Carrier ZONEKIT4ZCAR ÐWiring Diagram Reference For, Programmable OPTIONS-TOGGLES, ÐStart-Up

Page 13

If a value of 105 to 110 is selected (second-stage heating is turned off at this value) then the first-stage high temperature trip limit is the programmed value plus 5°F (first-stage is turned off).

If a value of 111 to 155 is selected (second-stage heating is turned off) then the first-stage high temperature trip limit is the programmed value plus 20°F (first stage is turned off).

Example 1:

High temperature trip limit selected is 105°F. (Shown as 05 in controller display.)

Second-stage heat will turn off when duct temperature sensor measures a temperature greater than 105°F.

First-stage heat will turn off when duct temperature sensor measures a temperature greater than 110°F.

Example 2: High temperature trip limit selected is 140°F. (Shown as 40 in controller display.)

Second-stage heat will turn off when duct temperature sensor measures a temperature greater than 140°F.

First-stage heat will turn off when duct temperature sensor measures a temperature greater than 160°F.

7.Dual Fuel Setpoint (S-7)

This option is used with a system that has a heat pump and another heat source (possibly gas) that should not run at the same time as heat pump. When any heat pump is on, all auxiliary heat will be off, and vice versa.

NOTE: The auxiliary heat must always have greater heating ability than the heat pump at low outdoor temperatures for this option to have any value.

NOTE: If Dual Fuel setpoint is set to 0, then this option is disabled. If Dual Fuel option is used, an outside air temperature sensor or refrigerated air sensor must be used.

When dual fuel setpoint variable is set to outdoor temperature (10°F to 60°F) that is the crossover point between running heat pump or using auxiliary heat as the preferred method of heating.

The setpoint is used only when the first stage of heating is brought on. If outdoor temperature is above setpoint, heat pump (Y1) is energized. If outdoor temperature is below setpoint, auxiliary heat (W1) is used. If heat pump is started and outdoor temperature goes below setpoint, dual fuel option is not used for that heating cycle.

PROGRAMMABLE OPTIONS-TOGGLES

Turn zone selector dial to position T. (See Fig. 18.) The controller display shows setting number and its value.

The upper left 2 digits show setting number while the right side shows the value of ON or OFF.

Press the COOL up or down setpoint buttons to change toggle number and the HEAT up or down setpoint buttons to change status of toggle. (See Table 11.)

Step 12ÐWiring Diagrams

Refer to Tables 7 and 8 for wiring diagram reference information.

Step 13ÐStart-Up

1.Verify that zone number for remote room sensors and corre- sponding zone damper wire connections are the same in the Comfort Zone Center.

2.Check that AC power wires (dampers and transformer) are kept away from DC wires (remote room sensors, 4 zone controller, communication bus) leading up to, and in the Comfort Zone Center.

3.Check location of 4 zone controller and remote room sensors to make sure that they are not near heat producing devices such as lamps, sunlight, and appliances.

Table 7ÐWiring Diagram Reference

For Fig. 19 and 20

FAN COIL WITH AIR CONDITIONER

 

INDOOR UNIT (FIG. 19)

 

OUTDOOR UNIT

FA4A

 

 

 

 

FB4A

FK4A

 

FK4B

 

 

 

 

 

FC4B

 

 

 

 

Single-Stage

A

A

 

B

 

Air Conditioner

 

 

 

 

 

 

 

Two-Speed

D

 

E

 

Air Conditioner

 

 

 

 

 

 

 

FURNACE WITH AIR CONDITIONER

 

 

INDOOR UNIT (FIG. 20)

 

 

 

 

58WAV

 

 

 

 

58PAP

58ZAV

 

 

 

 

58RAP

58PAV

 

 

OUTDOOR UNIT

 

58GFA

58RAV

 

58TUA

58VUA/VCA

58DFA

58SXC

58MVP

 

58TMA

 

 

58EFA

58DXC

 

 

 

 

58SXA

58EJA

 

 

 

 

58DXA

58MXA

 

 

 

 

 

58MCA

 

 

Single-Speed

A* B

B

B

C

C

Air Conditioner

 

 

 

 

 

Two-Speed

D E*

H

H I ²

Air Conditioner

 

 

 

 

 

*KGATT0101VSP (Optional) Two-stage relay kitÐ may help to control over conditioning.

² Latent capacity controlÐRequired, field supplied. See 2-speed Installation Instructions.

Table 8ÐWiring Diagram Reference

For Fig. 21 and 22

FAN COIL WITH HEAT PUMP

 

INDOOR UNIT (FIG. 21)

 

OUTDOOR UNIT

FA4A

 

 

 

 

FB4A

FK4A

 

FK4B

 

 

 

 

 

FC4B

 

 

 

 

 

 

 

 

 

 

Single-Stage

A

A

 

B

 

Heat Pump

 

 

 

 

 

 

 

Two-Speed

D

 

E

 

Heat Pump

 

 

 

 

 

 

 

 

FURNACE WITH HEAT PUMP

 

 

 

INDOOR UNIT (FIG. 22)

 

 

 

 

58WAV

 

 

 

 

58PAP

58ZAV

 

 

 

 

58RAP

58PAV

 

 

OUTDOOR UNIT

 

58GFA

58RAV

 

58TUA

58VUA/VCA

58DFA

58SXC

58MVP

 

 

58EFA

58DXC

 

58TMA

 

 

 

 

 

 

58SXA

58EJA

 

 

 

 

58DXA

58MXA

 

 

 

 

 

58MCA

 

 

Single-Speed

A** B* **

C

C

D

D

Heat Pump

 

 

 

 

 

Two-Speed

E** F* **

I

I

Heat Pump

 

 

 

 

 

*KGATT0101VSP (Optional) Two-stage relay kitÐmay help to control over conditioning.

