06E,07E Compressors and Condensing Units
Installation, Start-Up and
Service Instructions
Hermetic, Water-Cooled
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Receive and Inspect Unit. . . . . . . . . . . . . . . . . . . . . . . . . 1
Place Unit in Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Check Compressor Mounting . . . . . . . . . . . . . . . . . . . . 1
Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Evacuate, Dehydrate, and Leak Test. . . . . . . . . . . . . . 7
Oil Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Start Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Timer Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Compressor Thermal Protection . . . . . . . . . . . . . . . . . 9
Capacity Control System . . . . . . . . . . . . . . . . . . . . . . . . . 9
Removing, Inspecting and Replacing
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Lubrication System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cylinder Heads. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Pressure Relief Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Suction and Discharge Valve Plate Assembly . . . 14
Terminal Plate Assembly . . . . . . . . . . . . . . . . . . . . . . . . 14
Compressor Running Gear Removal . . . . . . . . . . . . 14
Compressor Running Gear Replacement. . . . . . . . 15
Motor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Motor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Motor Burnout
Condenser Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 17
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
When working on the equipment, observe precautions in the literature, tags, stickers and labels attached to the equipment, and other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves. Use care when handling, rigging, and setting bulky equipment.
Electrical shock can cause personal injury and even death. Be sure power to equipment is shut off before installing or servicing this equipment. There may be more than one dis- connect. Tag disconnect(s) to alert others not to turn power on until work is completed.
INSTALLATION
Receive and Inspect Unit — Inspect shipment for damage. File claim with the shipping company if shipment is damaged or parts are missing.
Local water conditions can cause excessive fouling or pitting of condenser tubes. If such conditions are anticipated, a water treatment analysis is recommended. Refer to Carrier System Design Manual, Part 5, for general water conditioning information.
Place Unit in Position — Locate unit on floor in a
Make provision in piping layout to drain and vent condenser if system is to be shut down in winter.
Level unit and bolt firmly to foundation.
Check Compressor Mounting — Loosen compres- sor mounting bolts and remove shipping blocks from under compressor. Tighten all 4 bolts on compressor. Loosen each bolt just enough until the flanged washer can be moved sideways with finger pressure. See Fig. 1.
NOTE: Be sure that compressor floats freely on mounting springs.
SNUBBER FLANGED | |
BOLT | WASHER |
NEOPRENE
SNUBBER
COMPRESSOR FOOT
ISOLATION SPRING
Fig. 1 — Compressor Mounting
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book | 2 | 2 | 4 | 4 | PC 802 | Catalog No. | Printed in U.S.A. | Form | Pg 1 | Replaces: | |
Tab | 1b | 2a | 2b | 3a |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|