Carrier 06D specifications Pressure Change Affecting, Switch Type Switch Position, Closed

Page 9

Table 2A — 06D Physical Data

UNIT 06D

A8081

 

H3131

 

A8181

 

 

E8251

 

E3281

 

E5371

OPERATING WEIGHT (lb)

180

 

250

 

265

 

 

325

 

325

 

330

REFRIGERANT

 

 

 

 

R-134a, R-22, R-507/404A

 

 

 

 

COMPRESSOR — 06D*

M808

 

M313

 

A818

 

 

A825

 

A328

 

A537

Cylinders

2

 

4

 

4

 

 

6

 

6

 

6

Bore (in.)

2

 

2

 

2

 

 

2

 

2

 

2

Stroke (in.)

11/4

 

1

 

17/16

 

 

11/4

 

115/32

 

115/16

Displacement (cfm at 1750 rpm)

8

 

13

 

18.3

 

 

23.9

 

28

 

37.1

Maximum Rpm

 

 

 

 

 

 

1750

 

 

 

 

Oil Charge (pt)

3

 

4.5

 

5.5

 

 

8

 

8

 

8

 

 

 

 

 

High Side Maximum Pressure

 

 

 

 

 

450

 

PSIG

 

 

 

 

Low Side Maximum Pressure

 

 

 

 

 

245 PSIG

 

 

 

 

CONNECTIONS (in.)

 

 

 

 

 

 

 

 

 

 

 

 

Suction Valve (ODF)

7/8

 

7/8

 

11/8

 

 

13/8

 

13/8

 

13/8

Discharge Valve (ODF)

5/8

 

5/8

 

7/8

 

 

7/8

 

7/8

 

11/8

*Compressors listed are for R-22 applications. For R-134a and R-507/ 404A an 06DR compressor is standard. Factory compressor substitutes may be made. Contact Carrier Sales Representative.

NOTE: The 06DE8251 compressor unit with the 06DA825 compressor replaces the 06DE8241 once inventory of the 06DA824 compressor is depleted.

Table 2B — 07D Physical Data

UNIT 07D

 

A203

 

B205

 

A208

 

 

B210

 

B212

 

B215

OPERATING WEIGHT (lb)

 

270

 

395

 

420

 

 

545

 

595

 

620

REFRIGERANT

 

 

 

 

 

R-134a, R-22, R-507/404A

 

 

 

 

COMPRESSOR — 06D*

 

M808

 

M313

 

A818

 

 

A825

 

A328

 

A537

Cylinders

 

2

 

4

 

4

 

 

6

 

6

 

6

Bore (in.)

 

2

 

2

 

2

 

 

2

 

2

 

2

Stroke (in.)

 

11/4

 

1

 

17/16

 

 

11/4

 

115/32

 

115/16

Displacement (cfm at 1750 rpm)

 

8

 

13

 

18.3

 

 

23.9

 

28

 

37.1

Maximum Rpm

 

 

 

 

 

 

1750

 

 

 

 

Oil Charge (pt)

 

3

 

4.5

 

5.5

 

 

8

 

8

 

8

 

 

 

 

 

 

High Side Maximum Pressure

 

 

 

 

 

 

450

 

PSIG

 

 

 

 

Low Side Maximum Pressure

 

 

 

 

 

 

245 PSIG

 

 

 

 

CONDENSER (Shell and Tube)† Part Number

P701-0605CX

 

P701-0607CX

 

P701-0610CX

 

P701-0615CX

 

P701-0620CX

 

P701-0625AX

Refrigerant Storage

R-134a

17.20

 

15.90

 

24.40

 

 

31.60

 

27.40

 

39.80

2.86

 

3.16

 

5.00

 

 

7.55

 

8.47

 

9.18

Capacity (lb)

 

 

 

 

 

 

 

R-22

17.00

 

15.70

 

24.10

 

 

31.20

 

27.10

 

39.30

 

 

 

 

 

 

 

Min Refrigerant Operating

2.80

 

3.10

 

4.90

 

 

7.40

 

8.30

 

9.00

 

 

 

 

 

 

 

 

14.70

 

13.60

 

20.90

 

 

27.10

 

23.50

 

34.10

Charge (lb)

