Carrier 06D specifications Unit 07D Width a, A203 B205 A208, B210, B212, B215

Page 2

DIMENSIONS (in.)

UNIT 07D

WIDTH A

A203

30

B205

30

A208

399/16

B210

519/16

B212

519/16

B215

6313/16

NOTES:

1. For standard service practices, such as trouble- shooting and refrigerant charging, allow a minimum 2′-6″ clearance around the unit.

2. Recommended service space for condenser tube removal is one condenser length at either end.

3. For compressor removal, allow a minimum 3′ wide access aisle to and from the unit.

4. Local codes or jurisdiction may prevail for unit clearances.

WATER CONNECTIONS FOR 07DB215 UNIT ONLY.

Fig. 1 — 07D Condensing Unit Dimensions

2

Image 2
Contents Safety Considerations ContentsBefore Installation InstallationB210 Unit 07D Width aA203 B205 A208 B21206D Compressor Unit Dimensions Electrical Connections HPS EquipGND LLSCrankcase Heater Overload Relay Control Relay Ground Connection SwitchLow-Pressure Switch Timer Relay Recommended Field Wiring Checking Operation Refrigerant ChargingInitial START-UP Closed Switch Type Switch PositionPressure Change Affecting Condenser Maintenance Capacity Control Pressure FigCapacity Control Valve Operation Size Threads Torque ServiceService Notes Range Usage PERPhase Barrier Positioning KEY see FIG Removing Pump End Bearing Head Motor END Compressor Part Compressor Model MAX* AllowWear Pump ENDCleaning Suction Strainer Compressor Running Gear RemovalCompressor Running Gear Replacement Compressor Motor BurnoutTroubleshooting Problem Cause RemedyFrosted suction line System noisesCompressor loses oil Hot liquid lineCopyright 2002 Carrier Corporation