When a capacity safety factor is used, the compressor is selected at its maximum speed to handle design load plus safe- ty factor. Multiplying factors for non-standard speeds are shown in Fig. 20.

Whether or not added capacity offered by the safety factor is incorporated at once is a matter of judgment. If it is, then the compressor will be operated at maximum speed at the start and any excess capacity achieved will be reflected in faster

pulldowns or lower temperatures. It is also a good practice to drive the machine at a speed that will provide slightly more rated capacity than is required by design load. Additional speed-up available will then constitute reserve capacity in the event it is needed. Motors should be sized to run the compres- sor at maximum speed to forestall any motor changes, should this maximum compressor speed be required in the future.

Fig. 18 — Flow Diagrams for Common Multistage Systems

(Not to be used as Piping Diagrams)

30

Image 30
Contents Application Data Compression Without Ratio WATER-COOLED Compression Exponent NFactors HeadsMinimum Protection SAT Saturated Suction Temperatures F Discharge Temp F RPMSST SDT Return GAS Temperature F Rating Basis and Capacity Multipliers for R-12 and R-134a913 922 931 Compressor Ratings R-12 UnitSST SDT 5H40 5H46 5H60 5H66 5H80 5H86 5H120 5H126 Compressor Ratings R-22 19.2 20.7 24.9 13.0 28.4 16.1 37.0 17.3 37.7 21.6 49.1 26.0 56.1 32.2 73.1 Compressor Ratings R-502 11.6 12.9 16.8 12.0 15.6 17.5 22.9 11.3 14.8 16.6 21.7 20.7 27.0 30.4 39.5 Compressor Ratings R-134a Compressor Ratings 507/404A Cond Weight Distribution, Condensing UnitsCompressor GPM ComprWeight Distribution, Compressor Units See drawing, Table ComprNema Frame Size Capacity Control Reduction Steps Compr ContrModel CYL Initial and Final Unloading Oil Pressures 5F20, 5F30 Capacity Control 5F40, 60 5H40, 46, 60, 66, 80Pneumatic Compensation External Solenoid-Type Capacity Control 5F40 and 5F60 Compressors 5H40, 46, 60, 66, 80, 86 Bearing Head Solenoid Capacity Control Steps Heat Pump ModificationExternal Available Compressor ValvesCompressor Starting Torques StartingBelt Drive Packages Pkg No Belts 5F20-A181Flywheel Width Pitch Grooves Flywheel Compressor DimensionsCompressor Flywheel Dimensions Model Model NumberPage Suct Discharge Temperature F Booster R FactorsCharacteristics Control Pressurestats for Low Stage ApplicationSelected Example 5F,H Booster Ratings R-12 SST SDT5F,H Booster Ratings R-22 SST SDT5F,H Booster Ratings R-502 5H40 5H46 5H60 5H66 Cap BhpRecommended MIN Motor Size HP Friction Compr Booster Compressor Starting DataUnloading During SizeCondenser Physical Data Max Condenser Tube Water VelocityCondenser Gpm at Various Water Velocities THR Condenser Water CircuitingWater to Glycol Flow Rate Correction