Carrier 09RH specifications Compressor Starting Torques

Page 27

The variety of systems using 5F,H compressors make it impractical to cover all aspects of hot gas bypass operation. The following guidelines will aid in determining the proper application.

The hot gas bypass valve is basically a pressure regulating valve installed to hold a constant compressor suction pressure. It should operate over as small a pressure range as possible. The normal set point of the valve should be coordinated with cylinder unloaders so that the bypass valve starts to open at a pressure where the last cylinder bank unloads, and is fully open at a slightly lower pressure. Types, ratings and published appli- cation guides for various available valves must be evaluated to determine the proper valve and installation practice for each application.

If a compressor system is to operate down to zero load, the valve capacity should equal compressor capacity when fully unloaded. For systems using multiple evaporators, it may be necessary to use multiple hot gas valves.

Hot gas should be taken from a point as close as possible to compressor discharge and fed through a hot gas solenoid valve and then through a hot gas valve. The hot gas solenoid valve can be controlled by a pressure switch or temperature switch. On compressors equipped with an electrically actuated cylinder unloader, the hot gas solenoid should be wired in parallel with the solenoid that unloads the final cylinder bank so that bypass- ing starts immediately when all cylinders are unloaded.

HOT GAS INJECTION INTO LIQUID LINE — When amount of bypass is small and the evaporator has a low pres- sure drop distribution system and existing system piping does not present problems, hot gas is frequently injected into the liquid line between the thermostatic expansion valve (TXV) and the evaporator. The ideal point for hot gas injection is into the side inlet of a side connection distributor, where inlet is downstream of distributor orifice. If too much hot gas is injected upstream of a distributor orifice, gas binding and erratic expansion valve operation will result. Injection into liquid line is recommended whenever practical, since agitation in the evaporator and normal operation of the TXV will tend to thoroughly desuperheat injected hot gas and prevent compres- sor overheating.

HOT GAS INJECTION INTO COMPRESSOR SUCTION — Hot gas injection into compressor suction is sometimes neces- sary but must be done with caution to ensure sufficient desuperheating of hot gas and to prevent liquid slugging in the compressor. Following guidelines should be observed:

1.Inject hot gas as close as possible to the evaporator outlet.

2.Install a TXV bulb at least 3 or 4 ft (further if possible) downstream from the hot gas injection point to ensure good gas mixing before the bulb.

3.Install a separate small TXV to inject liquid refrigerant into the suction line along with bypass gas. This valve should have capacity approximately 25% of hot gas valve capacity since hot gas must be superheated but not condensed.

4.Install a suction (knockout) drum in the suction line immediately before the compressor and downstream of the hot gas inlet and liquid injection inlet. Only larger industrial systems or systems with many remote evapora- tors can normally justify the extra expense of injecting hot gas into the compressor suction.

Motor Selection Data — Motor selection data based on brake horsepower occurring at design operating condition is usually satisfactory for applications in air conditioning suction temperature range.

Required compressor starting torque is dependent on dis- charge pressure as well as pressure differential occurring during start-up and is the same for any compressor speed. Values shown in Table 19 indicate maximum starting torque for R-12, R-134a, R-22, R-502, and R-507/404A. In most cases, a standard torque motor can be selected because of the partially unloaded starting feature of the 5F and 5H compressors.

In selection of a motor, the required motor starting torque must exceed the compressor starting torque only when the compressor is operating at same speed as the motor. If com- pressor speed is less than motor speed, as on some belt drive units, the motor starting torque requirements are reduced in proportion to the speed ratio between the compressor and motor because of mechanical advantage available to the motor.

In special applications or systems where there is a large pulldown requirement, the bhp requirement during pulldown may significantly exceed bhp at design conditions. The motor must not be overloaded during pulldown operation. If the motor is sized for pulldown, it will be only partially loaded during design operation and will run inefficiently. Therefore, select a motor that will be optimized for system design require- ments and not for pulldown requirements. Two ways for handling this are:

1.Install a crankcase pressure regulator in the system to maintain a given saturated suction temperature, thereby controlling bhp requirement, or

2.Install a current sensing device so that the motor current draw does not exceed the maximum rated motor current.

