Carrier 06E specifications Start-Up, 07E Physical Data, Unit 07E

Page 8

Table 3 — 07E Physical Data

UNIT 07E

 

A022

 

B027

 

 

B033

 

D044

OPERATING WEIGHT (lb)

 

1090

 

1200

 

 

1250

 

1410

REFRIGERANT

 

 

 

R-134a, R-22, R-507/404A

 

 

COMPRESSOR — 06E*

 

A250

 

A265

 

 

A275

 

A299

Cylinders

 

4

 

6

 

 

6

 

6

Bore (in.)

 

211/16

 

211/16

 

 

211/16

 

211/16

Stroke (in.)

 

23/16

 

2

 

 

23/16

 

27/8

Displacement (cfm at 1750 rpm)

 

50

 

68

 

 

75

 

99

Maximum Rpm

 

 

 

 

1750

 

 

Oil Charge (pt)

 

14

 

19

 

 

19

 

19

 

 

 

 

High Side Maximum Pressure (psi)

 

 

 

450

 

 

Low Side Maximum Pressure (psi)

 

 

 

245

 

 

CONDENSER (Shell and Tube)† Part Number

P701-0840AX

 

P701-0850AX

 

P701-0850AX

 

P701-1065AX

Refrigerant Storage

R-134a

71.3

 

85.90

 

 

85.90

 

112.70

15.4

 

18.67

 

 

18.67

 

23.77

Capacity (lb)

 

 

 

 

 

R-22

70.4

 

84.80

 

 

84.80

 

111.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min Refrigerant Operating

 

15.1

 

18.30

 

 

18.30

 

23.30

 

61.1

 

73.60

 

 

73.60

 

96.50

Charge (lb)

R-507/404A

 

 

 

 

15.1

 

18.30

 

 

18.30

 

23.30

 

 

 

 

 

 

REFRIGERANT CONNECTION (in. ODF)

 

 

 

 

 

 

 

 

Inlet

 

21/8

 

21/8

 

 

21/8

 

25/8

Outlet

 

13/8

 

13/8

 

 

13/8

 

15/8

WATER CONNECTION (in. FPT)

 

 

 

 

 

 

 

 

 

Inlet/Outlet

 

21/2

 

21/2

 

 

21/2

 

3

LEGEND

FPT — Female Pipe Thread

ODF — Outside Diameter, Female

*Compressor listed is the standard compressor for R-22, air conditioning duty. An 06ER compressor is standard equipment for low temperature (R-507/404A) applications. For medium temperature (R-134a) applications, an 06EM compressor is standard. Factory substitutions may be made. Contact Carrier Sales Representative.

†The condenser listed is for R-22, air conditioning duty and may change based on the application. Maximum condenser operating pressure: 350 psi refrigerant side, 150 psi water side.

START-UP

Energize crankcase heater at least 24 hours prior to start-up.

Check to see that oil level is approximately 1/3 up on the compressor sight glass.

Open water supply valve and allow water to reach condens- er. (Turn condenser fan on when the compressor unit is applied with air-cooled condenser.)

Backseat the compressor suction and discharge shutoff valves; open liquid line valve at receiver.

Start evaporator fan or chilled water pump.

Do not attempt start-up with terminal cover removed from compressor. Bodily injury or death may result from explosion and/or fire if power is supplied to compressor with the terminal cover removed or unsecured. See warning label on terminal cover.

Start Compressor — Push the control circuit START- STOP-RESET switch to START. The timer motor starts immediately. Depending on the position of the timer, the compressor start is delayed for 12 seconds to approximately 8 minutes. Check oil pressure after compressor has run a few minutes; the pressure should be 12 to 18 psi above the suction pressure. After about 20 minutes of operation, stop the com- pressor. Allow it to be idle for about 5 minutes, then observe the oil level in the sight glass. Refer to the Carrier Standard Service Techniques Manual, Chapter 1, Section 1-11, for adding oil. The proper oil level for the 06E compressor is approximately 1/3 up on sight glass.

Timer Functions (See Fig. 7 — Timer Cycle.)

1.Switch A (contacts A-A1 and A-A2) provides Time Guard® function. Start of compressor is delayed approxi- mately 5.5 minutes after shutoff. The minimum time between starts of compressor is 8 minutes.

2.Switch B (contacts B-B1 and B-B2) starts compressor and deenergizes the crankcase heater. These contacts also provide one-second time delay for part-winding start.

3.Switch E (contacts E-E1) provides approximately 40-second bypass of oil pressure switch (OPS) at start-up. Compressor will shut off if sufficient oil pressure does not build up.

4.Switch D (contacts D-D1) bypasses the low-pressure switch (LPS) for 2.5 minutes at start-up for winter start control.

Fig. 7 — Timer Cycle

8

Image 8
Contents Installation ContentsSafety Considerations Electrical Connections Unit 07E Volts A022B027 B03306E Hermetic Compressor Units Electrical Data Compressor Motor With Circuit Breaker LLS AUXDTS PRE-START-UP 06E Physical DataUnit 06E RefrigerantUnit 07E START-UP07E Physical Data Service Factory Switch SettingsProtection Devices Capacity Control SystemRemoving, Inspecting and Replacing Components Fig Capacity ControlNO. ContrSuction Cutoff Unloader Operation Compressor Components 06E Shown Lubrication System Torque ValuesSuction and Discharge Valve Plate Assembly Compressor Running Gear RemovalCompressor Running Gear Replacement Wear Limits 06E CompressorMotor Replacement Motor RemovalMotor Alignment Forced Circulation Page Copyright 2002 Carrier Corporation