Carrier 06D System noises, Compressor loses oil, Frosted suction line, Hot liquid line

Page 19

PROBLEM

CAUSE

REMEDY

System noises.

Piping vibration.

Support piping as required, check for loose pipe

 

 

connectors.

 

Expansion valve hissing.

Add refrigerant, check for plugged liquid line

 

 

strainer.

 

Compressor noisy.

Check valve plates for valve noise, replace

 

 

compressor (worn bearings), check for loose

 

 

compressor holddown bolts.

 

Insufficient compressor oil.

Add oil.

Compressor loses oil.

Leak in system.

Repair leak.

 

Plugged or stuck compressor oil return

Repair or replace.

 

check valve.

 

 

Oil trapping in line.

Check piping for oil traps.

 

Crankcase heaters not energized during

Replace heaters.

 

shutdown.

 

Frosted suction line.

Expansion valve admitting excess

Adjust expansion valve.

 

refrigerant.

 

Hot liquid line.

Shortage of refrigerant.

Repair leak and recharge.

Frosted liquid line.

Receiver shutoff valve partially closed or

Open valve or remove restriction.

 

restricted.

 

 

Restricted catchall.

Replace.

 

Restricted strainer drier.

Replace.

Frosted expansion valve.

Ice plugging TXV orifice.

Apply hot wet cloth to TXV.

 

Moisture indicated by increase in suction

Install drier.

 

pressure.

 

 

Plugged TXV strainer.

Clean strainer or replace TXV.

LEGEND

 

 

TXV — Thermostatic Expansion Valve

19

Image 19
Contents Installation ContentsBefore Installation Safety ConsiderationsB212 Unit 07D Width aA203 B205 A208 B21006D Compressor Unit Dimensions Electrical Connections LLS EquipGND HPSLow-Pressure Switch Timer Relay Ground Connection SwitchCrankcase Heater Overload Relay Control Relay Recommended Field Wiring Initial START-UP Refrigerant ChargingChecking Operation Pressure Change Affecting Switch Type Switch PositionClosed Capacity Control Pressure Fig Condenser MaintenanceCapacity Control Valve Operation Range Usage PER ServiceService Notes Size Threads TorquePhase Barrier Positioning KEY see FIG Removing Pump End Bearing Head Pump END Compressor Part Compressor Model MAX* AllowWear Motor ENDCompressor Running Gear Removal Cleaning Suction StrainerCompressor Motor Burnout Compressor Running Gear ReplacementProblem Cause Remedy TroubleshootingHot liquid line System noisesCompressor loses oil Frosted suction lineCopyright 2002 Carrier Corporation