Carrier 09RH specifications External Solenoid-Type Capacity Control

Page 23

Control Pressurestats — Dual pressurestats are furnished with all 5F,H compressors. They are often referred to as high- and low-pressure cutouts. Their function is to cut the circuit to the holding coil of the compressor motor starter when pressure setting limits are exceeded.

The high pressurestat has an operating range from 50 to 450 psig with a differential range from 170 to 235 psig (adj). The low pressurestat has an operating range from 20 in. Hg to 60 psig and a differential range from 60 to 90 psig (adj).

Pressurestat settings should be adjusted on the job to meet particular operating conditions for which the compressor(s) have been selected. Directions for setting these pressurestats are in the 5F,H Installation Instructions.

Permanently Unloaded Cylinders — Operation of an open- drive compressor with its cylinders permanently unloaded requires field modification. The 5F60, 5H40 and 5H60 com- pressors can operate with one cylinder unloaded; 5H80 and 5H120 compressors can operate with 2 cylinders unloaded. Compressors are modified by removing the suction valve and suction valve springs from the cylinder(s) shown in Fig. 4.

ELECTRIC SOLENOID VALVE CAPACITY CON- TROL — Closer control of a conditioned space or medium can be realized by activating the cylinder unloaders directly in response to an external step controller activated by solenoid valves. A temperature sensing controller activates the electric solenoid valves. Refer to Fig. 10 for an operating concept using an external electric solenoid-type capacity control. All compo- nents external to the compressor must be field supplied. Modi- fications required for standard sequence are as follows:

5F20 and 5F30 Compressors — Modifications are not required to the 5F20 and 5F30 compressors. See Fig. 4 and 11. Securely attach a ported solenoid valve to compressor to mini- mize line vibration. Connect a 1/4-in. steel tubing or high- pressure flexible hose, KA73RR025, between the compressor and solenoid valve.

5F40 and 5F60 Compressors

1.Remove the capacity control handhole cover. Remove the hydraulic relay and all tubing. As shown on Fig. 12, drill and tap 3 holes on the bottom side of the cover and 2 on the front. No hole is required at point A on 5F40 com-

pressors. Plug 5 cover holes that connected cover to the relay. Plugs are 1/8 NPT.

2.Install cover with a new cover gasket 5F40-1042.

3.Mount solenoid valves on a sturdy bracket attached to the handhole cover using stud bolts on the compressor.

4.Connect external oil lines as shown in Fig. 12 and 13. Steel tubing and compression fittings are recommended.

5H40 Through 5H86 Compressors — Standard compressors 5H40 through 5H86 built after Serial No. G103460 (July 1971) may be modified for electric solenoid unloading without addi- tional machining. Proceed as follows: (See Fig. 4, 13, 14, and 15).

1.Remove pump end cover only from the compressor.

2.Using the pump end cover gasket (Part No. 5H40-1423)

as a guide, make a blank metal disc (1/32 to 1/16-in. thick), making holes for bolts only.

3.Reinstall the pump end cover using 2 new 5H40-1423 gaskets, one on each side of the blank disc. This isolates the capacity control cover.

4.Mount solenoid valves and run oil lines.

5.To minimize vibration, mount the valves on a bracket attached to the compressor.

5H120, 126 Compressors — Following modifications are required to electrically unload 5H120, 126 compressors.

1.After closing the compressor service valves and reducing refrigerant pressure to the atmosphere, remove pump end bearing head.

2.Remove hydraulic relay assembly by removal of two

5/16-in.-18 socket head screws. Make a blank metal disc using a hydraulic relay gasket (5H120-3351) as a guide.

Using 1/32 to 1/16-in. thick metal, cut holes in the disc for dowel pins only. (Do not cut five 9/32-in. diameter holes.) Reinstall relay assembly using 2 new 5H120-3351 gaskets, one on each side of the metal disc. Torque 5/16-in. socket head screws evenly to 16 to 20 lb-ft.

3.Reinstall the bearing head using extreme care not to damage the oil pump tang. Align with recess in the end of the crankshaft. Do not force on.

4.Mount solenoid valves and run oil lines. See Fig. 4, 13, and 16.

5.To minimize vibration, mount the valves on a bracket attached to the compressor.

Valves — The following 3-way valves have been used in the field and are listed as a guide:

Alco Controls No. 702RA001.

Also Controls No. S608-1.

Sporlan Type 180.

SENSING

PROPORTIONING TYPE

BULB

ELECTRIC CONTROLLER

MOTOR

1 2

2-STEP SEQUENCE CONTROLLER

SOLENOID

VALVE

CLUSTER

Fig. 10 — External Solenoid-Type

Capacity Control

OIL FILLER PLUG

1/4” NPT OIL PUMP PRESS. CONN.

SOLENOID

VALVE

3/8” NPT OPENING TO

CRANKCASE

TO OIL COOLER

MAGNETIC PLUG

Fig. 11 — 5F20 and 5F30 Compressor

23

Image 23
Contents Application Data Heads Compression Exponent NFactors Compression Without Ratio WATER-COOLEDMinimum Protection RPM SAT Saturated Suction Temperatures F Discharge Temp FRating Basis and Capacity Multipliers for R-12 and R-134a SST SDT Return GAS Temperature F913 922 931 SST SDT Compressor Ratings R-12Unit 5H40 5H46 5H60 5H66 5H80 5H86 5H120 5H126 Compressor Ratings R-22 19.2 20.7 24.9 13.0 28.4 16.1 37.0 17.3 37.7 21.6 49.1 26.0 56.1 32.2 73.1 Compressor Ratings R-502 11.6 12.9 16.8 12.0 15.6 17.5 22.9 11.3 14.8 16.6 21.7 20.7 27.0 30.4 39.5 Compressor Ratings R-134a Compressor Ratings 507/404A Compr Weight Distribution, Condensing UnitsCompressor GPM CondNema Frame Size Weight Distribution, Compressor Units See drawing, TableCompr Model CYL Capacity Control Reduction StepsCompr Contr Capacity Control 5F40, 60 5H40, 46, 60, 66, 80 Initial and Final Unloading Oil Pressures 5F20, 5F30Pneumatic Compensation External Solenoid-Type Capacity Control 5F40 and 5F60 Compressors 5H40, 46, 60, 66, 80, 86 Bearing Head Valves Capacity Control Steps Heat Pump ModificationExternal Available Compressor SolenoidStarting Compressor Starting TorquesPkg No Belts 5F20-A181 Belt Drive PackagesModel Number Flywheel Compressor DimensionsCompressor Flywheel Dimensions Model Flywheel Width Pitch GroovesPage Booster R Factors Suct Discharge Temperature FControl Pressurestats for Low Stage Application CharacteristicsSelected Example SST SDT 5F,H Booster Ratings R-12SST SDT 5F,H Booster Ratings R-225H40 5H46 5H60 5H66 Cap Bhp 5F,H Booster Ratings R-502During Size Booster Compressor Starting DataUnloading Recommended MIN Motor Size HP Friction ComprCondenser Gpm at Various Water Velocities Condenser Physical DataMax Condenser Tube Water Velocity Condenser Water Circuiting THRWater to Glycol Flow Rate Correction