Spare Parts ListService Notes Service Notes Sterling/Sterlco Milwaukee, WI5200 West Clinton Avenue 414 Fax 414