Problem | Possible cause | Solution | |
| Refrigerant is low. | Check the refrigerant charge. | |
| Pressure switch contacts are | Sight glass should be clear | |
| while compressor runs. Call | ||
| open. | for service if bubbling or | |
|
| foaming. | |
| Refrigerant high pressure | Check for dirty condenser. | |
| cutout switch contacts are | Check for condenser air | |
Pump runs, compressor will | open. | obstruction. | |
not. | Defective fan motor. | Repair or replace. | |
| Compressor internal overload | Check for high/low voltage. | |
| Must be within plus or minus | ||
| is open. Allow time to cool | 10% of the nameplate rating. | |
| and reset. | Check for poor compressor | |
|
| electrical connections. | |
| Broken wire in the | Locate and repair. | |
| compressor control circuit. | ||
|
| ||
| Restricted condenser airflow. | Clean the condenser. | |
Unit runs continuously, but | Unit low on refrigerant. | Call Service. | |
Inefficient compressor. | Call Service. | ||
not enough cooling power. | |||
Unit undersized for | Call Sales Representative. | ||
| |||
| application. | ||
|
|
Page 34 |
| SMC Series Chillers |
| ||
|