Carrier Official Manual Guide for Models: Understanding the 38TDB Functionality

Page 12

Table 4—High Capacity Only Subcooling

 

TXV TYPE EXPANSION DEVICE

UNIT

HIGH CAPACITY ONLY

 

SUBCOOLING AT SERVICE VALVE

024

14°F

036

15°F

037

11°F

048

12°F

060

16°F

 

 

Table 5—Control Function LED Code

CODE

DEFINITION

SIGNAL

IMPORTANCE*

 

 

Constant flash

No demand

10

No pause

Stand by

 

1 flash

Low-speed operation

9

w/pause

 

 

2 flashes

High-speed operation

8

w/pause

 

 

3 flashes

Outdoor thermistor failure

7

w/pause

 

 

4 flashes

Outdoor coil thermistor failure

6

w/pause

 

 

3 flashes

 

 

pause

Thermistor out of range

5

4 flashes

 

 

5 flashes

 

 

pause

Low pressure switch trip

4

1 flash

 

 

5 flashes

 

 

pause

High pressure switch trip

3

2 flashes

 

 

6 flashes

Compressor VC/VH trip

2

w/pause

 

 

Constant light

 

 

No pause

Board failure

1

No flash

 

 

*Function light signal order of importance in case of multiple signal request; 1 is most important.

FACTORY DEFAULTS

Factory defaults have been provided in the event of failure of outdoor air thermistor, coil thermistor, and/or furnace interface jumper.

ONE MINUTE SPEED CHANGE TIME DELAY

When compressor changes speeds from high to low or low to high, there is a 1-minute time delay before compressor restarts. The outdoor fan motor remains running.

COMPRESSOR OPERATION

When the compressor operates in second stage operation, the motor rotates clockwise. Both the lower and upper pistons are eccentric with the rotating crankshaft and both compress refriger- ant. When the compressor operates in single stage operation the motor reverses direction (rotates counterclockwise). The lower piston becomes idle and the upper piston compresses refrigerant.

The start and run windings are reversed.

CRANKCASE HEATER OPERATION

The two-speed control board energizes the crankcase heater during unit off cycle.

OUTDOOR FAN MOTOR OPERATION

The outdoor unit control energizes outdoor fan any time compres- sor is operating. The outdoor fan remains energized during the 1-minute compressor speed change time delay and if a pressure

switch or compressor overload should open. Outdoor fan motor will continue to operate for one minute after the compressor shuts off when the outdoor ambient is greater than or equal to 100°F.

COMPRESSOR VOLTAGE FAILURE (6 FLASHES)

The control senses the voltage of the compressor run winding. If compressor voltage (Vc) is less than 90v when control board is calling for compressor operation, control shuts compressor off for 15 minutes with outdoor fan running. After 15 minutes (provided there is a call for Y1 or Y2), control attempts to start compressor. During this time, a code of 6 flashes appears at control board. If Vc trip occurs 3 consecutive times during a Y1 request, then low capacity operation is locked out and control responds to Y2 requests until a reset occurs. If 3 consecutive trips occur in a combination of Yl and Y2 or all Y2 requests, then both low and high capacity operation will be locked out. The compressor voltage failure (6 flashes) can be caused by:

compressor internal overload trip (refer to Table 6 for correct winding resistance)

no 240 volt power supply to outdoor unit

failed compressor contactor(s)

failure of start relay to pick-up properly

improper wiring

PRESSURE SWITCH PROTECTION

The outdoor unit is equipped with high- and low-pressure switches. If the control senses the opening of a high or low pressure switch, it will respond as follows:

1.De-energize the compressor low or high speed contactor,

2.Keep the outdoor fan operating for 15 minutes,

3.Display the appropriate error code on the status light. (See Table 5)

4.After a 15 minute delay, if Yl or Y2 inputs are on and the LPS or HPS is reset, energize appropriate compressor contactor, either low or high.

5.If LPS or HPS has not closed after a 15 minute delay, the outdoor fan is turned off. If the open switch closes anytime after the 15-minute delay, then resume operation on call for Y1 and/or Y2.

MAJOR COMPONENTS

2-Speed Control

The two-speed control board controls the following functions:

-Low- and high-compressor contactor operation

-Outdoor fan motor operation

-Crankcase heater operation

-Compressor protection

-Pressure switch monitoring

-Time delays

Field Connections

The two-speed control received 24vac low-voltage control system inputs through the screw connections on the left side of the control board.

Dual Capacity Compressor

The dual capacity compressor contains motor windings that provide 2-pole (3500 RPM) operation. Refer to Table 6 for correct winding resistance.

Compressor Internal Relief

The compressor is protected by an internal pressure relief (IPR) which relieves discharge gas into compressor shell when differen- tial between suction and discharge pressures exceeds 525 psi. The compressor is also protected by an internal overload attached to motor windings.

12

Image 12
Contents Check Equipment and Job Site Unpack UnitA98516 Book Catalog No Form 38TDB-4SI Replaces 38TDB-3SI TabDimensions Install on a Solid, Level Mounting Pad→ -Install TXV Clearance Requirements→ FAN Coil LONG-LINE ApplicationsMake Piping Connections Install LIQUID-LINE Filter Drier Outdoor Unit Connected to FACTORY-APPROVED Indoor UnitRefrigerant Tubing Sweat ConnectionInstall Electrical Accessories Make Electrical ConnectionsSee notes 1, 2, 3, 6, 8, 10, A01495See notes 1, 2, 3, 4, A01496See notes 1, 2, 3, A01501See note 1, 2, 3, 4, A01504 A01502Make Airflow Selections Airflow Selection for 58CVA/58MVP FurnacesAirflow Selection for FK4C, FV4A, or 40FK FAN Coils Accessory Usage A01222† Required for all applications Start-Up A01192A00430 Required Liquid-Line Temperature F Check ChargeSystem Functions and Sequence of Operation High Capacity Only Subcooling Control Function LED CodeTemperature Thermistors Two-Speed Compressor Winding Resistance at 70F ±Final Checks Wiring Diagram-024, 036 A01513Wiring Diagram-037 A01439Wiring Diagram-060