Carrier 09RH specifications Compressor Ratings 507/404A

Page 17

Table 12 — Compressor Ratings;

R-507/404A

UNIT

5F20

5F30

5F40

5F60

SST

SDT

Cap.

Bhp

Cap.

Bhp

Cap.

Bhp

Cap.

Bhp

 

90

1.0

3.5

1.5

5.1

2.1

6.8

3.1

10.2

–40

100

0.8

3.3

1.3

4.9

1.7

6.5

2.5

9.7

105

0.7

3.2

1.1

4.8

1.5

6.3

2.2

9.4

 

 

110

0.6

3.1

0.9

4.7

1.3

6.2

1.9

9.2

 

90

2.1

5.0

3.2

7.5

4.3

10.0

6.5

14.9

–20

100

1.9

5.1

2.9

7.5

3.9

10.0

5.8

14.9

105

1.8

5.1

2.7

7.5

3.6

10.0

5.5

14.9

 

 

110

1.7

5.1

2.5

7.5

3.4

10.0

5.2

14.9

 

90

3.9

6.3

5.8

9.4

7.8

12.5

11.7

18.7

0

100

3.5

6.6

5.3

9.8

7.1

13.0

10.7

19.4

105

3.4

6.7

5.1

9.9

6.8

13.2

10.2

19.8

 

 

110

3.2

6.8

4.8

10.1

6.4

13.4

9.7

20.1

 

90

6.6

7.4

9.9

11.0

13.3

14.6

19.9

21.8

20

100

6.0

7.9

9.1

11.7

12.2

15.6

18.2

23.3

105

5.8

8.1

8.7

12.1

11.6

16.1

17.4

24.1

 

 

110

5.5

8.4

8.3

12.4

11.0

16.5

16.6

24.8

 

 

 

 

 

UNIT

5H40

5H46

5H60

5H66

SST

SDT

Cap.

Bhp

Cap.

Bhp

Cap.

Bhp

Cap.

Bhp

 

90

5.0

14.9

6.2

19.4

7.6

22.1

9.4

28.7

–40

100

4.1

14.4

5.1

18.7

6.2

21.3

7.8

27.7

105

3.6

14.1

4.5

18.3

5.5

20.9

6.9

27.2

 

 

110

3.1

13.9

3.9

18.0

4.7

20.5

6.0

26.7

 

90

10.3

22.2

12.8

28.9

15.5

33.1

19.3

43.0

–20

100

9.3

22.4

11.6

29.1

14.0

33.3

17.5

43.3

105

8.8

22.4

10.9

29.1

13.2

33.4

16.5

43.4

 

 

110

8.2

22.5

10.2

29.2

12.4

33.4

15.5

43.5

 

90

18.5

28.6

22.9

37.1

27.7

42.6

34.5

55.5

0

100

16.9

29.7

21.0

38.6

25.4

44.3

31.6

57.7

105

16.2

30.2

20.0

39.2

24.3

45.0

30.2

58.7

 

 

110

15.4

30.7

19.0

39.9

23.1

45.8

28.7

59.6

 

90

30.9

33.6

38.3

43.7

46.3

50.2

57.5

65.3

20

100

28.4

36.0

35.2

46.8

42.6

53.8

52.9

70.0

105

27.1

37.1

33.7

48.2

40.7

55.4

50.6

72.2

 

 

110

25.9

38.2

32.1

49.6

38.8

57.0

48.2

74.2

LEGEND

Bhp — Brake Horsepower

Cap. — Capacity (Tons)

SDT — Saturated Discharge Temperature (F)

SST — Saturated Suction Temperature (F)

NOTES:

1. Shaded ratings require water-cooled heads, if the dis- charge temperature exceeds 275 F.

2.An oil cooler is recommended for all long stroke compressors (5H46, 66, 86, 126).

3.Oil cooler required when SST is below –20 F.

4.Refer to Table 5 for Total Heat Rejection.

