Carrier Comprehensive Overview of 06E Compressor Parts List and Part Winding Start Compressor

Page 5

Table 1 — Electrical Data — Compressor Motor With Circuit Breaker

 

 

 

COMPRESSOR MOTOR DATA

 

 

CIRCUIT BREAKER

Compressor

Voltage

 

Maximum

Maximum

 

LRA-PW

Motor

Recommended

 

 

 

 

 

 

Winding

 

 

 

Recommended

Part Number

(3 Ph - 60 Hz)

Hp

Must Trip

RLA

LRA-XL

(first

Resistance

Circuit Breaker

MHA

MTA

LRA

RLA

06E*

 

 

Amps

 

 

winding)

(Ohms)

Part No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

208/230

 

108

87

345

207

0.32

HH83XB336

91

104

350

74.3

 

575

20

45

36

120

72

2.2

XA461

33

38

124

27.1

 

 

460

 

54

44

173

104

1.3

XA424

42

49

175

35.0

 

265

208/230

 

140

112

446

268

0.27

HH83XC509

110

127

420

90.7

 

575

25

57

46

164

98

1.6

XA469

46

53

164

37.9

A

 

460

 

70

56

223

134

1.1

XA426

55

643

210

45.7

275

208/230

 

168

135

506

304

0.22

HH83XC539

142

163

507

116.4

 

 

 

575

30

65

52

176

106

1.3

XA430

50

58

168

41.4

 

 

460

 

84

68

253

152

0.9

XA425

63

73

210

52.1

 

299

208/230

 

236

189

690

414

0.15

HH83XC537

187

215

636

153.6

 

575

40

94

75

276

165

1.0

XA551

74

85

236

60.7

 

 

460

 

118

95

345

207

0.58

XA550

92

106

295

75.7

 

LEGEND

LRA

Locked Rotor Amps

MHA — Must Hold Amps

MTA

Must-Trip Amps

PW

Part-Winding (Start)

RLA

Rated Load Amps

XL

Across-the-Line (Start)

*Refer to physical data table to match compressor with correct com- pressor or water-cooled condensing unit.

NOTES:

1.Compressor MTA and RLA values are maximum figures.

2.LRA values for PW second winding = 1/2 the LRA – XL value.

3.3-Pole XL circuit breakers shown, other 3-Pole XL alternates and 6-Pole PW breakers available. Terminal lugs for circuit breakers available in package 06EA660152 (not shown).

 

LEGEND

C1

Compressor Contactor

C2

Compressor Contactor (PW)

CCB

Compressor Circuit Breaker

CHR

Crankcase Heater Relay

CR

Control Relay

FU

Fuse

GND

Ground

HPS

High-Pressure Switch

LPS

Low-Pressure Switch

NEC

National Electrical Code

NEMA — National Electrical

 

Manufacturer’s Association

OPS

Oil Pressure Switch

POR

Pumpout Relay

TB

Terminal Block

TDR

Time Delay Relay

TM

Timer Motor

TR

Timer Relay

4.Recommended RLA value shown is determined by: circuit breaker must trip value 1.40. Use this recommended (and minimum) RLA value to determine nameplate stamping, mini- mum contactor sizing, and wire sizing. RECOMMENDED RLA FOR 06E COMPRESSORS EQUALS: MUST-TRIP (MTA) OF

CARLYLE APPROVED OVERCURRENT DEVICE BEING USED 1.40

5.Compressor operating amps at any specific condition can only be determined from a performance curve.

6.Ohm values for resistance are approximate and shown for ref- erence purposes only. Motors from different vendors and motors of different efficiencies can differ up to 15% from data shown.

7.Electrical data for compressor part numbers 06ER, 06EM and 50 Hz models (not shown) are available from Carrier Sales Representative.

Fig. 5 — Component Location

5

Image 5
Contents Installation ContentsSafety Considerations Electrical Connections A022 Unit 07E VoltsB027 B03306E Hermetic Compressor Units Electrical Data Compressor Motor With Circuit Breaker LLS AUXDTS 06E Physical Data PRE-START-UPUnit 06E RefrigerantUnit 07E START-UP07E Physical Data Factory Switch Settings ServiceProtection Devices Capacity Control SystemCapacity Control Removing, Inspecting and Replacing Components FigNO. ContrSuction Cutoff Unloader Operation Compressor Components 06E Shown Torque Values Lubrication SystemCompressor Running Gear Removal Suction and Discharge Valve Plate AssemblyWear Limits 06E Compressor Compressor Running Gear ReplacementMotor Removal Motor ReplacementMotor Alignment Forced Circulation Page Copyright 2002 Carrier Corporation