Carrier 06E, 07E specifications Aux, Dts, Lls

Page 6

 

 

 

LEGEND

AUX

Auxiliary

M1

Evaporator Fan or

C

Compressor Contactor

 

Chilled Water Pump

C1

Compressor Contactor

M2

Cooling Tower Pump

 

(XL start and first step of PW start)

M3

Cooling Tower Fan

C2

Compressor Contactor

NEC

National Electrical Code

 

(PW second step)

OPS

Oil-Pressure Switch

CH

Crankcase Heater

POR

Pumpout Relay

CHR

Crankcase Heater Relay

PW

Part Wind

CR

Control Relay

SW

Start-Stop-Reset Switch

DTS

Discharge Temperature Sensor

TB

Terminal Block

DX

Direct Expansion

TDR

Time Delay Relay

FU

Fuse

TM

Timer Motor

HPS

High-Pressure Switch

TR

Timer Relay

LLS

Liquid Line Solenoid Valve

XL

Across-the-Line

LPS

Low-Pressure Switch

 

 

Terminal Block Connector

Unmarked Terminal

Marked Terminal

Factory Wiring

Field Control Wiring

To indicate common potential only; not to represent wiring.

Splice

NOTES:

1.Factory wiring is in compliance with NEC. Any field modifications or additions must be in compliance with all applicable codes. Use copper, copper-clad aluminum for field power supply only.

2.Field power supply wiring must be 75 C minimum.

3.Compressor thermally protected. Three-phase motors are pro- tected against primary single-phasing condition.

4.Pilot duty control must be field supplied. Minimum contact rating must be 25 va.

5.60 Hz units have 120 volt control circuit. 50 Hz units have 230 volt control circuit. A separate source of supply at the correct voltage must be field supplied through a fused disconnect device with a

maximum rating of 15 A to TB2 connections L1 (Hot Side) and L2 (Neutral).

6.Open control circuit disconnect switch for servicing only. Discon- nect must remain closed for crankcase heater to operate.

7.A transformer of the following rating may be field supplied for 60 Hz units: 350 va.

8.Transformer must be fused and grounded per applicable codes.

9.If any of the original wiring furnished must be replaced, it must be replaced with 90 C wire or its equivalent.

10.Wiring is shown for single pumpout control. Single pumpout control should not be used on direct-expansion (DX) cooler appli- cations (see lower diagram for wiring when applied with DX cooler).

Fig. 6 — Control Circuit Wiring for 06E/07E Units

6

Image 6
Contents Contents Safety ConsiderationsInstallation Electrical Connections B027 Unit 07E VoltsA022 B03306E Hermetic Compressor Units Electrical Data Compressor Motor With Circuit Breaker AUX DTSLLS Unit 06E PRE-START-UP06E Physical Data RefrigerantSTART-UP 07E Physical DataUnit 07E Protection Devices ServiceFactory Switch Settings Capacity Control SystemNO. Removing, Inspecting and Replacing Components FigCapacity Control ContrSuction Cutoff Unloader Operation Compressor Components 06E Shown Lubrication System Torque ValuesSuction and Discharge Valve Plate Assembly Compressor Running Gear RemovalCompressor Running Gear Replacement Wear Limits 06E CompressorMotor Replacement Motor RemovalMotor Alignment Forced Circulation Page Copyright 2002 Carrier Corporation