Water Circuiting Arrangements — The water cir- cuiting arrangement selected for 5F and 09RH condensers
Determine condenser loading factor by use of following formula:
depends on available condenser water pressure, temperature, quantity and source. Refer to Table 32.
LF =
THR
Refer to the Carrier System Design Manual for specific
SDT – 1.5 line loss – EWT
information and recommendations for refrigerant and water
=
153
piping.
Economics — Selection of a condenser requires balancing of certain economic variables, including:
1.First cost of
2.Operating costs.
3.Ratio between power costs and water costs.
Where first cost is the most important consideration, the best combination of compressor and condensers has the lowest total equipment cost.
If owning and operating costs are important, combination must be selected on basis of both considerations.
A condenser selection that permits operation of the system at a low condensing temperature, results in the lowest compres- sor motor brake horsepower and consequently, lowest operat- ing cost. A condenser selection that is heavily loaded requires the compressor to operate at a higher condensing temperature and results in higher compressor motor brake horsepower and operating cost.
For a given
Condenser Performance with Ethylene Gly- col — Increased use of closed circuit cooling towers has led to a corresponding increase in the need for shell and tube con- denser ratings for use with ethylene glycol. When towers are installed outdoors, a brine solution is required for freeze protec- tion during winter operations.
In most outdoor installations, specifications will call for a percentage of concentration of ethylene glycol or other brine solution. If concentration is not specified, it may be the choice of the contractor to determine a percentage of glycol concentra- tion to ensure against
To perform simplified selection, use Fig. 22 to convert a condenser water rating to a brine rating.
EXAMPLE:
Assume that a building with a
From product literature, selected unit will deliver 121 tons at 105.8 F saturated discharge temperature (SDT) and has 153 tons of heat rejection.
(105.8 – 1.5) – 85
= 19.3153 = 7.9
Where: EWT — Entering Water Temperature LF — Loading Factor
THR — Total Heat Rejection
The 85 F value is return water temperature from closed cir- cuit cooler.
Entering condenser rating data at loading factor of 7.9, 300 gpm are required to maintain design condensing tempera- ture. Next, determine the rise by:
Rise = THR x 24
Gpm
= 153 x 24 = 12.2 degrees 300
If a more precise rise is desired, go back and assume a slightly different condensing temperature, recalculate the load- ing factor and rise and repeat the procedure until a final balance is found.
For this example, condenser water pressure drop is approxi- mately 9.4 ft for the design 300 gpm flow rate. Using Fig. 22, flow rate correction can be determined for any glycol concen- tration versus water in shell and tube condensers.
Continuing with example, assume specifications required protection against
In a condenser system, the use of proper ethylene glycol brine concentration is important because of the phenomenon that commonly published freeze points are not freeze points but are the point of crystallization where the first crystals begin to form. Actual freezing into a solid occurs at much lower temperatures. For example, freeze point of 20% ethylene glycol is given as +16 F but does not become a solid until it reaches
Entering Fig. 22 at 0° F crystallization point, necessary concentration of glycol is either 32.5% by weight or 30% by volume. Next, determine glycol flow rate:
THR (tons) x Glycol Factor (GF)
Glycol Flow Rate =
Rise
Table 32 — Condenser Water Circuiting
WATER CIRCUITING | CONDENSER SIZE | CONDENSER | NORMAL USE | |
ARRANGEMENTS | CHARACTERISTICS | |||
|
| |||
Double Circuit | 5F20, 5F30 | High Water Quantity |
| |
4 Passes | 5F40, 5F60 | Cooling Tower | ||
Low Pressure Drop | ||||
3 Passes | All 09RH |
| ||
|
| |||
Single Circuit | 5F20, 5F30 | Low Water Quantity |
| |
8 Passes | 5F40, 5F60 | City or Well Water | ||
High Pressure Drop | ||||
6 Passes | All 09RH |
| ||
|
|
39