Carrier Electric Heater Data, Electric Heater Used with, Branch Circuit Unit 88EN Unit 50AH

Page 10

Electrical data (cont)

ELECTRIC HEATER DATA

ELECTRIC HEATER

USED WITH

V-PH

CAP. (kW)

 

BRANCH CIRCUIT

 

UNIT 88EN

UNIT 50AH

(60 Hz)

Heater Amps

MCA

 

MOCP (Amps)

 

 

0050CA01

 

240-1

5.0

20.8

26.0

 

30

0075CA01

 

240-1

7.5

31.3

39.1

 

40

0115CA01

024, 036

240-1

11.5

47.9

59.9

 

60

0075EA01

1-Stage Heat

208-3

5.6

15.6

19.5

 

20

 

240-3

7.6

18.0

22.6

 

25

 

 

 

1150EA01

 

208-3

11.3

31.2

39.0

 

40

 

240-3

15.0

36.1

45.1

 

50

 

 

 

0100EA01

 

208-3

7.5

20.8

26.0

 

30

 

240-1*

10.0

41.7

52.1

 

60

 

 

240-3

10.0

24.1

30.1

 

35

0150EA01

 

208-3

11.3

31.2

39.0

 

40

 

240-1*

15.0

62.5

78.1

 

80

 

 

240-3

15.0

36.1

45.1

 

50

0200EA01

 

208-3

15.0

41.7

52.1

 

60

048, 060

240-1*

20.0

83.3

104.2

 

110

 

2-Stage Heat

240-3

20.0

46.9

58.6

 

60

0300EA01

 

208-3

22.5

62.5

78.2

 

80

 

240-3

30.0

72.2

90.2

 

100

 

 

 

0300CA01

 

240-1

30.0

124.0

155.0

 

175

0100FA01

 

480-3

10.0

12.0

15.0

 

15

0150FA01

 

480-3

15.0

18.1

22.6

 

25

0200FA01

 

480-3

20.0

24.1

30.1

 

35

0300FA01

 

480-3

30.0

36.1

45.1

 

50

LEGEND

MCA — Minimum Circuit Ampacity

MOCP — Maximum Overcurrent Circuit Protection

(Fuses or Circuit Breaker)

*May be field converted to single-phase units, see electric heat installation instructions. NOTE: Separate power source is required for all heaters. Control from base unit 50AH (24 v).

10

Image 10
Contents Features/Benefits Product DataModel number nomenclature Table of contentsARI* capacity ratings Physical data Operating Weight Distribution Center of GravityDimensions Unit88EN Electric Heat Module Field-installed accessoriesAccessory Unit DuctBase unit dimensions Unit Component LocationsGross Cooling Capacities Selection procedure with examplePerformance data SHCUnit Size 50AH CFM Evaporator FAN PerformanceESP Condenser FAN Performance Belt Drive Evaporator FAN PerformanceUnit Cond Electrical data Unit Voltage Range Compressor FAN Motors Power SupplyControls Electric Heater Unit MIN Unit CFM Unit 88ENBranch Circuit Unit 88EN Unit 50AH Electric Heater DataElectric Heater Used with MCATypical wiring schematic CLO LOROUTDOOR-AIR Temperature Operating Limits F Typical piping and wiringApplication data Guide specifications Indoor Packaged UnitPage Carrier Corporation Syracuse, New York 204