Carrier 50AH manual Belt Drive Evaporator FAN Performance, Condenser FAN Performance, Unit Cond

Page 8

Performance data (cont)

BELT DRIVE EVAPORATOR FAN PERFORMANCE

(Special Order Only, Pricing and ordering on related price pages.)

 

 

 

UNIT SIZE — 50AH

 

 

CFM

 

048

 

060

 

ESP

 

Fan kW

ESP

 

Fan kW

1800

 

 

1850

 

 

1900

 

 

1950

.81

 

1.03

 

2000

.72

 

1.05

 

2050

.63

 

1.07

 

2100

.55

 

1.08

1.02

 

1.17

2150

.47

 

1.11

.93

 

1.21

2200

.42

 

1.14

.84

 

1.24

2250

.34

 

1.17

.75

 

1.27

LEGEND

ESP — External Static Pressure (in. wg)

kW — Total Fan Power Motor Input (kilowatts)

NOTE: Pulley setting must be adjusted to limit cfm to 450 cfm/ton maximum. Unit operation beyond that limit may result in blow-off and condensate problems.

CONDENSER FAN PERFORMANCE

UNIT

COND

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.0

 

0.1

 

0.2

 

0.3

 

0.4

 

 

0.5

 

0.6

50AH

CFM

 

 

 

 

 

 

 

 

 

Turns

 

kW

Turns

kW

Turns

 

kW

Turns

 

kW

Turns

 

kW

Turns

 

kW

Turns

 

kW

 

1525

Note 4

 

.66

 

 

 

 

 

 

024

1475

 

Note 4

 

.64

 

 

 

 

 

1400

 

 

Note 4

 

.63

 

 

 

 

 

1350

 

 

 

Note 4

 

.62

 

 

 

 

1300

 

 

 

 

Note 4

 

.62

 

 

 

1650

2

 

.84

 

 

 

 

 

 

 

1600

 

2

 

.82

 

 

 

 

 

 

1550

 

 

2

 

.80

 

 

 

 

036

1500

3

 

.72

 

 

2

 

.78

1

 

.84

 

 

1450

4

 

.63

3

 

.70

 

 

2

 

.76

1

 

.83

 

 

 

 

 

 

 

 

 

 

1400

 

4

 

.61

3

 

.68

 

 

 

1

 

.81

 

1350

5

 

.51

 

 

3

 

.67

 

2

 

.73

 

 

1300

 

5

 

.50

4

 

.57

 

3

 

.65

 

2

 

.71

 

2700

2

 

.90

 

 

 

 

 

 

 

2600

 

2

 

.87

 

 

 

 

 

048

2550

3

 

.81

 

 

 

 

 

 

2450

 

3

 

.77

2

 

.83

1

 

.89

 

 

 

 

2350

 

 

 

2

 

.80

1

 

.86

 

 

 

2300

4

 

.68

 

3

 

.74

 

 

0

 

.90

 

 

2200

 

4

 

.66

 

 

2

 

.77

1

 

.82

0

 

.86

 

3100

3

 

1.34

 

 

 

 

 

 

 

3000

 

3

 

1.32

 

 

 

 

 

 

2900

 

 

 

2

 

1.39

 

 

 

 

2850

4

 

1.11

 

3

 

1.24

 

 

 

 

 

2750

 

4

 

1.07

 

 

2

 

1.32

 

 

060

2700

 

 

 

3

 

1.17

 

 

 

2650

 

 

 

 

 

 

1

 

1.37

 

 

 

 

 

 

 

 

 

2600

5

 

.95

 

4

 

1.01

 

 

2

 

1.26

 

 

2550

 

 

 

 

3

 

1.12

 

 

 

2500

 

5

 

.92

 

 

 

 

 

 

2450

 

 

 

4

 

.97

 

 

2

 

1.21

 

2400

 

 

5

 

.90

 

 

3

 

1.08

 

LEGEND

kW — Total Fan Motor Power Input (kilowatts)

NOTES:

1.Above fan performance is based upon coil and deducted casing losses only.

2.External static pressure (ESP) is measured in inches water gage (in. wg).

3.Interpolation is permissible. Do not extrapolate.

4.Condenser fan on unit size 024 only, is direct drive.

5.Minimum one turn open of motor pulley is required on unit sizes 036 and 060.

6.Number of turns open applies to field setting of motor pulley.

7.Factory setting as follows: 036, 4 turns open; 048, 2 turns open; 060, 5 turns open.

8.Care should be taken when hoods and/or louvers are installed to avoid condenser air recirculation.

8

Image 8
Contents Features/Benefits Product DataARI* capacity ratings Table of contentsModel number nomenclature Operating Weight Distribution Center of Gravity DimensionsPhysical data UnitField-installed accessories Accessory88EN Electric Heat Module Unit DuctBase unit dimensions Unit Component LocationsSelection procedure with example Performance dataGross Cooling Capacities SHCESP Evaporator FAN PerformanceUnit Size 50AH CFM Unit Cond Belt Drive Evaporator FAN PerformanceCondenser FAN Performance Unit Voltage Range Compressor FAN Motors Power Supply ControlsElectrical data Electric Heater Unit MIN Unit CFM Unit 88ENElectric Heater Data Electric Heater Used withBranch Circuit Unit 88EN Unit 50AH MCATypical wiring schematic CLO LORApplication data Typical piping and wiringOUTDOOR-AIR Temperature Operating Limits F Guide specifications Indoor Packaged UnitPage Carrier Corporation Syracuse, New York 204