² Latent capacity controlÐRequired, field supplied. See 2-speed Installation Instructions.

**Field-supplied isolation relay.

4.Make sure that the 3 wire communication bus cable for the 4 zone controller is not run in same conduit, or use same cable jacket, as the 5 wire conductor of the 4 zone controller.

5.On a remote room sensor follow wire guide stamped on base by terminal screws in order to keep polarity and voltages correct. Otherwise sensor will not work properly.

6.Make sure duct temperature sensor is placed in supply air duct work, downstream of furnace and evaporator coil, and up- stream of bypass damper.

13

Image 13
Contents ZONEKIT4ZCAR ÐCheck Equipment and Jobsite ÐWiringShielded Cable ÐInstall Comfort Zone Center ÐWiring RequirementsÐInstall Zone Dampers From MAX Comfort Zone Gage Length Wires Center toRectangular Metal Duct Work Round Metal Duct WorkRound Flexible Duct Work Damper Mounting BracketÐInstall Duct Temperature Sensor ÐInstall Barometric Bypass DamperÐRound Flexible Duct Work Rectangular Fibrous Glass Duct WorkÐInstall Four Zone Controller ÐInstall Dx Coil SensorÐInstall Remote Room Sensors or Smart Sensors Optional ÐSequence of OperationÐComfort Zone System Wiring Diagram Selection of a Reference Zone in the System Sequence of Events for a Normal Heating or Cooling CyclePRE-POSITIONING Dampers and Starting the System FAN Controlling the Zone Dampers ÐZone Damper Positions Damper Position Versus Zone DemandOperating the Heating and Cooling Equipment Control Strategy for Heating / Cooling StagesÐHeating System Option Vs. Type of Heater Used Configuration Options for Equipment OperationÐAvailable Heating and Cooling Stages Vs. System Type Relay Pack to Hvac Equipment ConnectionsStage Control During Equipment Operation Ðhvac Equipment Stages Vs. Zone DemandHeating & Cooling Demand F Demand C Equipment Stages ÐConfiguring Four Zone Controller ÐProgrammable Options-SettingsProgrammable OPTIONS-SETTINGS ÐWiring Diagrams ÐWiring Diagram Reference ForProgrammable OPTIONS-TOGGLES ÐStart-UpÐProgramming Schedules System SwitchesController Display ÐExample Weekly ScheduleZone Selector Dial Right AM Time Period PM Time Period WrongÐAccessories ÐTemperature Sensor CalibrationsHome Access Module Smart Sensor and Smart Sensor Power PackÐTroubleshooting Outside AIR Temperature SensorÐToggle Summary Toggle Setting OFF DefaultSymptom Possible Cause ÐOperating ProblemsSF Error Code Description Solution HF Error Code Description Solution ÐTypical Wiring Diagrams Fan Coil with Air Conditioner Comfort Zone Center Speed AIR Conditioner ÐTypical Wiring Diagrams Furnace with Air Conditioner A94037 ÐTypical Wiring Diagrams Furnace with Air Conditioner ÐTypical Wiring Diagrams Fan Coil with Heat Pump A94044 ÐTypical Wiring Diagram Furnace with Heat Pump ÐTypical Wiring Diagrams Furnace with Heat Pump ÐTypical Wiring Diagrams Furnace with Heat Pump Toggle Description Factory Record Default JOB Setting Comfort Zone Configuration TableSetting Rotary

ZONEKIT4ZCAR specifications

The Carrier ZONEKIT4ZCAR is an innovative zoning system designed to enhance the comfort and efficiency of heating and cooling in residential and commercial spaces. Its functionality allows users to customize temperature settings in different areas of a building, which is especially valuable in larger homes or multi-room facilities.

One of the standout features of the ZONEKIT4ZCAR is its integration with Carrier’s advanced HVAC technology. This zoning system utilizes dampers that control airflow, directing heated or cooled air to specific areas as needed. This ensures that every room is maintained at the desired temperature without wasting energy on unused spaces. The system can effectively manage up to four different zones simultaneously.

The ZONEKIT4ZCAR is equipped with smart technology compatibility, allowing seamless integration with smart home systems. Users can control their zoning settings through mobile applications, voice commands, or smart thermostats. This feature enhances user convenience, providing access to temperature adjustments from anywhere in the home. Additionally, the system can be programmed to follow user schedules, optimizing energy usage and potentially lowering energy bills.

Another key characteristic of the Carrier ZONEKIT4ZCAR is its reliability and durability. Carrier is a well-respected brand in the HVAC industry, associated with high-quality products that are built to last. The ZONEKIT4ZCAR reflects this commitment, featuring robust construction and materials that ensure longevity and consistent performance.

The installation process of the ZONEKIT4ZCAR is designed to be straightforward, making it an appealing choice for both professionals and DIY enthusiasts. It is compatible with various Carrier heating and cooling systems, allowing for easy upgrades or replacements in existing setups.

In terms of energy efficiency, the ZONEKIT4ZCAR caters to environmentally conscious users. By allowing precise control over the climate in specific areas, the system reduces overall energy consumption, thereby lowering carbon footprints.

Finally, the ZONEKIT4ZCAR provides exceptional comfort and control, making it a smart investment for anyone looking to improve their indoor climate experience. With its combination of cutting-edge technology, user-friendly features, and energy efficiency, the Carrier ZONEKIT4ZCAR stands out in the HVAC market as a reliable choice for modern zoning solutions.