R-507/404A

 

 

 

 

 

 

 

 

2.80

 

3.10

 

4.90

 

 

7.40

 

8.30

 

9.00

REFRIGERANT CONNECTION (in. ODF)

 

 

 

 

 

 

 

 

 

 

 

 

Inlet

 

15/8

 

15/8

 

15/8

 

 

15/8

 

15/8

 

15/8

Outlet

 

11/8

 

11/8

 

11/8

 

 

11/8

 

11/8

 

11/8

WATER CONNECTION (in. FPT)

 

 

 

 

 

 

 

 

 

 

 

 

 

Inlet/Outlet

 

1

 

1

 

11/4

 

 

11/4

 

11/4

 

2

LEGEND

FPT — Female Pipe Thread

ODF — Outside Diameter, Female

*Compressor listed is the standard compressor for R-22, air conditioning duty. An 06DR compressor is standard equipment for low temperature (R-507/404A) or medium temperature (R-134a) applications. Factory substitutions may be made. Contact Carrier Sales Representative.

†The condenser listed is for R-22, air conditioning duty and may change based on the application. Maximum condenser operating pressure: 350 psi refrigerant side, 300 psi water side (“CX” models); 350 psi refrigerant side, 150 psi water side (“AX” models).

NOTE: The 07DB210 with the 06DA825 compressor replaces the 07DB210 with the 06DA824 once the compressor inventory is depleted.

Table 3 — Factory Switch Settings

 

 

PRESSURE CHANGE AFFECTING

SWITCH TYPE

 

SWITCH POSITION

 

 

 

Closed

 

Open

High Pressure

210

(±10) (psig)

290

(±10) (psig)

Low Pressure

70

(±4) (psig)

60

(±4) (psig)

Oil Pressure

 

6 (psid)

11 (psid)

LEGEND

psid — pounds per square inch differential psig — pounds per square inch gage

NOTES:

1.Values for the high- and low-pressure switches based on R-22. For other refrigerants, reset to pressure corresponding to satura- tion temperatures indicated by the listed pressures.

2.Values for oil pressure are above operating suction pressure (pressure differential between suction and discharge pressures of oil pump).

CAPACITY CONTROL (Suction Cutoff Type)

Control Set Point (Cylinder Load Point) — Set point is adjustable from 0 to 86 psig. Pressure differential between cylinder load-up point and cylinder unload point is adjustable from 7 to 19 psi.

To Regulate Control Set Point — Refer to Fig. 7. Turn adjustment nut clockwise to its bottom stop (with nut in this position, set point is 86 psig). Control set point is then regulated to desired pressure by turning adjustment nut coun- terclockwise. Every full turn decreases set point by 7.2 psi. Approximately 12 turns in counterclockwise direction will de- crease control set point to 0 psig. Table 4 shows steps of control for the compressor and condensing unit.

Pressure Differential Adjustment — Turn differ- ential adjusting screw counterclockwise to its back-stop posi- tion (differential in this position is 7 psi). Pressure differential is set by turning adjustment screw clockwise. Every full turn increases differential by 1.2 psi. Approximately 10 turns in clockwise direction will increase pressure differential to 19 psi.

9

802

Image 9
Contents Before Installation ContentsSafety Considerations InstallationA203 B205 A208 Unit 07D Width aB210 B21206D Compressor Unit Dimensions Electrical Connections GND EquipHPS LLSGround Connection Switch Low-Pressure Switch Timer RelayCrankcase Heater Overload Relay Control Relay Recommended Field Wiring Refrigerant Charging Initial START-UPChecking Operation Switch Type Switch Position Pressure Change AffectingClosed Capacity Control Pressure Fig Condenser MaintenanceCapacity Control Valve Operation Service Notes ServiceSize Threads Torque Range Usage PERPhase Barrier Positioning KEY see FIG Removing Pump End Bearing Head Wear Compressor Part Compressor Model MAX* AllowMotor END Pump ENDCompressor Running Gear Removal Cleaning Suction StrainerCompressor Motor Burnout Compressor Running Gear ReplacementProblem Cause Remedy TroubleshootingCompressor loses oil System noisesFrosted suction line Hot liquid lineCopyright 2002 Carrier Corporation