Carrier 09RH specifications Minimum Protection

Page 3

During compressor shutdown, gravity, thermal action and refrigerant absorption can result in a refrigerant and oil mixture in compressor crankcase. Gravity flow can be prevented by the use of recommended loops, but thermal action and the absorp- tion of refrigerant by lubricating oil cannot be prevented by piping design.

For the above reasons, the compressor must be controlled during idle times by one of the following methods.

MINIMUM PROTECTION — The minimum protection that Carrier will allow is shown in Fig. 1. Actuated control thermo- stat energizes crankcase heater and closes the liquid line solenoid valve simultaneously. With crankcase heaters

protection against liquid refrigerant accumulating in the compressor crankcase.

Do not use pumpdown control with dry expansion coolers as it may cause frost pinching or freeze-up. Do not use pumpdown control with dry expansion coolers if it is antici- pated that there will be short bursts of system operation, as this will result in a gradual loss of oil.

CONTROL POWER CIRCUIT

EVAP

THERMO AUX SOLENOID

energized, the crankcase temperature is always held above

HIGH-

CONT VALVE

shutdown temperature in the evaporator coil and there will be no refrigerant migration to the crankcase.

With this type of control, a control relay is required and crankcase heaters have to be energized when the compressor is not operating.

The control relay coil is located in parallel with the liquid line solenoid, and a normally open control relay contact is added in series with the compressor starter and other auxiliary safety devices.

When the thermostat calls for cooling, the solenoid valve opens and control relay is energized. This closes the relay contact and, if other safety devices are in their normal position, compressor will start. Simultaneously, the normally closed compressor auxiliary contact will open, removing crankcase heaters from the circuit.

When the thermostat is satisfied, the solenoid will close and control relay is deenergized. This opens relay contacts and compressor stops. This causes compressor auxiliary contacts to close, energizing crankcase heaters.

Specifications are sometimes written to call for a degree of protection greater than that afforded by the standard method. If this is the case, either single pumpout or automatic pumpdown control may be required.

CONTROL POWER

 

 

 

 

 

CONTROL

 

 

 

 

 

RELAY

 

 

 

EVAP

 

 

 

 

THERMO

AUX CONT

 

HIGH-

 

 

COMPR

SOLENOID

 

 

 

VALVE

 

PRESS.

 

 

 

STARTER

 

 

SWITCH

 

 

 

 

 

 

 

AUTO-

OIL

LOW-

CONTROL

 

OFF

RELAY

 

 

SWITCH

FAILURE

PRESS.

 

 

 

 

SWITCH

SWITCH

 

OIL FAILURE

OVERLOADS

 

 

 

 

 

 

 

 

SWITCH

 

COMPR

CRANKCASE

 

 

 

AUX CONT

HEATERS

 

 

 

Fig. 1 — Minimum Protection

AUTOMATIC PUMPDOWN CONTROL (Fig. 2) — Pump- down control is the most effective means of compressor control in keeping liquid refrigerant out of the crankcase on system shutdown.

In the basic pumpdown control sequence, the thermostat controls the liquid line solenoid valve to stop or start the flow of refrigerant to the evaporator as required.

The pumpdown control system permits compressor cycling if a system malfunction allows low side pressure to rise. Although this cycling is sometimes considered objectionable, it illustrates need for maintenance attention and provides positive

PRESS.

SWITCH

AUTO-

OIL

LOW-

 

OVERLOADS

OFF

 

 

 

SWITCH

FAILURE

PRESS.

 

COMPR

 

SWITCH

SWITCH

OIL FAILURE

 

STARTER

 

 

 

 

SWITCH

COMPR

CRANKCASE

HEATERS

AUX CONT

 

Fig. 2 — Automatic Pumpdown Control

SINGLE PUMPOUT CONTROL (Fig. 3) — Pumpout con- trol is not as effective as pumpdown control in keeping liquid refrigerant out of the crankcase. However, it is usually satisfac- tory when used with crankcase heaters if pumpdown is not acceptable.