UNIT

5H80

5H86

5H120

5H126

SST

SDT

Cap.

Bhp

Cap.

Bhp

Cap.

Bhp

Cap.

Bhp

 

90

10.1

29.2

12.6

37.9

15.2

43.3

18.9

56.4

–40

100

8.3

28.1

10.3

36.5

12.5

41.6

15.6

54.3

105

7.3

27.6

9.1

35.8

11.1

41.0

13.8

53.2

 

110

6.3

27.1

7.9

35.2

9.6

40.2

11.9

52.3

 

90

20.7

43.8

25.9

57.0

31.1

65.3

38.6

85.0

–20

100

18.7

44.1

23.3

57.4

28.1

65.8

34.9

85.5

105

17.7

44.2

22.0

57.6

26.5

65.9

33.0

85.7

 

110

16.6

44.2

20.6

57.7

24.9

66.0

31.0

85.9

 

90

37.0

56.5

46.0

73.5

55.5

84.3

68.9

109.7

0

100

33.9

58.7

42.2

76.5

50.9

87.7

63.2

114.1

 

105

32.4

59.7

40.2

77.9

48.6

89.2

60.3

116.1

 

110

30.8

60.7

38.2

79.2

46.2

90.7

57.3

118.0

 

90

61.8

66.6

76.7

86.7

92.7

99.5

114.9

129.3

20

100

56.8

71.4

70.5

93.0

85.2

106.7

105.8

138.7

105

54.3

73.6

67.4

95.9

81.5

110.0

101.1

143.1

 

110

51.8

75.7

64.3

98.6

77.7

113.2

96.4

147.2

17

Image 17
Contents Application Data Factors Compression Exponent NCompression Without Ratio WATER-COOLED HeadsMinimum Protection RPM SAT Saturated Suction Temperatures F Discharge Temp FRating Basis and Capacity Multipliers for R-12 and R-134a SST SDT Return GAS Temperature F913 922 931 SST SDT Compressor Ratings R-12Unit 5H40 5H46 5H60 5H66 5H80 5H86 5H120 5H126 Compressor Ratings R-22 19.2 20.7 24.9 13.0 28.4 16.1 37.0 17.3 37.7 21.6 49.1 26.0 56.1 32.2 73.1 Compressor Ratings R-502 11.6 12.9 16.8 12.0 15.6 17.5 22.9 11.3 14.8 16.6 21.7 20.7 27.0 30.4 39.5 Compressor Ratings R-134a Compressor Ratings 507/404A Compressor GPM Weight Distribution, Condensing UnitsCond ComprNema Frame Size Weight Distribution, Compressor Units See drawing, TableCompr Model CYL Capacity Control Reduction StepsCompr Contr Capacity Control 5F40, 60 5H40, 46, 60, 66, 80 Initial and Final Unloading Oil Pressures 5F20, 5F30Pneumatic Compensation External Solenoid-Type Capacity Control 5F40 and 5F60 Compressors 5H40, 46, 60, 66, 80, 86 Bearing Head External Available Compressor Capacity Control Steps Heat Pump ModificationSolenoid ValvesStarting Compressor Starting TorquesPkg No Belts 5F20-A181 Belt Drive PackagesCompressor Flywheel Dimensions Model Flywheel Compressor DimensionsFlywheel Width Pitch Grooves Model NumberPage Booster R Factors Suct Discharge Temperature FControl Pressurestats for Low Stage Application CharacteristicsSelected Example SST SDT 5F,H Booster Ratings R-12SST SDT 5F,H Booster Ratings R-225H40 5H46 5H60 5H66 Cap Bhp 5F,H Booster Ratings R-502Unloading Booster Compressor Starting DataRecommended MIN Motor Size HP Friction Compr During SizeCondenser Gpm at Various Water Velocities Condenser Physical DataMax Condenser Tube Water Velocity Condenser Water Circuiting THRWater to Glycol Flow Rate Correction