Drive Packages — Table 20 indicates drive package components for 5F,H standard belt drive packages. Figure 17 and Tables 21 and 22 indicate data for the flywheel used in each of these packages.

Table 19 — Compressor Starting Torques

 

%

 

 

SATURATED DISCHARGE TEMPERATURE (F)

 

 

 

 

80 F

 

 

100 F

 

 

120 F

 

COMPRESSOR

UNLOADING

 

 

 

 

 

 

 

 

 

SIZE

DURING

R-12,

R-22

R-502,

R-12,

R-22

R-502,

R-12,

R-22

R-502,

R-134a

R-507/404A

R-134a

R-507/404A

R-134a

R-507/404A

 

STARTING

 

 

 

 

 

 

 

 

Maximum Starting Torque (lb-ft)

 

 

 

5F20

None

19

30

32

27

42

45

34

53

57

5F30

None

22

34

37

30

47

50

39

61

65

5F40

75

18

28

30

25

39

42

32

50

53

5F60

662/

22

34

37

30

47

50

39

61

65

 

3

 

 

 

 

 

 

 

 

 

5H40

75

42

65

70

57

89

95

74

115

123

5H46

75

53

81

87

71

111

119

92

144

154

5H60

662/

51

79

85

69

107

115

90

140

149

5H66

3

64

99

106

86

134

144

113

175

186

662/

 

3

 

 

 

 

 

 

 

 

 

5H80

75

58

90

96

79

123

130

102

158

169

5H86

75

73

113

120

99

154

162

127

197

212

5H120

662/

91

141

151

123

191

204

160

249

266

5H126

3

114

176

189

154

239

255

200

311

332

662/

 

3

 

 

 

 

 

 

 

 

 

27

Image 27 Contents
Application Data Heads Compression Exponent NFactors Compression Without Ratio WATER-COOLEDMinimum Protection RPM SAT Saturated Suction Temperatures F Discharge Temp FRating Basis and Capacity Multipliers for R-12 and R-134a SST SDT Return GAS Temperature F913 922 931 Compressor Ratings R-12 UnitSST SDT 5H40 5H46 5H60 5H66 5H80 5H86 5H120 5H126 Compressor Ratings R-22 19.2 20.7 24.9 13.0 28.4 16.1 37.0 17.3 37.7 21.6 49.1 26.0 56.1 32.2 73.1 Compressor Ratings R-502 11.6 12.9 16.8 12.0 15.6 17.5 22.9 11.3 14.8 16.6 21.7 20.7 27.0 30.4 39.5 Compressor Ratings R-134a Compressor Ratings 507/404A Compr Weight Distribution, Condensing UnitsCompressor GPM CondWeight Distribution, Compressor Units See drawing, Table ComprNema Frame Size Capacity Control Reduction Steps Compr ContrModel CYL Capacity Control 5F40, 60 5H40, 46, 60, 66, 80 Initial and Final Unloading Oil Pressures 5F20, 5F30Pneumatic Compensation External Solenoid-Type Capacity Control 5F40 and 5F60 Compressors 5H40, 46, 60, 66, 80, 86 Bearing Head Valves Capacity Control Steps Heat Pump ModificationExternal Available Compressor SolenoidStarting Compressor Starting TorquesPkg No Belts 5F20-A181 Belt Drive PackagesModel Number Flywheel Compressor DimensionsCompressor Flywheel Dimensions Model Flywheel Width Pitch GroovesPage Booster R Factors Suct Discharge Temperature FControl Pressurestats for Low Stage Application CharacteristicsSelected Example SST SDT 5F,H Booster Ratings R-12SST SDT 5F,H Booster Ratings R-225H40 5H46 5H60 5H66 Cap Bhp 5F,H Booster Ratings R-502During Size Booster Compressor Starting DataUnloading Recommended MIN Motor Size HP Friction ComprCondenser Physical Data Max Condenser Tube Water VelocityCondenser Gpm at Various Water Velocities Condenser Water Circuiting THRWater to Glycol Flow Rate Correction