Carrier 48XL Routing Power Leads Into Unit, Connecting Ground Lead to Ground Screw

Page 12

Table2- MaximumGas Flow Capacity*

NOMINAL

INTERNAL

 

 

 

 

 

 

LENGTH OF PIPE ft (m)'{"

 

 

 

 

 

IRON PIPE

DIAMETER

10

20

30

40

50

60

70

80

90

100

125

150

175

200

SIZE (IN.)

(IN.)

(3.0)

(6.1)

(9.1)

(12.1)

(15.2)

(18.3)

(21.3)

(24.4)

(27.4)

(30.5)

(38.1)

(45.7)

(53.3)

(61.0)

 

1/2

.622

175

120

97

82

73

66

61

57

53

50

44

40

--

--

 

3/4

.824

360

250

200

170

151

138

125

118

110

103

93

84

77

72

 

1

1.049

680

465

375

320

285

260

240

220

205

195

175

160

145

135

1

- 1/4

1.380

1400

950

770

600

580

530

490

460

430

400

360

325

300

280

1

- 1/2

1.610

2100

1460

1180

990

900

810

750

690

650

620

550

500

460

430

*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-IN. W.C. (based on a 0.60 specific gravity gas). Refer to Table, NFPA 54/ANSI Z223,1.

1- This length includes an ordinary number of fittings.

ROUTING POWER LEADS INTO UNIT

Use only copper wire between disconnect and unit. The high voltage leads should be in a conduit until they enter the duct panel;

conduit termination at the duct panel must be watertight. Run the

high-voltage leads through the power entry knockout on the power entry side panel. See Fig. 5 and 6 for location and size. For

single-phase units, connect leads to the black and yellow wires.

CONNECTING GROUND LEAD TO GROUND SCREW

Connect the ground lead to the chassis using the ground screw on the control plate near the inducer switch (See Fig. 13).

ROUTING CONTROL POWER WIRES

For detailed instruction on the low voltage connections to the User Interface (UI), refer to the UI installation guide.

Form a drip-loop with the control leads before routing them into the unit. Route the low voltage control leads through grommeted,

low-voltage hole provided into unit (See Fig. 5 and 6). Connect user interface leads to unit control power leads as shown in Fig. 14.

The unit transformer supplies 24-v power for complete system

including accessory electrical heater. Transformer is factory wired for 230-v operation. If supply voltage is 208-v, rewire transformer

primary as described in Special Procedures for 208-v Operation section.

The furnace board is fused by a board-mounted automotive fuse

placed in series with transformer SEC1 and R circuit. The C circuit

of transformer circuit is referenced to chassis ground through a

printed circuit run at SEC2 and gas valve grounding wire. Check to

be sure control board is mounted securely using both

factory-installed screws.

ACCESSORY INSTALLATION

A. Outdoor Air Thermistor (OAT)

EQUIPMENT OPERATION HAZARD

The installation of an outdoor temperature sensor using the

Infinity control board OAT terminals is required. Many

Infinity features (auto humidity control, comfort rollback, ETC.) will be lost if the OAT is not connected.

For detailed mounting instructions for the OAT sensor,

please refer to TSTATXXSEN01-B installation instructions

(catalog no. 63TS-TAI3): Procedures 1 through 3.

The OAT input is used to supply outdoor temperature data for

system level functions and for temperature display on User

Interface (UI). Using two wires of the field-supplied thermostat wire cable, wire the ends of the two black OAT pigtails. Wire the

opposite ends of these two wires to the OAT provided with the UI. There is no polarity to be observed.

NOTE: Mis-wiring OAT inputs will not cause damage to either

Infinity control or thermistor. If the thermistor is wired incorrectly,

no reading will appear at UI. Re-wire thermistor correctly for normal operation.

B. Humidifier Connections

The furnace control board terminal marked HUM is provided for

low voltage (24-vac) control of a humidifier. No humidistat is required as UI monitors indoor humidity.

When commanded to operate humidifier, the unit control will

energize the HUM output to turn humidifier on and de-energize

HUM output to turn humidifier off. Wire HUM and COM

terminals directly to humidifier as shown in Fig. 14.

C. Electronic Air Cleaner

Electronic Air Cleaner terminals are provided on the Infinity

Control Board (EAC-I and EAC-2). While these terminals can be

used to power a 230V EAC, it is recommended that any EAC be

installed per the EAC installation instructions and connected

separately to a standard II5V or 230V outlet with an airflow sensor to control operation of the EAC.

SPECIAL PROCEDURES FOR 208-V OPERATION

Be sure unit disconnect switch is open.

Disconnect the black primary lead from the transformer. See unit wiring label (See Fig. 16 and 17).

Connect the black primary lead to the transformer terminal labeled 208-v.

12

Image 12
Contents Installation Unit Operation and Safety Hazard ElectricalshockhazardIdentify Unit Inspect ShipmentIN. MM IN.MMNumber 024-030Left Side View Frontview Rightsideview Front View Compressors Furnace SectionBurner Orifice No. Qty.Drill Size RETURN-AIR Filters ThrowawayClearances PlaceSelect and Install Ductwork See Detail a Install Flue Hood Install Gas PipingProvide for Condensate Disposal Carbon Monoxide Poisoning HazardInstall Electrical Connections Fire or Explosion HazardHIGH-VOLTAGE Connections Electrical Shock HazardRouting Power Leads Into Unit Connecting Ground Lead to Ground ScrewRouting Control Power Wires Accessory InstallationGround Screw OAT Black Wires Field ConnectionRequired Factory ConnectedUnit Start-Up and Troubleshooting FIRE, EXPLOSION,ELECTRICALSHOCK HazardVerify Motor Winding Section Motor Turns SlowlyDUSO0003 DU500095 Status Code 22 Abnormal FLAME-PROVING Signal Status Code 23 Pressure Switch did not OpenStatus Code 25 Invalid Model Selection or Setup Error Status Code 33 Limit Circuit FaultIndoor Airflow Adjustments Unit Operation HazardAIR Conditioner Sequence of Operation Cooling Operation Utility Interface with Infinity ControlAmber LED Operation Fault Flash Possible Cause Action Code Rated HeatingHigh Stage Low Stage Dehumidification Mode GAS Heat Mode and AdjustmentsInfinity Controlled LOW Ambient Cooling Sequence of OPERATION-GAS HeatFire and Unit Damage Hazard U.S.ACanada ExampleCheck GAS Input Propane GAS Check Burner FlameStart-Up Adjustments Check for Refrigerant LeaksTo USE Cooling Charging Charts Refrigerant ChargeNo Charge LOW Charge CoolingField Connection Required Blackwires FactorywiresprovidedLimit Switch Indoor Fan and MotorBurner Ignition Main BurnersElectrical Controls and Wiring Pressure Switches Refrigerant CircuitOutdoor Coil, Indoor Coil, and Condensate Drain Pan Outdoor FanRefrigerant System Pressure Switch PROTECTION-REFRIGERANT Control Fault230V Line Power Disconnect Detection Temperature ThermistorsFailed Thermistor Default Operation Thermistor Sensor ComparisonOCT Page Symptom RemedyTable lO--Troubleshooting Chart Cont-Gas Remove and Store in Job File