Single pumpout control is similar to pumpdown control, except that a pumpout relay is added, a normally open com- pressor auxiliary contact is necessary, and energizing of crank- case heaters is required at end of each operating cycle.

CONTROL POWER CIRCUIT

PUMPOUT

RELAY

COIL

 

 

 

EVAP

 

 

 

 

THERMO AUX CONT

 

HIGH-

 

 

 

SOLENOID

 

 

 

COMPR

VALVE

 

PRESS.

 

 

 

STARTER

 

 

SWITCH

 

 

 

 

 

 

 

AUTO-

OIL

LOW-

COMP

 

 

OFF

 

 

AUX

 

 

SWITCH

FAILURE

PRESS.

 

 

CONTACT

 

 

 

SWITCH

SWITCH

OIL FAILURE

OVERLOADS

 

 

 

 

 

 

 

 

PUMPOUT

SWITCH

 

 

 

 

 

 

 

RELAY CONTACT

 

COMPR

CRANKCASE

 

 

 

AUX CONT

HEATERS

 

 

 

Fig. 3 — Single Pumpout Control

With single pumpout control, when the thermostat is satis- fied, the compressor pumps down once and stops. It starts again only when the thermostat calls for cooling. In pumpdown control, the compressor cycles only on the low-pressure switch, regardless of thermostat demands.

Do not use pumpout control with dry expansion coolers as it may cause frost pinching or freeze-up.

MANUAL PUMPDOWN — The compressor may be con- trolled manually without the use of pumpdown, or single pumpout control, and without crankcase heaters, provided the system is at all times under control of a qualified operator. The operator will pump down the system by use of manual valves and will keep liquid, suction and discharge valves closed when the machine is not operating.

3

Image 3 Contents
Application Data Heads Compression Exponent NFactors Compression Without Ratio WATER-COOLEDMinimum Protection RPM SAT Saturated Suction Temperatures F Discharge Temp FRating Basis and Capacity Multipliers for R-12 and R-134a SST SDT Return GAS Temperature F913 922 931 Compressor Ratings R-12 UnitSST SDT 5H40 5H46 5H60 5H66 5H80 5H86 5H120 5H126 Compressor Ratings R-22 19.2 20.7 24.9 13.0 28.4 16.1 37.0 17.3 37.7 21.6 49.1 26.0 56.1 32.2 73.1 Compressor Ratings R-502 11.6 12.9 16.8 12.0 15.6 17.5 22.9 11.3 14.8 16.6 21.7 20.7 27.0 30.4 39.5 Compressor Ratings R-134a Compressor Ratings 507/404A Compr Weight Distribution, Condensing UnitsCompressor GPM CondWeight Distribution, Compressor Units See drawing, Table ComprNema Frame Size Capacity Control Reduction Steps Compr ContrModel CYL Capacity Control 5F40, 60 5H40, 46, 60, 66, 80 Initial and Final Unloading Oil Pressures 5F20, 5F30Pneumatic Compensation External Solenoid-Type Capacity Control 5F40 and 5F60 Compressors 5H40, 46, 60, 66, 80, 86 Bearing Head Valves Capacity Control Steps Heat Pump ModificationExternal Available Compressor SolenoidStarting Compressor Starting TorquesPkg No Belts 5F20-A181 Belt Drive PackagesModel Number Flywheel Compressor DimensionsCompressor Flywheel Dimensions Model Flywheel Width Pitch GroovesPage Booster R Factors Suct Discharge Temperature FControl Pressurestats for Low Stage Application CharacteristicsSelected Example SST SDT 5F,H Booster Ratings R-12SST SDT 5F,H Booster Ratings R-225H40 5H46 5H60 5H66 Cap Bhp 5F,H Booster Ratings R-502During Size Booster Compressor Starting DataUnloading Recommended MIN Motor Size HP Friction ComprCondenser Physical Data Max Condenser Tube Water VelocityCondenser Gpm at Various Water Velocities Condenser Water Circuiting THRWater to Glycol Flow Rate Correction